2 | Safety
14
B1510622_en | Operating instructions Firewood boiler S4 Turbo
WARNING
When inspecting and cleaning the boiler with the main switch on:
Serious injuries possible due to boiler/individual components starting up
automatically (induced draught)!
Before inspection and cleaning work in/on the boiler:
r
Allow the fuel in the boiler to burn off
r
Allow boiler to cool off and switch off main switch
NOTICE
Automatic ignition set incorrectly or not carried out
Possible damage to equipment from frost, etc.
Take the following precautions:
r
Check the start time that has been set for automatic ignition
r
After a short time, ensure that automatic ignition has been carried out successfully
Ä
Due to differing fuel compositions, Froling cannot guarantee successful automatic
ignition. The manufacturer/supplier is not responsible for resulting damage.
2.9 Emergency procedure
2.9.1 Overheating of the system
If the system overheats and the safety devices fail to operate, proceed as follows:
NOTICE! Do not under any circumstances switch off the main switch or disconnect
the power supply.
r
Keep all the doors on the boiler closed
r
Switch boiler off by tapping “Boiler OFF”
r
Open all mixing valve taps, switch on all pumps.
Ä
The Froling heating circuit control takes on this function in automatic operation.
r
Leave the boiler room and close the door
r
Open any thermostatic valves on the radiator and ensure sufficient heat dissipation
from the rooms
If the temperature does not drop:
r
Contact the installer or Froling customer services