21
7425MUM753
Model: CWE-Q
- Use and Maintenance Manual
Rev. 15
5.8
P
ARAMETERS CHANGING
NOTE
The parameters setting can only be changed at a higher level of programming of the
electronic control: please request the password by contacting our company.
After contact our company, follow this procedure:
•
Starting from the main screen press
for 4 seconds;
•
Use the
key to reach the
User
and press
;
•
Use
or
keys to scroll the list;
•
Press
to reach the label
PDd1
;
•
Then press
and insert using
or
keys the password
•
Press
to confirm;
•
The complete list of parameter will be available for change;
•
Press
to return to the main screen.
5.9
S
ETTING THE DATE AND TIME
Follow this procedure:
•
Starting from the main screen press
for 4 seconds;
•
Use the
key to reach the
rtc
menu;
•
Press
and using
or
keys insert the date and time;
•
Press
to confirm;
•
Press
to return to the main screen.
5.10 L
OW WATER TEMPERATURES
(<32°F//0°C)
If it was not anticipated that the chiller unit offered was to produce water at
temperatures close to 0°C//32°F, or below, you should contact our company.
To achieve temperatures that are negative, or near zero, it is necessary to use anti-
freeze (ethylene glycol) in percentages that depend on the desired temperature; it is
also necessary to change the calibration of safety devices.
NOTE
The safety devices setting can only be changed at a higher level of programming of
the electronic control: please request the password by contacting our company.
CWE-Q
units can operate with water and ethylene glycol mixtures up to a
concentration of 40%.
In case of RH and/or RA1 / RA2 / RA3 (HEATING or ANTI-FREEZE RESISTORS)
option installed on the machine, check that the Chiller setpoint does not conflict with
the one chosen for this option. Contact our Service Assistance to request
instructions.
1
Contact our company.