5.7.2 Table of alarm codes
Code
Alarm description
Type of rearm
AL01
Water low temperature
Semiautomatic
AL02
Water high temperature
Semiautomatic
AL03
Water differential pressure switch
Manual
AL04
High pressure from pressure switch
Manual
AL06
High pressure from pressure transducer
Automatic
AL07
Low pressure from pressure transducer
Semiautomatic
AL09
Antifreeze
Manual
AL31
Level switch
Manual
AC21
Thermal protection compressor
Manual
AC25
Thermal protection fans
Manual
AC26
Thermal protection pump 1 (optional)
Manual
AC27
Thermal protection pump 2 (optional)
Manual
AL11
High temperature refrigerant discharge
Automatic
AL13
Working limit
Automatic
AL14
Defrost
Automatic
AL27
Phase sequence alarm
Manual
ES01
Inlet water temperature probe
Automatic
ES02
Ambient temperature probe
Automatic
ES03
Outlet water temperature probe
Automatic
ES11
Discharge temperature probe
Automatic
ES12
Suction temperature probe
Automatic
ES14
Temperature probe
Automatic
ES15
Auxiliary probe 1
Automatic
ES16
Auxiliary probe 2
Automatic
AL15
I/O configuration alarm
Automatic
5.7.3 Displaying alarm history
To display the alarm history:
•
Press the
key;
•
Press
at
Hi St
menu;
•
Use
keys to scroll the list of alarms;
•
Press
again until you return to the main screen.