Start-up
14 – EN
ACT ES 20 – 500
5.3 Start-up and shut down
ACT ES 200-500 3phase
- For short periods of inactivity, (max 2-3 days) we recommend that
power is maintained to the dryer and the control panel. Otherwise, before re-starting the
dryer, it is necessary to wait at least 2 hours for the compressor crankcase heater to heat
the oil of the compressor.
Start-up (refer to paragraph 7.1 Control Panel)
Check the condenser for cleanliness.
Turn ON the switch - pos. 1 on the control panel.
Ensure that electronic instrument is ON.
If the temperature displayed on the electronic instrument is sufficiently high, verify that the refrigerating
compressor starts within a few minutes.
NOTE!
– With low temperatures, the refrigerating compressor
will remain OFF.
Wait a few minutes; verify that the DewPoint temperature displayed on electronic instrument is correct
and that the condensate is regularly drained.
Switch on the air compressor.
Shut down (refer to paragraph 7.1 Control Panel)
Check that the DewPoint temperature indicated on the electronic instrument is within range.
Shut down the air compressor.
After a few minutes, turn OFF the switch - pos. 1 on the control panel.
ACT ES 200-500 3phase
- Dryer remote control ON-OFF
Remove jump on terminals 1 and 2 of the terminal strip and wire a dry contact – potential free (see
electric diagram).
Turn ON the switch - pos. 1 on the control panel.
Close contact on terminal 1 and 2 switch ON the dryer
Open contact on terminal 1 and 2 switch OFF the dryer
Use dry contacts only (potential free) suitable for 230 Vac. Assure an adequate isolation of
potentially dangerous powered parts.
NOTE :
A DewPoint within 32°F (0°C) e +50°F (+10°C) displayed on electronic instrument is correct
according to the possible working conditions (flow-rate, temperature of the incoming air, ambient
temperature, etc.).
In the ECO operating mode (Energy Saving, ESS=YES – see section 7.12.7), the refigerating compressor is
switched ON and OFF by the electronic instrument, according to thermal load applied to the dryer. The dryer
must remain ON during the full usage period of the compressed air, even if the air compressor works
intermittently.
The number of starts/stops by pressing the ON-OFF switch - pos. 1 of control panel should
be limited to 6 per hour
.
The dryer must stop running for at least 5 minutes before being started up again.
Frequent starts may cause irreparable damage.
The user is responsible for compliance with these rules.
Summary of Contents for ACT ES 20-500
Page 15: ...Technical data ACT ES 20 500 15 EN 6 Technical data 6 1 Technical data ACT ES 20 200 1 115 60 ...
Page 16: ...Technical data 16 EN ACT ES 20 500 6 2 Technical data ACT ES 20 500 1 230 60 ...
Page 17: ...Technical data ACT ES 20 500 17 EN 6 3 Technical data ACT ES 200 500 3phase 3 460 60 ...
Page 18: ...Technical data 18 EN ACT ES 20 500 6 4 Technical data ACT ES 200 500 3phase 3 575 60 ...
Page 37: ...Attachments ACT ES 20 500 37 EN 9 1 Dryers dimensions 9 1 1 ACT ES 20 50 ...
Page 38: ...Attachments 38 EN ACT ES 20 500 9 1 2 ACT ES 75 ...
Page 39: ...Attachments ACT ES 20 500 39 EN 9 1 3 ACT ES 100 150 ...
Page 40: ...Attachments 40 EN ACT ES 20 500 9 1 4 ACT ES 200 250 ...
Page 41: ...Attachments ACT ES 20 500 41 EN 9 1 5 ACT ES 300 350 ...
Page 42: ...Attachments 42 EN ACT ES 20 500 9 1 6 ACT ES 400 500 ...
Page 43: ...Attachments ACT ES 20 500 43 EN 9 1 7 ACT ES 200 250 3phase ...
Page 44: ...Attachments 44 EN ACT ES 20 500 9 1 8 ACT ES 300 350 3phase ...
Page 45: ...Attachments ACT ES 20 500 45 EN 9 1 9 ACT ES 400 500 3phase ...
Page 46: ...Attachments 46 EN ACT ES 20 500 9 2 Exploded views 9 2 1 ACT ES 20 30 ...
Page 47: ...Attachments ACT ES 20 500 47 EN 9 2 2 ACT ES 50 ...
Page 48: ...Attachments 48 EN ACT ES 20 500 9 2 3 ACT ES 75 ...
Page 49: ...Attachments ACT ES 20 500 49 EN 9 2 4 ACT ES 100 ...
Page 50: ...Attachments 50 EN ACT ES 20 500 9 2 5 ACT ES 125 150 ...
Page 51: ...Attachments ACT ES 20 500 51 EN 9 2 6 ACT ES 200 250 ...
Page 52: ...Attachments 52 EN ACT ES 20 500 9 2 7 ACT ES 300 350 ...
Page 53: ...Attachments ACT ES 20 500 53 EN 9 2 8 ACT ES 400 500 ...
Page 54: ...Attachments 54 EN ACT ES 20 500 9 2 9 ACT ES 200 250 3phase ...
Page 55: ...Attachments ACT ES 20 500 55 EN 9 2 10 ACT ES 300 350 3phase ...
Page 56: ...Attachments 56 EN ACT ES 20 500 9 2 11 ACT ES 400 500 3phase ...
Page 65: ...Blank pages ACT ES 20 500 65 EN 10 Blank pages ...
Page 66: ...Blank pages 66 EN ACT ES 20 500 ...