Rev. Tarihi:25.05.2016 Rev.No:9 Dok. No: KLV.004.ENG
FdLF
no
no
no
no
Pr2
“doF'' delay enabled also for the first switching off
no/YES
odo
20
20
20
20
Pr2
Regulation delay on start-up
0 ÷ 255 sec.
LSE
-40
-40
0,3
0,3
Pr2
Minimum set point for compressors
PA04 ÷ HSE
HSE
10
50
7,2
100
Pr2
Maximum set point for compressors
LSE ÷ PA20
Pb
4
8
2.0
24
Pr2
Proportional band or neutral zone
width for fans
0.1÷10.0 bar/30.0°C/80
PSI/50°F
ESF
0
0
0
0
Pr2
Energy saving value for fans
- + 20.0 bar/- + 50.0°C / -
+ 300
PSI/- + 90°F
Fon
15
15
15
15
Pr2
Time delay between the insertion of two different fans
0 ÷ 255 sec.
FoF
5
5
5
5
Pr2
Time delay between switching off of two different fans
0 ÷ 255 sec.
LSF
10
50
7,2
100
Pr2
Lower set for fans
PA04 ÷ HSE
HSF
60
140
27,8
404
Pr2
Higher set for fans
LSE ÷ PA20
Pao
30
30
30
30
Pr2
Alarm probe exclusion at power on
0 ÷ 255 min.
LAL
15.0
30
1,5
21
Pr1
Low pressure (temperature) alarm compressor section
> 0÷30.0 bar/100.0
°C/430 PSI/200 °F
HAL
20.0
40
2,5
46
Pr1
High pressure (temperature) alarm compressor section
> 0÷30.0 bar/100.0
°C/430 PSI/200 °F
tAo
15
15
15
15
Pr1
Low and High pressure (temperature) alarms delay-
compressor section
0 ÷ 255 min.
SEr
999
999
999
999
Pr2
Service request
(0 = disable) 1÷ 999; res
10h
PEn
5
5
5
5
Pr2
Low pressure-switch intervention numbers
0 ÷ 15
PEi
15
15
15
15
Pr2
Pressure -switch interventions time
0 ÷ 255 min.
SPr
2
2
2
2
Pr2
Number of steps engaged with faulty probe
0 ÷ # compressors
The thermostat’s set point is sent programming to 28 ˚C by the
technicians of Friterm A.
Ş
.
The parameters specified with “ * ” are adjusted according to the
products of Friterm A.
Ş
.