Step 3: Duct and accessories installation
1. Install the filter (optional) according to the size
of the air inlet.
2. Install the canvas tie-in between the body and
duct.
3. The air inlet and air outlet duct should be far
enough apart enough to avoid air passage
short-circuit.
4. Connect the duct according to the following
diagram:
Canvas tie-in Canvas tie-in
Fig. 4.10
5. Refer to the following static pressure guidelines
when installing the indoor unit.
Table.4-2
MODEL
(Btu/h)
Static Pressure
(Pa)
18K
0~100
24K
0~160
30K~36K
0~160
42K~60K
0~160
Change the fan motor static pressure
according to external duct static pressure.
Isolation booth
Air outlet
Isolation booth
checking orifice
Air inlet
Air dust filter
NOTE:
1. Do not place the connecting duct
weight on the indoor unit.
2.When connecting the duct, use a
nonflammable canvas tie-in to prevent vibrating.
3.Insulation foam must be wrapped outside the
duct to avoid condensate. An internal duct
underlayer can be added to reduce noise,
if the end-user requires.
V.1