6.CONTROL MODE
I < I
O
-1.5A Without limitation.
I>I
O
+1.5A Frequency drops.
I≥I
max
Operation stops.
5.
Dehumidification
5.1 In the dehumidification mode, the temperature is determined by the remote controller. The
temperature range is 16
℃
—30
℃
. The controller will determine the running mode according
to the indoor and outdoor temperature difference.
5.2
When the room temperature is 2
℃
higher than the preset temperature, cooling run will be
5.3
T
set temperature
– T
room temperature
≥1℃
The compressor and the outdoor fan stop working,
and the indoor fan runs at a speed of 600 rpm.
6.Heating
6.1 When T
internal coil
≥
38℃, the indoor fan works in accordance with the setting of
the remote controller.
T
setting
- T
indoor
Fan speed
T
setting
- T
indoor
Fan speed
1
℃
Low
1
℃
Low
2
℃
Mid
2
℃
Low
3
℃
Mid
3
℃
Mid
4
℃
Mid
4
℃
Mid
5
℃
High
5
℃
Mid
Temperature
difference
≥
6
℃
High
Temperature
difference
≥
6
℃
High
6.2
Current protection
I
O
is the normal working current value of E
2
ROM,I
max
is the ceiling current value
of E
2
ROM.
I < I
O
-1.5A Without limitation.
I>I
O
+1.5A Frequency drops.
I≥I
max
Operation stops.
6.3 Defrosting
6.3.1 The defrosting is done through changing the flow direction of refrigerant inside of the
four-way valve.
6.3.2 Defrosting conditions:
Continuous heating run for more than 30min
During single machine operation, T
outdoor
– T
outdoor coil
≥
12
℃
and lasts 8minutes
6.3.3 Defrosting process:
Compressor and outdoor fan motor off
→
four-way valve off
→
compressor on
→
defrosting conditions met
→
compressor off
→
four-way valve on
→
compressor on
→
outdoor fan on
→
end
6.3.4 Overhot protection for the indoor heat exchanger