6.CONTROL MODE
Surrounding air: K0, K1, K2, K4, K5
Directional air: Left K0, K1, K2, K3
Directional air: Right K0, K3, K4, K5
Directional air: Center K0, K2, K3, K4
Swinging air: K0K1, K0K2, K0K3 respectively according to the actual working status
Error message
Press the Emergency button for over 5 seconds when the power is on, the air conditioner will give
out alarm as follows: indoor unit trouble at the indoor temperature reading area and outdoor unit
trouble at the outdoor temperature area; the message is blinking at a frequency of 1Hz.
3.Temporary switch
3.1 If the remote controller is missing, press the temporary switch and the system starts in the
automatic mode, press the switch again to stop the system. Automatic mode follows:
A indoor temperature>
26℃ cooling mode temperature setting 26℃
B indoor temperature>
23℃ heating mode temperature setting 26℃
C
23℃≤
indoor temperature
≥26℃ fan mode
Indoor fan speed is automatic in automatic mode.
3.2 Hold down the temporary switch for 5 seconds or longer and the system is forced to run in the
cooling mode regardless of indoor temperature.
3.3. How to start the outdoor unit without the indoor unit
Short-circuit the two CN404 terminals on the IPM board of the outdoor unit, and switch on
the power, the air conditioner will start heating operation, and the outdoor fan is working; then
open the short circuit, the air conditioner will start cooling operation (the compressor starts 50
seconds later), and the fan is still working. Cut off the power, the outdoor unit will stop running.
4.Control mode
4.1 Automatic
4.1.1 When the air conditioner is switched on and the remote controller is set to Auto mode, the
air conditioner will select running modes automatically according to the difference
between the room temperature and the setting temperature.
4.1.2 The running mode will be set when the machine is first switched on. Once set, the
running mode cannot be changed within 30 minutes.
4.1.3 If the difference between the room temperature and the setting temperature exceeds 3
degrees, change the running mode immediately.
4.1.4 If the machine is turned off and restarted using the remote controller, the above conditions
are still good.
4.1.5 If the machine is powered off and restarted, the running mode must be re-selected.
4.1.6 The running frequency will be determined by the temperature difference.
4.2 Cooling
4.2.1 In the cooling mode, the preset temperature is determined by the remote controller. The
temperature range is 16
℃
—30
℃
.