8

CONDENSATE DRAIN 

A 3/4” condensate fi tting extends out of the side 
of the unit. The drain trap, shipped in the electrical 
compartment, must be installed to prevent water 
from collecting inside the unit. Thread the elbow 
provided with the unit into the drain connection 
until hand tight. Install the trap into the fi tting 
making sure it is level. Route the condensate 
from the trap to a suitable drain. Any tubing or 
hose connected must have the outlet below trap 
level for proper drainage.

 WARNING:

Turn off electrical power before servic-
ing controls. Severe electrical shock 
may result unless power is turned off. 
Unit must be installed in compliance 
with the National Electrical Code (NEC) 
and local codes.

ELECTRICAL CONNECTIONS

1. ELECTRICAL SERVICE

High Voltage

a.  Install a branch circuit disconnect of adequate 

size per NEC. Locate the disconnect within 
sight of the unit.

b.  Extend leads through power wiring hole 

provided. Connect L1 and L2 directly to the 
contactor. (See Figure 9.)

c.  Ground the heat pump unit using the green 

grounding screw provided in the control 
panel.

Low Voltage

a.  Route 24v control wires through the sealing 

grommet near the power entrance. (See 
Figure 9.)

b.  Connect the control wires to the defrost board 

and blower relay wire. (See Figure 10.)

2. OVERCURRENT PROTECTION

In general, the best fuse or breaker for any 
heat pump is the smallest size that will permit 
the equipment to run under normal use and 
service without nuisance trips. Such a device, 
sized properly, gives maximum equipment 
protection. The principal reason for specifying 
a

 

time delay type is to prevent nuisance trips 

when the unit starts.

In the event that a fuse does blow or a breaker 
trips, always determine the reason. Do not arbi-
trarily put in a larger fuse or breaker and do not, 
in any case, exceed the maximum size listed on 
the data label of the unit.

3.  LOCATING THE THERMOSTAT

Locate the thermostat away from drafts and 
slamming doors and place it where there is a free 
fl ow of air. Mount on an inside wall approximately 
fi ve feet from the fl oor.

Do not locate near a lamp, kitchen range, direct 
sunlight, or in line with air fl ow from supply 
registers.

Connect the Heat-Cool Thermostat: 

The 

heat-cool thermostat is equipped with a system 
HEAT-COOL switch, which provides a positive 
means of preventing simultaneous operation of 
the heating and cooling units. The thermostat is 
also equipped with an ON-AUTO fan switch which 
allows the home owner to operate the indoor 
blower when air circulation is desired.

Connect the low voltage wires to the respective 

terminals on the thermostat base. See thermo-

stat instruction sheet for more detailed informa-

tion. (See Figure 10).

Figure 9.  Power Entry

Low Voltage

High Voltage

Summary of Contents for PPH2RD

Page 1: ... weather comfort control system appliance The basic operation of the heating cooling system is described and illustrated on page 1 of this manual The surprising fact that heat exists in air even at below freezing temperatures is actually the basic law of physics which the heat pump uses to provide energy saving heating comfort At outdoor temperatures of 47 Fahrenheit or 8 Celsius your heat pump ca...

Page 2: ...temperature at the desired cooling level NOTE If the thermostat temperature level is re adjusted or if the thermostat system switch is re positioned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand theoutdoorfanoffforapproximatelyfiveminutes following a previous operation or the interruption of the main electric power To Operate Your H...

Page 3: ...te installation Use of components other than those speci fied may invalidate ARI Certification Code Agency Listing and limited warranty on the air conditioner PRE INSTALLATION CHECK Before any installation is attempted the cool ing load of the area to be conditioned must be calculated and a system of the proper capacity selected It is recommended that the area to be conditioned be completely insul...

Page 4: ...earance between overhang and top of unit 72 Clearance around condenser coil area to wall or shrubs excludes duct panel side 12 Minimum clearance to combustible materials Combustible Base Wood or Class A B or C roof Covering material 0 Supply and Return Air Ducts 0 Duct Connection side 0 DUCT REQUIREMENTS The supply duct system including the number and type of registers will have much more ef fect ...

Page 5: ... the filter box through a boxed in area at the closet floor level Make sure the filter is readily accessible After determining the location of the return air opening start the installation from under the home by cutting a small hole in the fiber under board to determine how the floor joist location will affect cutting the opening needed for the box Floor joists generally are located on 16 centers ...

Page 6: ...n Association Standard for Installation of Air Conditioning and Ventilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA 90B these instructions and all applicable codes TYPICAL APPLICATIONS Figure 6 Drain Trap Elbow P Trap MULTIPLE DUCT APPLICATION SINGLE DUCT APPLICATION 6 6 4 4 5 2 3 1 5 2 3 6 4 1 7 1 3 2 4 5 6 7 Figure 7 Typical...

Page 7: ... High Efficiency Motors with 5 speed taps If Standard Motor 2 and 2 5 Ton 1 Disconnect all electrical power to the unit and remove the service panel 2 The blower speed is preset at the factory for operation at the same speed for heating and cooling 3 Place the desired blower speed lead on the COM terminal of the blower relay Use another wire tie field supplied to bundle the remaining motor lead up...

Page 8: ... 10 2 OVERCURRENT PROTECTION In general the best fuse or breaker for any heat pump is the smallest size that will permit the equipment to run under normal use and service without nuisance trips Such a device sized properly gives maximum equipment protection The principal reason for specifying a time delay type is to prevent nuisance trips when the unit starts In the event that a fuse does blow or ...

Page 9: ...ypical Heat Pump Thermostat Connections E O G R Y1 INDOOR THERMOSTAT SUB BASE Green W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Optional 2nd Stage Outdoor Thermostat Field Supplied Outdoor Thermostat Factory Option E O G R Y1 INDOOR THERMOSTAT SUB BASE Green W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Outdoor Thermostat Factory Option ...

Page 10: ... the drain for proper conden sate drainage Is the unit installed with the proper clear ances See Figure 2 Is the wiring correct according to the wiring diagram and electrical codes Are all the wiring connections tight Check the condenser fan to make sure it turns freely Is the overcurrent protection properly sized Is the thermostat wired correctly Is it installed in a proper location 2 START UP PR...

Page 11: ...s will initiate a defrost test in 5 10 or 15 seconds This is determined by the 30 60 or 90 minute defrost pin settings The factory setting will be 30 minutes Note that this will bypass the compressor off delay when the unit goes into defrost test and if left in defrost test the delay will be bypassed when the test is terminated by the processor If the jumper is removed before the test is over the ...

Page 12: ...oxes indicate flooded conditions Rated Design Values Suction Pressure will be lower than design value if indoor air flow entering dry bulb or entering wet bulb temperatures are lower than design Discharge temperatures greater than charted values indicate an undercharged system Refrigerant Charging Chart Legend for Cooling Mode of Operation 2 5 Ton OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Su...

Page 13: ...0 355 163 374 164 394 165 414 165 436 166 152 378 168 398 169 417 170 438 170 154 401 173 421 174 440 174 156 424 178 444 179 158 447 183 160 3 Ton OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Suct Press Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 138 267 113 140 269 118 290 119 142 271 1...

Page 14: ...49 370 174 391 175 412 175 434 175 457 175 151 395 179 416 179 437 179 459 178 153 419 183 440 183 461 183 155 444 187 465 187 157 468 191 159 5 Ton OUTDOOR TEMPERATURE deg F 70 75 80 85 90 95 100 105 Suc Press Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 1...

Page 15: ...57 267 109 71 283 115 84 299 121 100 334 125 116 364 127 133 395 128 13 SEER Refrigerant Charging Tables for Heating Mode of Operation 2 5 Ton OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Page 16: ...8 127 68 285 128 83 301 129 97 330 130 112 354 131 126 378 133 39 259 124 54 274 125 69 290 126 84 305 127 98 337 127 113 361 127 127 385 126 3 Ton OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Pr...

Page 17: ...20 30 40 50 60 Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 31 203 134 44 233 139 57 264 143 70 294 148 84 313 162 100 344 186 116 375 210 32 210 132 45 239 137 58 269 141 71 298 146 85 320 159 101 351 182 1...

Page 18: ...ESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED RED RED BLACK BLACK YELLOW BLACK YE YE YE YE YELLOW GREY BLACK BLACK VIOLET BLACK FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE NOTES 208 230 VOLT SMALL PACKAGE HEAT PUMP 60HZ SINGLE PHASE 1 Disconnect all power before servicing 2 ...

Page 19: ...ELLOW ORANGE WHITE WHITE GREEN YELLOW WHITE WHITE WHITE GREY GREY BROWN BLACK BLACK BLACK BLACK GREEN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE SMALL PACKA...

Page 20: ... PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 709067A Replaces 7090670 Specifications and illustrations subject to change without notice and without incurring obligations 08 09 709067 709067A ...

Reviews: