background image

4

2. UNPACK THE UNIT

It is recommended that the unit be unpacked 
at the installation site to minimize damage due 
to handling.

 CAUTION:

Do not tip the unit on its side. Oil may 
enter the compressor cylinders and 
cause starting trouble. If unit has been 
set on its side, restore to upright posi-
tion and do not run for several hours. 
Then run unit for a few seconds. Do this 
three or four times with fi ve minutes 
between runs. 

a.  Remove the bands from around the unit. 

b.  Unfold the top and bottom cap fl anges.

c.   Carefully remove the top cap and tube.

3.  CLEARANCES

Minimum clearances, as specifi ed in Figure 2, 

MUST by maintained from adjacent structures 
to provide room for proper servicing and air 
circulation.

Do NOT install unit in a confi ned or recessed 

area that will allow discharge air from the unit to 
re-circulate into the condenser air inlet, through 
the coil.

Service Access Clearance:

Blower access panel side  .......................... 24”
Electrical compartment access panel side ... 12”

Clearance between overhang and top of 

unit  .........................................................72”

Clearance around condenser coil area to wall 

or shrubs (excludes duct panel side) .......... 12”

Minimum clearance to combustible materials:

Combustible Base (Wood or Class A, B, or C 
roof Covering material) ...............................0”
Supply and Return Air Ducts .......................0”
Duct Connection side ..................................0”

DUCT REQUIREMENTS

The supply duct system, including the number 
and type of registers, will have much more ef-
fect on the performance of an air conditioning 
system then any other factor. The duct must be 
suffi ciently large to conduct an adequate amount 
of air to each register.

4.  INSTALL THE RETURN AND SUPPLY AIR 

FITTINGS ON THE UNIT

The supply and return fi ttings are included with 
select models. If supplied, the duct fi ttings are 
shipped in the supply duct. They attach to the unit 
openings with a fl ange and bead arrangement, 
secured with two sheet metal screws. Note: For 
ease of access, install fi tting before positioning 
unit in fi nal location.

Figure  3.  Return and Supply Air Fittings

Supply Air

14” Duct Dimples

Return Air

Transition Duct Screws

13 SEER

Return Dia. (in)

2 Ton

12

2 1/2 Ton

14

3 Ton

14

3 1/2 Ton

14

4 Ton

14

5 Ton

14

6 ft.

24"

12"

12"

Figure  2.  Minimum Unit Clearances

Summary of Contents for PPH2RD

Page 1: ... weather comfort control system appliance The basic operation of the heating cooling system is described and illustrated on page 1 of this manual The surprising fact that heat exists in air even at below freezing temperatures is actually the basic law of physics which the heat pump uses to provide energy saving heating comfort At outdoor temperatures of 47 Fahrenheit or 8 Celsius your heat pump ca...

Page 2: ...temperature at the desired cooling level NOTE If the thermostat temperature level is re adjusted or if the thermostat system switch is re positioned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand theoutdoorfanoffforapproximatelyfiveminutes following a previous operation or the interruption of the main electric power To Operate Your H...

Page 3: ...te installation Use of components other than those speci fied may invalidate ARI Certification Code Agency Listing and limited warranty on the air conditioner PRE INSTALLATION CHECK Before any installation is attempted the cool ing load of the area to be conditioned must be calculated and a system of the proper capacity selected It is recommended that the area to be conditioned be completely insul...

Page 4: ...earance between overhang and top of unit 72 Clearance around condenser coil area to wall or shrubs excludes duct panel side 12 Minimum clearance to combustible materials Combustible Base Wood or Class A B or C roof Covering material 0 Supply and Return Air Ducts 0 Duct Connection side 0 DUCT REQUIREMENTS The supply duct system including the number and type of registers will have much more ef fect ...

Page 5: ... the filter box through a boxed in area at the closet floor level Make sure the filter is readily accessible After determining the location of the return air opening start the installation from under the home by cutting a small hole in the fiber under board to determine how the floor joist location will affect cutting the opening needed for the box Floor joists generally are located on 16 centers ...

Page 6: ...n Association Standard for Installation of Air Conditioning and Ventilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA 90B these instructions and all applicable codes TYPICAL APPLICATIONS Figure 6 Drain Trap Elbow P Trap MULTIPLE DUCT APPLICATION SINGLE DUCT APPLICATION 6 6 4 4 5 2 3 1 5 2 3 6 4 1 7 1 3 2 4 5 6 7 Figure 7 Typical...

Page 7: ... High Efficiency Motors with 5 speed taps If Standard Motor 2 and 2 5 Ton 1 Disconnect all electrical power to the unit and remove the service panel 2 The blower speed is preset at the factory for operation at the same speed for heating and cooling 3 Place the desired blower speed lead on the COM terminal of the blower relay Use another wire tie field supplied to bundle the remaining motor lead up...

Page 8: ... 10 2 OVERCURRENT PROTECTION In general the best fuse or breaker for any heat pump is the smallest size that will permit the equipment to run under normal use and service without nuisance trips Such a device sized properly gives maximum equipment protection The principal reason for specifying a time delay type is to prevent nuisance trips when the unit starts In the event that a fuse does blow or ...

Page 9: ...ypical Heat Pump Thermostat Connections E O G R Y1 INDOOR THERMOSTAT SUB BASE Green W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Optional 2nd Stage Outdoor Thermostat Field Supplied Outdoor Thermostat Factory Option E O G R Y1 INDOOR THERMOSTAT SUB BASE Green W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Outdoor Thermostat Factory Option ...

Page 10: ... the drain for proper conden sate drainage Is the unit installed with the proper clear ances See Figure 2 Is the wiring correct according to the wiring diagram and electrical codes Are all the wiring connections tight Check the condenser fan to make sure it turns freely Is the overcurrent protection properly sized Is the thermostat wired correctly Is it installed in a proper location 2 START UP PR...

Page 11: ...s will initiate a defrost test in 5 10 or 15 seconds This is determined by the 30 60 or 90 minute defrost pin settings The factory setting will be 30 minutes Note that this will bypass the compressor off delay when the unit goes into defrost test and if left in defrost test the delay will be bypassed when the test is terminated by the processor If the jumper is removed before the test is over the ...

Page 12: ...oxes indicate flooded conditions Rated Design Values Suction Pressure will be lower than design value if indoor air flow entering dry bulb or entering wet bulb temperatures are lower than design Discharge temperatures greater than charted values indicate an undercharged system Refrigerant Charging Chart Legend for Cooling Mode of Operation 2 5 Ton OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Su...

Page 13: ...0 355 163 374 164 394 165 414 165 436 166 152 378 168 398 169 417 170 438 170 154 401 173 421 174 440 174 156 424 178 444 179 158 447 183 160 3 Ton OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Suct Press Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 138 267 113 140 269 118 290 119 142 271 1...

Page 14: ...49 370 174 391 175 412 175 434 175 457 175 151 395 179 416 179 437 179 459 178 153 419 183 440 183 461 183 155 444 187 465 187 157 468 191 159 5 Ton OUTDOOR TEMPERATURE deg F 70 75 80 85 90 95 100 105 Suc Press Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 1...

Page 15: ...57 267 109 71 283 115 84 299 121 100 334 125 116 364 127 133 395 128 13 SEER Refrigerant Charging Tables for Heating Mode of Operation 2 5 Ton OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Page 16: ...8 127 68 285 128 83 301 129 97 330 130 112 354 131 126 378 133 39 259 124 54 274 125 69 290 126 84 305 127 98 337 127 113 361 127 127 385 126 3 Ton OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Pr...

Page 17: ...20 30 40 50 60 Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 31 203 134 44 233 139 57 264 143 70 294 148 84 313 162 100 344 186 116 375 210 32 210 132 45 239 137 58 269 141 71 298 146 85 320 159 101 351 182 1...

Page 18: ...ESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED RED RED BLACK BLACK YELLOW BLACK YE YE YE YE YELLOW GREY BLACK BLACK VIOLET BLACK FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE NOTES 208 230 VOLT SMALL PACKAGE HEAT PUMP 60HZ SINGLE PHASE 1 Disconnect all power before servicing 2 ...

Page 19: ...ELLOW ORANGE WHITE WHITE GREEN YELLOW WHITE WHITE WHITE GREY GREY BROWN BLACK BLACK BLACK BLACK GREEN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE SMALL PACKA...

Page 20: ... PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 709067A Replaces 7090670 Specifications and illustrations subject to change without notice and without incurring obligations 08 09 709067 709067A ...

Reviews: