background image

SS-FRS12PYS1-07/10-1

POWER

Circuit Amps
Maximum Fuse Size

CAPACITIES

Cooling
Amps
Watts
Min/Max Cooling
SEER
EER
Low Ambient Temperature
Voltage/Frequency/Phase
Dehumidification

INDOOR UNIT

Sound Rating
Net Weight
Shipping Weight
Dimensions (H x W x D)
Full Loaded Amps
Number of Fan Speeds
Fan Type
Motor Watts
Full Loaded Amps

COMPRESSOR

Type
Amps
Locked Rotor Amps

HEATING

Total Capacity (BTU)
HSPF
Amps
Max Amps
Power Inputs
Back Up Strip Heater
Outdoor Sound Rating

18 A
25 A

12000 Btu
11 A
1000 W
4500 Btu-14000 Btu
18
12
5° F 

£

 T 

£

 115° F

115V/60Hz/1P
2.54PT/H

(40)/36/32/26dB (A) 
22 lb
26 lb
10.83" x 33.27" x 7.09"
0.35 A
4
cross flow
20 W
0.33 A

C-6RZ110H1A

twin rotary DC inverter
4.59 A
33 A

13000 Btu
9.6
12.5 A
18.2 A
1200 W
n/a

£ 

55 dB (A) 

Job: ______________________________

Location: __________________________

Engineer: __________________________

Submitted to: ______________________

Reference: _________________________

Approval:  _________________________

Date: _____________________________

Submitted by: ______________________

Construction: ______________________

Unit Number:  ______________________

Drawing Number: ___________________

A

B

C

FRS12PYC1 Outdoor

B

A

C

FRS12PYW1 Indoor

OUTDOOR UNIT

Sound Rating
Net Weight
Shipping Weight
Dimensions (H x W x D)
Recommended Fuse
Minimum Amps
Running Current
Drive Type
Motor Watts
CFM (high)

FEATURES

Controls
Remote Control
Temperature control
Timer
Air Louvers
Horizontal
Vertical
Low Voltage Restart
Self-Diagnosis
Quiet Operation
Air Filter

REFRIGERANT SYSTEM

Refrigerant
Ounces
Lineset
Maximum Height
Maximum Line length
Discharge Vapor Line (od)
Suction (od)

£ 

55 dB (A) 

82.38 lb
89 lb
12.60" x 33.39" x 21.26"
25 A
15 A
18.2 A
dc motor
30 W
1058

microprocessor
lcd wireless
16-30° C
24 hr
2 pieces 
manual
swing
built-in
yes
no
washable, anti-mold

R410A
45.8
16.4 ft
33 ft
66 ft

F

 6 mm (1/4")

F

 9 mm (3/8")

Ductless Mini-Split System Air Conditioners

Submittal Sheet

FRS12PYS1

PRODUCT DIMENSIONS

Indoor –

A - Height
B - Width
C - Depth
Max. Wall Thickness

Outdoor –

A - Height
B - Width
C - Depth

10-7/8"
33-1/4"
7-1/8"
18"

21-1/4"
33-3/8"
12-5/8"

Summary of Contents for FRS12PYC1

Page 1: ...e with ductwork This loss can amount to up to 40 due to leaks tears and long lengths Inverter Technology Allows the unit to maintain room temperatures while operating at a lower and quieter speed Multi Speed Fan Features three different fan speeds for more cooling flexibility Sleep Mode Quiet operation keeps you cool without keeping you awake Plus Sleep Mode gradually increases room temperature af...

Page 2: ...ensed refrigeration technician for full parts and labor warranty validation Insulated line sets and control wires are required and available for Frigidaire split systems in 16 4 ft length Each line set is equipped with flare nuts on both ends Each system requires one line set for each indoor unit installed NOTE For planning purposes only Always consult local and national electric codes Refer to Pr...

Page 3: ...3000 Btu 9 6 12 5 A 18 2 A 1200 W n a 55 dB A POWER Circuit Amps Maximum Fuse Size CAPACITIES Cooling Amps Watts Min Max Cooling SEER EER Low Ambient Temperature Voltage Frequency Phase Dehumidification INDOOR UNIT Sound Rating Net Weight Shipping Weight Dimensions H x W x D Full Loaded Amps Number of Fan Speeds Fan Type RPM at High Speed Motor Watts Full Loaded Amps Coil Type Fin Type Pipe Type F...

Page 4: ... _ _________________________ Date ______________________________ Submitted by _ ______________________ Construction _______________________ Unit Number _______________________ Drawing Number _ ___________________ A B C FRS12PYC1 Outdoor B A C FRS12PYW1 Indoor OUTDOOR UNIT Sound Rating Net Weight Shipping Weight Dimensions H x W x D Recommended Fuse Minimum Amps Running Current Drive Type Motor Wat...