1. The inside and outside connecting
cable can be connected without
removing the front grille.
2. Connecting cable between indoor unit
and outdoor unit shall be approved
polychloroprene sheathed flexible cord,
type designation H07RN-F or heavier
cord.
3. Lift the indoor unit panel up, remove
the electrical box cover by loosening the
screw.
4. Ensure the colour of wires of outdoor
unit and the terminal Nos. are the same
to the indoors respectively.
5. Wrap those cables not connected with
terminals with insulation tapes, so that
they will not touch any electrical
components. Secure the cable onto the
control board with the cord clamp.
Connect the cable to the indoor unit
21
22
40mm
40mm
10mm
10mm
< 18000 btu's CABLE (Cooling model)
> 18000 btu's CABLE
(Heating and cooling model)
Cable code
< 18000 btu's CABLE
(Heating and cooling model)
40mm
10mm
40mm
10mm
"Cable A"
"Cable C”
"Cable B"
or
cable code
Cable code
Cable code
> 24000 Btu's
< 12000 Btu's
12000 Btu's < model < 24000 Btu’s
220-240V~/50Hz
220-230V~/ 60Hz
220-240V~/ 50Hz
220-230V~/ 60Hz
220-240V~/ 50Hz
220-230V~/ 60Hz
MODEL
INPUT RATED AMP
Switch / Fuse
POWER SUPPLY
CABLE
SIZE
10A
10A
16A
16A
25/32A
25/32A
1,0 mm²
1,5 mm²
> 2,5 mm²
> 2,5 mm²
2,5 mm²
2,5 mm²
Note:
The supply voltage must be consistent with the rate voltage of the air conditioner.
Electrical work
1. If there is serious safety problem
about the power supply, the
technicians should refuse to install
the air conditioner and explain to
the client until the problem is
solved.
2. Power voltage should be in the
range of 90%~110%of rated
voltage.
3. The creepage protector and main
power switch with a 1.5 times
capacity of Max. Current of the unit
should be installed in power circuit.
4. Ensure the air conditioner is
grounded well.
5. According to the attached Electrical
Connection Diagram located on the
panel of the outdoor unit to connect
the wire.
6. All wiring must comply with local
and national electrical codes and be
installed by qualified and skilled
electricians.
7. An individual branch circuit and
single receptacle used only for this
air conditioner must be available.
See the following table for
suggested wire sizes and fuse
specifications: