2-5
Electronic Control
Error Indication
The following error conditions are monitored by each electronic control assembly:
1. Thermistor open or shorted. A defective thermistor will require that the affected electronic control assembly
be replaced.
2.
Stuck Key (the key appears to be pressed for longer than 30 seconds).
3.
Low Voltage (AC line voltage has dropped below 90 volts).
If any of these errors occur, the display will flash an "E" at one second intervals and the control will go into Fail Safe
Mode.
Fail Safe Mode
While in Fail Safe mode, the compressor will run constantly with a 30 minute defrost cycle every 12 hours.
Stuck Key
If either key is held in for more than 30 seconds the control enters fail safe operation.
Exiting Fail Safe Mode
Once a failure is resolved (thermistor, stuck key or low voltage), the control resumes its normal operating mode
under the setting it was at before the error occurred.
Summary of Contents for FKCH17F7HW
Page 2: ......
Page 3: ...Basic Information 1 1 Section 1 Basic Information ...
Page 9: ...Electronic Control 2 1 Section 2 Electronic Control ...
Page 14: ...2 6 Electronic Control Notes ...
Page 15: ...3 1 Refrigeration System Section 3 Refrigeration System ...
Page 30: ...3 16 Refrigeration System HFC 134a CFC 12 Pressure Temperature Chart ...
Page 33: ...4 1 Component Teardown Section 4 Component Teardown ...
Page 47: ...5 1 Troubleshooting Section 5 Troubleshooting ...
Page 52: ...5 6 Troubleshooting Notes ...
Page 53: ...6 1 Wiring Diagrams Section 6 Wiring Diagrams ...
Page 54: ...6 2 Wiring Diagrams 7 4 6 2 8 3 5 1 ...
Page 56: ...7 1 Section 7 Installation Information Installation Information ...
Page 62: ...7 7 Installation Information Model FKCH17F7HW Unit Dimensions ...