INSTALLATION
PTAC Installation Recommendations
5
PTAC Installation Recommendations
PTAC.units.should.be.installed.
no.closer.than.12".apart.when.
two. units. are. side. by. side.. . If.
three.or.more.PTAC.units.are.to.
operate.next.to.one.another.allow.
a.minimum.of.36".between.units...
Also,.a.vertical.clearance.of.60".
should.be.maintained.between.
units. installed.. . In. the. interior.
of.the.room.the.unit.should.be.
located.a.minimum.of.1/4".from.
the.
.and.a.minimum.of.36".
from.the.ceiling.
•
For. minor. obstructions.
such.as.lamp.poles.or.small.
shrubbery. a. clearance. of.
12".from.the.outdoor.louver.
should.be.maintained.
•
For.major.obstructions.such.
as. a. solid. fence,. wall. or.
other.heat.rejecting.device.
like. a. condensing. unit,. a.
minimum. distance. of. 36".
should.be.kept.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances
below:
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
The.above.suggestions.are.for.reference.only.and.do.not.represent.all.possible.installations...Please.contact.Friedrich.for.information.regarding.affects.of.other.
installation.arrangements...By.following.these.simple.recommendations.you.can.be.
.that.your.Friedrich.PTAC.will.provide.years.of.worry.free.operation.
Figure 1
Figure 2
FRP002
PTAC
SHRUB
POLE
FENCE OR WALL
C
A
T
P
C
A
T
P
TYPICAL BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJOR
OBSTRUCTIONS
12" MINIMUM, MINOR
OBSTRUCTIONS
FRP001
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
TWO ADJACENT PTACs
12" MINIMUM
TYPICAL
WINDOW
VIEW: OUTSIDE BUILDING ELEVATION
60" VERTICAL
MINIMUM
BETWEEN
PTACs
12"
6"
36"
60"
Summary of Contents for ZONEAIRE SELECT PZE07K3SA
Page 47: ...47 COMPONENT TESTING Electrical ...
Page 48: ...48 COMPONENT TESTING Electrical ...
Page 61: ...61 TROUBLESHOOTING MalfunctionAnalysis ...
Page 62: ...62 TROUBLESHOOTING Malfunction Analysis ...
Page 63: ...63 TROUBLESHOOTING Malfunction Analysis ...
Page 64: ...64 TROUBLESHOOTING Malfunction Analysis ...
Page 66: ...66 TROUBLESHOOTING HeatPump Figure 702 ...
Page 67: ...67 WIRING DIAGRAMS RemoteWallThermostatWiringDiagram CoolWithElectricHeat Figure 801 ...
Page 68: ...68 WIRING DIAGRAMS Remote Wall Thermostat Wiring Diagram HeatPumpWithElectricHeat Figure 802 ...
Page 69: ...69 Figure 803 WIRING DIAGRAMS ...
Page 71: ...71 PARTS CATALOG PZE Figure 901 ...