background image

En-14

TROUBLESHOOTING

Symptom

Doesn’t operate immedi-
ately:

Noise is heard:

Smells:

Mist or steam are
emitted:

Air flow is stopped:

Problem

If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent
fuse blowouts.

Whenever the electrical breaker is turned off then on again, the
protection circuit will operate for about 3 minutes, preventing unit
operation during that period.

During operation and immediately after stopping the unit, the
sound of water flowing in the air conditioner’s piping may be
heard. Also, noise may be particularly noticeable for about 2 to 3
minutes after starting operation (sound of coolant flowing).

During operation, a slight squeaking sound may be heard. This is
the result of minute expansion and contraction of the panel due
to temperature changes.

During Heating operation, a sizzling sound may be heard occa-
sionally. This sound is produced by the Automatic Defrosting op-
eration.

Some smell may be emitted from the indoor unit. This smell is
the result of room smells (furniture, tobacco, etc.) which have
been taken into the air conditioner.

During Cooling, a thin mist may be seen emitted from the indoor unit.
This results from the sudden Cooling of room air by the air emitted
from the air conditioner, resulting in condensation and misting.

During Heating operation, the outdoor unit’s fan may stop, and
steam may be seen rising from the unit. This is due to the Auto-
matic Defrosting operation.

When Heating operation is started, fan speed is temporarily very
low, to allow internal parts to warm up.

During Heating operation, if the room temperature rises above
the thermostat setting, the outdoor unit will stop, and the indoor
unit will operate at very low fan speed. If you wish to warm the
room further, set the thermostat to a higher setting.

During Heating operation, the unit will temporarily stop opera-
tion (between 2 and 16 minutes) as the Automatic Defrosting mode
operates. During the Automatic Defrosting operation, 

 will

be shown on the remote controller display.

The fan may operate at very low speed when the unit is monitor-
ing the room’s temperature.

In the monitor AUTO operation, the fan will operate at very low speed.

In case of Multi-type unit, if multiple units are operated in
different operation modes as shown below, the units operated
afterward will stop and 

  will be shown on the remote

controller display of the stopped indoor units.
Heating mode and cooling mode (or dry mode)
Heating mode and fan mode

See Page

9

9

9

NORMAL

FUNCTION

Instructions relating to heating are applicable only to “HEAT & COOL MODEL” (Reverse Cycle).

 WARNING!

In the event of a malfunction (burning smell, etc.), immediately stop operation, turn off the electrical breaker,
and consult authorized service personnel.
Merely turning off the unit’s power switch will not completely disconnect the unit from the power source.
Always be sure to turn off the electrical breaker to ensure that power is completely off.

Before requesting service, perform the following checks:

10

9368987060-01_OM_en.p65

2/4/10, 4:46 PM

14

Summary of Contents for P/N9368987060-01

Page 1: ...PE OPERATING MANUAL MODE D EMPLOI MANUAL DE FUNCIONAMIENTO KEEP THIS MANUAL FOR FUTURE REFERENCE CONSERVEZ CE MODE D EMPLOI AFIN DE POUVOIR VOUS Y R F RER ULT RIEUREMENT GUARDE ESTE MANUAL PARA PODERL...

Page 2: ...nds Turn off power source when not using the unit for extended periods Always turn off the electrical breaker whenever cleaning the air conditioner or changing the air filter Connection valves become...

Page 3: ...T Button C Vertical Airflow Direction and Swing Button D Operation Lamp E Timer and Clock Display F Operation Mode Display G Fan Speed Display H Operation Lock Display I Temperature Display J Function...

Page 4: ...ress repeatedly to adjust the current time in 1 minute increments Press and hold to adjust the current time in 10 minute increments ex Monday 10 00 A M Press again to end CLOCK ADJUST 1 3 4 AUTO COOL...

Page 5: ...sing this function If this function is locked the location where the room temperature is detected cannot be changed and the mark flashes when the THERMO SENSOR button is pushed Indoor unit Energy save...

Page 6: ...to repeat the timer settings for all of the days Temperature SET BACK timer See page 8 Use this timer function to change the set temperature in the operation times set for each day of the week This ca...

Page 7: ...at steps 3 and 4 To complete the weekly timer settings press the SET button for 2 seconds or more SET To delete the operating time DELETE If the DELETE button is pressed during steps 3 or 4 the operat...

Page 8: ...18 21 SU MO TU WE TH FR SA 3 6 9 12 15 18 21 SU MO TU WE TH FR SA 3 6 9 12 15 18 21 To cancel Follow the same procedures as those for setup ex The DAY OFF is set for Monday mark Indicates the DAY OFF...

Page 9: ...ain the SET BACK timer will be cancelled Temperature SET BACK timer setting SET BACK 1 DELETE 2 SET BACK If there is no existing SET BACK tempera ture setting will be displayed for the temperature SU...

Page 10: ...es on the heat pump principle absorbing heat from outdoor air and transferring that heat indoors As a result the operating performance is reduced as outdoor air temperature drops If you feel that insu...

Page 11: ...oling efficiency will be less than when a single indoor unit is used alone Accordingly when you wish to use more than one in door unit for cooling at the same time the use should be concentrated at ni...

Page 12: ...During AUTO mode the airflow direction will be set to horizontal airflow 1 for the first minute of air conditioner opera tion The airflow direction cannot be changed during this time Always use the r...

Page 13: ...filters to dry thoroughly in an area protected from sunlight NOTES Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of mild deter gent and w...

Page 14: ...nnel How to cleaning When used for extended periods the unit may accumulate dirt inside reducing its performance We recommend that the unit be inspected regularly in addition to your own cleaning and...

Page 15: ...This is due to the Auto matic Defrosting operation When Heating operation is started fan speed is temporarily very low to allow internal parts to warm up During Heating operation if the room temperat...

Page 16: ...r a circuit breaker been tripped Is the timer operating Is the air filter dirty Are the air conditioner s intake grille or outlet port blocked Did you adjust the room temperature settings thermostat c...

Page 17: ...9368987060 01_OM_es p65 2 4 10 4 48 PM 18...

Page 18: ...Friedrich Air Conditioning Co 4200 N Pan Am San Antonio Texas 78218 USA Tel 210 357 4400 Fax 210 357 4490 Visit us at www friedrich com 9368987060 01_OM_es p65 2 4 10 4 48 PM 19...

Reviews: