background image

4

COMPRESSOR WINDING TEST 

(Figure 2.)

Remove the compressor terminal box cover and disconnect the 
wires from the terminals. Using an ohmmeter, check continuity 
across the following:

COMPONENT OPERATION AND TESTING

COMPRESSORS

Compressors are single phase, 208/230 volt. All compressor 

motors are permanent split capacitor type, using only a running 
capacitor across the start and run terminal.

All compressors are internally spring mounted and externally 

mounted on rubber isolators.

Line Voltage Overload

The compressor is equipped with an internal line voltage over-

load. This overload is embedded in the windings of the motor 
to sense the motor temperature. The overload will open and 
disconnect the power to the motor due to high temperatures 

caused by:

1.  A locked rotor.

2.  Excessive running amps.

3.  High discharge temperature.

4.  Low refrigerant charge.

FIGURE 1  INTERNAL OVERLOAD

LINE BREAK 
INTERNAL OVERLOAD

OHMMETER

FIGURE 2 COMPRESSOR WINDING TEST

Testing Procedures

1. 

Terminal "C" and "S" – no continuity – open winding 

– replace compressor.

2.  Terminal "C" and "R" – no continuity – open winding 

– replace compressor.

3.  Terminal "R" and "S" – no continuity – open winding 

- replace compressor.

4. 

Terminal "C" and the shell of the compressor – continuity 

– grounded motor – replace compressor.

5.  Should continuity exist between terminals "R" and "S", 

but not between terminals "C" and "S" and "C" and "R", 
the internal overload may be open. If the compressor is 
extremely hot, allow it suffi cient time to cool. It may require 
as long as one hour for the compressor to cool suffi ciently 
for the internal overload to close.

CHECKING COMPRESSOR EFFICIENCY

The reason for compressor ineffi ciency is normally due to bro-

ken or damaged suction and/or discharge valves, reducing the 
ability of the compressor to pump refrigerant gas.

This condition can be checked as follows:

1.  Install a piercing valve on the suction and discharge or liquid 

process tube.

2.  Attach gages to the high and low sides of the system.

3.  Start the system. Run a "cooling or heating performance test."

If test shows:

A.  Below normal high side pressure. 

B.  Above normal low side pressure.

C.  Low temperature difference across the coil.

The compressor valves are faulty - replace the compressor.

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one lead to 
the compressor body (clean point of contact, as a good connec-
tion is a must) and the other probe in turn to each compressor 
terminal. (See Figure 3.) If a reading is obtained, the compressor 
is grounded and must be replaced.

FIGURE 3 TYPICAL GROUND TEST

WARNING

DISCONNECT ELECTRICAL POWER TO THE 

UNIT BEFORE SERVICING OR TESTING

Summary of Contents for HAZARDGARD SH15L30-B

Page 1: ...SH15L30 B SH20L30 B HG SVC PRTS 07 3 07 Room Air Conditioners 60 Hz Models 2007 Service Parts Manual...

Page 2: ...ntrol Switch 5 Run Capacitor 5 Thermostat 5 Low Ambient Bypass Valve 6 Sealed Refrigeration System Repairs 6 Hermetic Component Replacement 7 Special Procedure in the case of Compressor Motor Burn Out...

Page 3: ...TING FOR CLASS I DIVISION 2 GROUPS A B C D Model Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth...

Page 4: ...hell of the compressor continuity grounded motor replace compressor 5 Should continuity exist between terminals R and S but not between terminals C and S and C and R the internal overload may be open...

Page 5: ...can be used for each motor or a dual rated capacitor can be used for both The capacitor s primary function is to reduce the line current while greatly improving the torque characteristics of a motor...

Page 6: ...ressure reaches 50 psig This pressure setting cannot be altered The system can be operated at outdoor temperatures as low as 45 F before the evaporator coil will begin to accumulate frost To determine...

Page 7: ...pump to the high side and low side of the system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate the system to an absolute holding pressure of 200 microns or less 12 Resta...

Page 8: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Page 9: ...SOR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for nam...

Page 10: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Page 11: ...11 WIRING DIAGRAM MODELS SH15L30 B and SH20L30 B...

Page 12: ...12 HAZARDGARD CABINET PARTS...

Page 13: ...13 HAZARDGARD CHASSIS PARTS...

Page 14: ...1 399 RELAY SOLID STATE 61108800 2 2 399 6 THERMOSTAT 61822502 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 150 HARNESS WIRE COMP 61821308 1 1 399 REFRIGERATION...

Page 15: ...4905 1 743 30 SCROLL 61817505 1 743 32 BASE PAN 61803444 1 1 730 34 BOLT COMP MOUNT 91400400 3 3 791 35 PLENUM ASSEMBLY 61831006 1 1 753 36 OUTER SHELL 61825708 1 770 36 OUTER SHELL 61825709 1 770 37...

Page 16: ...rranty period providing the unit is returned to an authorized Friedrich Repair Station located within the Continental United States The Friedrich warranty does not cover 1 Any charges for removal tran...

Reviews: