background image

7

 NOTE: This procedure can be sped up by the use of 

heat lamps, or by breaking the vacuum with refrigerant 
or dry nitrogen at 5,000 microns. Pressure system to 5 
PSIG and leave in the system a minimum of 10 minutes. 
Recover refrigerant, and proceed with evacuation to a 
pressure of 200 microns or a minimum of 10%.

11.  Break the vacuum by charging the system from the high 

side with the correct amount of refrigerant specifi ed. This 
will prevent boiling the oil out of the crankcase.

 

NOTE: If the entire charge will not enter the high side, 

allow the remainder to enter the low side in small 
increments while operating the unit.

HERMETIC COMPONENT REPLACEMENT

The following procedure applies when replacing components 

in the sealed refrigeration circuit or repairing refrigerant leaks. 

(Compressor, condenser, evaporator, capillary tube, refrigerant 

leaks, etc.)

1.  Recover the refrigerant from the system at the process 

tube located on the high side of the system by installing 
a line tap on the process tube. Apply the gauge from the 
process tube to EPA approved gauges from the process 
tube to the EPA approved recovery system. Recover the 

CFC’s in the system to at least 5%.

2.  Cut the process tube below the pinch off in the suction side 

of the compressor.

3.  Connect the line from the nitrogen tank to the suction 

process tube.

4.  Drift dry nitrogen through the system and unsolder the 

more  distant  connection  first.  (Filter  drier,  high  side 
process tube, etc.)

5.  Replace the inoperative component, and always install a 

new fi lter drier. Drift dry nitrogen through the system when 
making these connections.

6.  Pressurize the system to 30 PSIG with proper refrigerant 

and boost the refrigerant pressure to 150 PSIG with dry 
nitrogen.

7.  Leak test the complete system with the electric halogen 

leak detector, correcting any leaks found.

8.  Reduce the system to zero gauge pressure.

9.  Connect the vacuum pump to the high side and low side 

of the system with deep vacuum hoses, or copper tubing. 

(Do not use regular hoses.)

10.  Evacuate the system to an absolute holding pressure of 

200 microns or less.

12.  Restart the unit several times after allowing pressures 

to stabilize. Pinch off the process tubes, cut and solder 
the ends. Remove the pinch off tool, and leak check the 
process tube ends.

SPECIAL PROCEDURES IN THE CASE OF 
COMPRESSOR MOTOR BURNOUT

1.  Recover all refrigerant and oil from the system.

2.  Remove the compressor, capillary tube and fi lter drier from 

the system.

3.  Flush the evaporator, condenser and all connecting tubing 

with dry nitrogen, or equivalent, to remove all contamination 
from the system. Inspect the suction and discharge lines 
for carbon deposits. Remove and clean if necessary.

4.  Reassemble the system, including a new drier-strainer and 

capillary tube.

5.  Proceed with processing as outlined under hermetic 

component replacement.

ROTARY COMPRESSOR 
SPECIAL TROUBLESHOOTING & SERVICE

Basically, troubleshooting and servicing rotary compressors 
is the same as on the reciprocating compressor with only a 
few exceptions.

1.  Because of the spinning motion of the rotary, the mounts 

are critical. If vibration is present, check the mounts 
carefully.

2.  The electrical terminals on the rotary are in a different order 

than the reciprocating compressors. The terminal markings 
are on the cover gasket. Use your wiring diagram to insure 
the correct connections.

REFRIGERANT CHARGE

1.  The refrigerant charge is extremely critical. Measure the 

charge carefully and as exactly as possible to the nameplate 
charge.

2.  The correct method for charging the rotary is to introduce 

liquid refrigerant into the high side of the system with the 
unit off. Then start the compressor and enter the balance 
of the charge, gas only, into the low side.

 

The introduction of liquid into the low side, without the use of 

a capillary tube, will cause damage to the discharge valve 
of the rotary compressor.

NOTE: 

All inoperative compressors returned to Friedrich 

must have all lines properly plugged with the plugs from 
the replacement compressor.

Summary of Contents for HAZARDGARD SH15L30-B

Page 1: ...SH15L30 B SH20L30 B HG SVC PRTS 07 3 07 Room Air Conditioners 60 Hz Models 2007 Service Parts Manual...

Page 2: ...ntrol Switch 5 Run Capacitor 5 Thermostat 5 Low Ambient Bypass Valve 6 Sealed Refrigeration System Repairs 6 Hermetic Component Replacement 7 Special Procedure in the case of Compressor Motor Burn Out...

Page 3: ...TING FOR CLASS I DIVISION 2 GROUPS A B C D Model Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth...

Page 4: ...hell of the compressor continuity grounded motor replace compressor 5 Should continuity exist between terminals R and S but not between terminals C and S and C and R the internal overload may be open...

Page 5: ...can be used for each motor or a dual rated capacitor can be used for both The capacitor s primary function is to reduce the line current while greatly improving the torque characteristics of a motor...

Page 6: ...ressure reaches 50 psig This pressure setting cannot be altered The system can be operated at outdoor temperatures as low as 45 F before the evaporator coil will begin to accumulate frost To determine...

Page 7: ...pump to the high side and low side of the system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate the system to an absolute holding pressure of 200 microns or less 12 Resta...

Page 8: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Page 9: ...SOR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for nam...

Page 10: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Page 11: ...11 WIRING DIAGRAM MODELS SH15L30 B and SH20L30 B...

Page 12: ...12 HAZARDGARD CABINET PARTS...

Page 13: ...13 HAZARDGARD CHASSIS PARTS...

Page 14: ...1 399 RELAY SOLID STATE 61108800 2 2 399 6 THERMOSTAT 61822502 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 150 HARNESS WIRE COMP 61821308 1 1 399 REFRIGERATION...

Page 15: ...4905 1 743 30 SCROLL 61817505 1 743 32 BASE PAN 61803444 1 1 730 34 BOLT COMP MOUNT 91400400 3 3 791 35 PLENUM ASSEMBLY 61831006 1 1 753 36 OUTER SHELL 61825708 1 770 36 OUTER SHELL 61825709 1 770 37...

Page 16: ...rranty period providing the unit is returned to an authorized Friedrich Repair Station located within the Continental United States The Friedrich warranty does not cover 1 Any charges for removal tran...

Reviews: