HARD-WIRED SIREN TEST

Press 

The internal relay driving the hardwired siren will be

switched ON for a period of approximately 5 seconds.

Zone LED 2 will be illuminated during the test.

SIREN TEST

Press 

The Control Panel alarm and the External Solar Siren

will be operated for a period of approximately 5

seconds with the external Solar Siren switching ON

and OFF a few seconds after the Control Panel.

Zone LED 3 will be illuminated during the test.

CONTROL PANEL LED TEST

Press 

Zone LED 4 will illuminate.

Use         and         buttons to scroll through and

illuminate each LED in turn.

Press             to exit LED test.

SOLAR SIREN SERVICE MODE

In order to remove the Solar Siren from the wall to

change the batteries.  It is necessary to place the Siren

into Service mode to prevent the Tamper protection on

the Siren operating and triggering the siren.

Press                to switch the Solar Siren between Service

Mode and normal Operating Mode.

Service Mode:  The Solar Siren will produce two

short beeps followed by a single long beep 10

seconds later to indicate that it has switched into

service mode.

Operating Mode:  After 10 seconds the Solar Siren

will produce one long beep followed immediately by

two short beeps to indicate that it has switched into

normal operating mode.

IMPORTANT:  After changing the batteries and refitting

in position, the Solar Siren must be put back into normal

Operating Mode, otherwise the siren will not sound in

the event of an alarm condition.

VOICE DIALLER TEST

Press 

Zone LED 6 will illuminate.

The voice dialler will call each activate number in the

dialling sequence in turn set number of times.  When a

call is answered the recorded alarm message will be

replayed for the set Message Play Time.  If the call is

unanswered or an acknowledgment signal is not

received from the number called, (i.e. by pressing the  

button on the telephone keypad) the next number

in the sequence will be called.

Press             to exit voice Dialler test.

FACTORY DEFAULTS

User Access Code:

1 2 3 4

Alarm Duration:

3 minutes

Hardwird Siren:

Equal to Alarm Duration

Zone Operating Mode:

Zones 1-6:

Intruder

Part-Arm:

Zones 1, 5, 6:

Disabled

Zones 2, 3, 4:

Active

Instant/Delay:

Zone 1:

Delay

Zones 2-6:

Instant

Entry/Exit Delay:

30s

Entry/Exit Warning Tone:

On

Zone Lockout:

On

Jamming Detection:

Off

Phone Numbers:

Not programmed

Message Play Time:

70s

Alarm Message:

Not programmed

Call Routing:

All numbers disabled

Call Attempts:

3

Dial Method:

Tone/DTMF

RESET FACTORY DEFAULT
CONDITIONS

1. Press           ,                                      ,

to place the system in Test Mode.

2. Undo the Control Panel cover fixing screws and

open the cover.

19

ESC

3

4

ESC

5

6

2

User Access Code

?

?

?

?

ENTER

Summary of Contents for SA3 PLUS

Page 1: ...ZONE 1 1 4 2 3 5 6 7 8 0 ENTER ESC ZONE 2 ZONE 3 ZONE 4 TAMPER FIRE ZONE 6 ZONE 5 POWER PART ARM ARM LOW BATT 9 SA3 PLUS with Telephone Dialler Installation Operating Manual...

Page 2: ...gh Environmental Officer to obtain full details of your area s requirements SYSTEM SECURITY This system has been designed to both detect intruders and act as a strong deterrent to would be intruders w...

Page 3: ...formation 15 Positioning the Solar Siren 15 Installing and Configuring the Solar Siren 16 Power up of the Solar Siren 17 Testing the Solar Siren 17 EXTERNAL CONNECTIONS 18 TESTING THE SYSTEM 18 Initia...

Page 4: ...d unless the clamshell is unopened and intact EXTENDING THE ALARM SYSTEM The following additional accessories are available to enhance your system and provide further protection and a higher level of...

Page 5: ...fully armed until after the Entry Exit delay period has expired When a detector on a Delay Armed zone is triggered an alarm condition will not be triggered until after the Entry Exit period has elapse...

Page 6: ...ame frequency If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detection f...

Page 7: ...m system may be extended to provide even greater protection by fitting additional PlR Movement Detectors and Magnetic Contact Detectors as required PLANNING AND EXTENDING YOUR WIREFREE ALARM SYSTEM LE...

Page 8: ...E REMOTE CONTROL 1 Remove the rear cover by undoing the small screw on the rear of the Remote Control and keeping it safe for later 2 Select and record in the Alarm Record section of this manual a ran...

Page 9: ...rotected door or passing through an area protected by a PIR movement detector when the system is armed 5 The Control Panel must be located within reach of a mains socket 6 If the telephone voice diall...

Page 10: ...s to both back up batteries and refit batteries Battery 1 left Red lead to ve battery terminal Blue lead to ve battery terminal Battery 2 right Blue lead to ve battery terminal Black lead to ve batter...

Page 11: ...button is pressed LED ON 1 House Code DIP Switch On Up LED OFF 0 House Code DIP Switch Off Down b Press to save the new setting and return to programming mode c Press to return to programming mode wit...

Page 12: ...h the system House Code and are mounted within effective radio range of the Control Panel The PIR Detector is powered by a PP3 Alkaline battery which under normal conditions will have an expected life...

Page 13: ...of the fixing holes on the wall 4 Fix the rear cover to the wall using the two 18mm No 4 screws and 25mm wall plugs a 5mm hole will be required for the wall plugs Do not over tighten the fixing screws...

Page 14: ...the detector to stabilise before commencing testing 1 Put the Control Panel into Walk Test mode by pressing on the Control Panel The Panel will beep and the Zone 1 LED will illuminate 2 Walk into and...

Page 15: ...tion selected for the Magnetic Contact detector is within effective range of the Control Panel It is recommended that prior to installation the detector is configured and tested with the Control Panel...

Page 16: ...ectors slide onto either side of the circuit board 10 Fit the battery cover into position on the Detector TESTING THE MAGNETIC CONTACT DETECTORS Ensure that the system is in Test mode see page 18 1 Pu...

Page 17: ...unted on a sound flat surface so that the rear tamper switch is not activated when mounted Ensure that the tamper switch does not fall into the recess between brick courses as this could prevent the s...

Page 18: ...ews holding the DIP Switch Cover in place and remove the cover 8 Under the cover you will find a series of 9 DIP switches Note When the Solar Siren is viewed as shown above Solar panel at top the DIP...

Page 19: ...epeatedly during installation and testing as this will rapidly drain the battery It is recommended that the Siren be left for at least a day in order to charge the battery before the system is Armed 2...

Page 20: ...is recommended that the system is tested at regular intervals not exceeding 3 months With the system in Standby Mode with the Power LED ON Press The Arm and Part Arm LEDs will flash The system is now...

Page 21: ...ate that it has switched into normal operating mode IMPORTANT After changing the batteries and refitting in position the Solar Siren must be put back into normal Operating Mode otherwise the siren wil...

Page 22: ...rned OFF Press to save the new User Access code and return to programming mode Press to return to programming mode without saving SYSTEM HOUSE CODE Press The Zone LEDs 1 6 Fire and Tamper LEDs will il...

Page 23: ...nute 2 2 minutes 3 3 minutes 4 5 minutes 5 10 minutes Press the key corresponding to the required alarm period the corresponding zone LED will illuminate as the setting is changed Note When set to No...

Page 24: ...ing OFF Press The zone 1 LED will illuminate to indicate the current Jamming Detector status LED ON Jamming Detection enabled LED OFF Jamming Detection disabled Press to change the setting to the oppo...

Page 25: ...l Attack PA Zone 2 LED Intruder Zone 3 LED 24 Hour Intruder Zone 4 LED Fire Zone 5 LED Test Enter the key corresponding to the required operating mode the corresponding zone LED will illuminate as the...

Page 26: ...cate the active status of telephone numbers 1 4 in the routing sequence LEDs for telephone numbers disabled will be OFF LED ON Telephone number enabled LED OFF Telephone number disabled To change the...

Page 27: ...tart beeping with the beep rate increasing in steps as the delay expires If the system has not been Disarmed when the Entry Delay expires a Full Alarm condition will be initiated If a Full Alarm condi...

Page 28: ...n the system will automatically reset or until the system is Disarmed from the Remote Control or Control Panel The Tamper LED on the Control Panel will flash to indicate the Tamper Alarm has been acti...

Page 29: ...ector has a low battery status it will be indicated on the LOW BAT LED on the Control Panel LED ON Magnetic Contact LED Flashing PIR When a low battery indicator is activated the device will continue...

Page 30: ...e power up battery to ensure that the Unit receives sufficient power until the solar panel can recharge the main battery 3 The main rechargeable battery has a typical life of 3 4 years and needs no ma...

Page 31: ...Access Codes and Installer Access Code below User Access Code System House Code Use the above diagram to record your House Code e g Voice Dialler Phone Numbers Phone Number 1 Phone Number 2 Phone Num...

Page 32: ...lose to metal objects 3 Detector battery low Replace detector battery Detection Zone triggered LED flashing but no alarm is sounding 1 Entry Exit delay still running and not yet expired 2 Alarm durati...

Page 33: ...battery Magnetic Contact Detector not working 1 Ensure batteries are connected with correct polarity 2 Ensure battery connections are good 3 Ensure House Code is correctly set 4 Ensure DIP switches 9...

Page 34: ...Code of Practice on Noise from Intruder Alarms 1981 you should carry out the following procedures within 48 hours of Intruder Alarm installation 1 Notify your local police station in writing that an I...

Page 35: ...aterials and workmanship Understandably if the product has not been installed operated or maintained in accordance with the instructions has not been used appropriately or if any attempt has been made...

Page 36: ...arm message Rings up to 4 telephone numbers 6 Zones Part Arm Facility Instant or Delayed Alarm Zones Programmable Entry Exit Delay Entry Exit Delay Warning selectable Internal piezo siren Connections...

Reviews: