Thermozone AD Corinte A/E

_

GB

secure it using expander bolts or similar in 
the countersunk holes (see fig. 5). Stand the 
air curtain on the edging.

6. Flat bar for fixing of the air curtain is 

supplied. Fix the air curtain through the 
quadratic hole, to secure it sideways. Make 
sure that the flat bar is not bent when 
securing.

7. Secure the top with an angle bracket or 

similar to prevent the air curtain from 
toppling over. There is a hole in the centre 
of the top of the air curtain with an internal 
M6 thread for securing the bracket.

Horizontal mounting

The unit is mounted with the outlet facing 
downwards. Do not remove the protective 
plastic until mounting is completed. Take care 
not to damage the surfaces.

For optimal performance it is recommended 

that a minimum gap of 220 mm to the ceiling 
is maintained above the air curtain. Closer 
mounting might cause over heating.

Two brackets are delivered with the unit 

for mounting on the wall or hanging from the 
ceiling.

Horizontal mounting on the wall

1. Mount the brackets on the wall according to 

measurements in Fig. 7 and 8.

2. Lift the unit into place and lock it using a 

hexagon key and the M8 screws supplied.  
Apply Loctite 270 (3 ml) to the screws 
(supplied).

Horizontal mounting on the wall

1. Mount pendulums or similar (not included 

in delivery) on the ceiling with c-c distance 
according to Fig. 7 and 8.

2. Mount the brackets on the unit with a 

hexagon key and the M8 screws supplied. 
Apply Loctite 270 (3 ml) to the screws 
(supplied).

3. Lift the unit into place and fix the brackets 

to the pendulums.

Note! The unit needs to be further secured if 
suspended from chains.

General instructions

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

Application area

The Thermozone AD Corinte air curtain is 
supplied with or without an electric heater 
coil and is intended for permanent installation 
above or beside entrance doors and other 
openings up to three metres in height/width.
Protection class IP20

Operation

Air is drawn in at the top/rear of the unit and 
blown out downwards/outwards so that it 
shields the door opening and minimizes heat 
loss. To achieve the optimum curtain effect 
the unit must extend the full height/width of 
the door opening.

During installation the exhaust grille is 

normally directed outwards slightly so that 
the airflow obstructs incoming cold air. (See 
fig 1).

The fan speed should be controlled using a 

frequency converter.

The efficiency of the air curtain(s) depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure. 
NOTE! Negative pressure in the building 
considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced.

Vertical mounting

The unit is mounted vertically on the floor 
with the exhaust opening facing outwards.

Before installation, decide whether any 

electrical connections are to be made from 
below.

Do not remove the protecting plastic until 

mounting is completed. Be careful so the 
surfaces are not damaged. 
For installation see figure 3.
1. Undo the screws in the front panel.
2. Undo the screws that secure the front panel 

to the exhaust grille.

3-4. Take off the front panel.
5. Place the edge on the floor and if necessary 

Assembly and operating instructions

Summary of Contents for Thermozone ADC A Series

Page 1: ...Thermozone ADC A E 17 GB 14 SE...

Page 2: ...Thermozone AD Corinte A E 125 60 150 45 150 Min 220 Min 220 30 20 3x Doorway Wall Top Bottom seen from above Wall Top Bottom seen from above Fig 1 M6 M6...

Page 3: ...Thermozone AD Corinte A E 500 350 1700 2200 2450 Fig 2...

Page 4: ...Thermozone AD Corinte A E 1 2 3 4 5 6 2 6 7 Fig 3...

Page 5: ...Thermozone AD Corinte A E Fig 4...

Page 6: ...Thermozone AD Corinte A E 80 12 35 35 180 40 Fig 7 Fig 8 Fig 6 360 243 22 10 15 5 10 Fig 5...

Page 7: ...Thermozone AD Corinte A E Min 220 mm Min 220 mm 50 376 75 1700 2200 1670 2170 75 30 20 3x Left connection Right connection Wall Fig 7 Fig 8 Fig 9...

Page 8: ...Thermozone AD Corinte A E A C A C B B ADCEH 8 12 2x 2 alternatives for securing at the top 1 8 for securing at the air curtain 2...

Page 9: ...Thermozone AD Corinte A E Extra ADEAEB ADEAR ADEAOS MDCDC FC15A M ADCEH ADEA ADEAR ADEAOS MDCDC ADEAIS...

Page 10: ...te Grey TK B1 PE L1 B3 L2 L3 B2 TK Blue Brown TK TK L2 L1 PE B1 B3 B2 L3 TK TK Blue Green Yellow Yellow Black White Green Grey Grey Grey Grey Grey M3 M1 M2 M4 PE L1 L2 L3 TK TK Brown TK TK TK L3 L1 L2...

Page 11: ...Thermozone AD Corinte A E 11 P1 P3 P2 C C N 8 9 K1 K2 11...

Page 12: ...1L2L3 230V ADC17 22 25A PCS EMC filter FC15M 5 1 T3 T2 T1 N L1 L N 2 230V PCS EMC filter FC15M 5 1 ADC17 22 25A FC15M EMC 3 PE 2 PE 230V Motor and control ADC17 22 25A FC15M EMC 3 PE 2 PE 230V Motor a...

Page 13: ...Motor 3x2 5mm2 4 L N 8 5 6 9 11 82 8081 85 8384 8687 6 4 5 9 7 8 10 11 30 2021 41 3140 5051 230V 5 PCS 5 PCS ADEAR ADEAEB ADEAOS MDCDC EMC FC15A 230V Control ADEAR ADEAOS MDCDC ADEAEB P1P2P3 400V3 He...

Page 14: ...internt i apparaten fram till kopplingsplinten Bunta d fast kablarna i apparaten f r att f rhindra att de sugs in i fl ktarna Allm nna anvisningar L s noga igenom denna bruksanvisning f re installatio...

Page 15: ...r att st emot belastningen Generellt kan s gas att ju st rre belastning desto st rre vinkel kr vs Lossa med hj lp av insexnyckel de tre skruvarna som h ller utbl sgallret Vinkla gallret ut t s att lu...

Page 16: ...S kerst ll att omr det kring apparatens insugs och utbl sgaller h lls fritt fr n ma terial som kan hindra luftstr mmen genom apparaten Apparaten har vid drift heta ytor Jordfelsbrytare g ller aggrega...

Page 17: ...he pendulums Note The unit needs to be further secured if suspended from chains General instructions Read these instructions carefully before installation and use Keep this manual for future reference...

Page 18: ...he fans see Fig 6 If not swap two phases in the motor supply to change the direction of rotation When installing ADEA please note that the parameter FANC should be set to 1 see instruction for ADEA fo...

Page 19: ...ar A sample of Fingerprint remover is inclu ded on delivery The product gives a clean and dry surface To order please state no 11631 Fingerprint remover 0 5 l Safety Keep the areas around the air inta...

Page 20: ...United Kingdom Frico Limited Tel 44 0 1213220854 72 Cheston Road Fax 44 0 1213220858 B7 5EJ info uk frico se UK Birmingham www frico co uk United Kingdom Russia Frico repr office in Russia Tel 7 495...

Reviews: