Thermozone AC 300

• When mounting vertically, draught can

occur due to rotating air. The mounting of
a narrow wall at the side of the opening
(the side where no units are mounted),
can decrease the rotation.

Electrical installation

The electrical installation should be carried
out by a qualified electrician in conformity
with prevailing regulations. The appliance
should be preceded by a triple pole switch
with at least 3 mm breaking gap.

Different alternatives for air flow

regulation are possible, see wiring diagram
pages 4-7.

The hatch on the underside of the unit is

opened by turning the locking pins 1/4 of a
lap. The connection should be made with a
cable type S05VV-U, A05VV-R or similar.

On the upper side of the unit there are

knock-outs, 2 pcs ø 37 mm and 3 pcs ø 29
mm. The cable-glands used must guarantee
the protection class requirements!

Type

Power

Voltage

Min. area

kW

V

mm

2

All control

230V

1,5

AC 308

8

230V 3~

4

AC 308

8

400V 3~

2,5

AC 312

12

230V 3~

10

AC 312

12

400V 3~

4

For the units with electrical heating, the
power and voltage should be supplied in
different connection areas (see wiring
diagram).

In the distribution board it is to be

indicated that 

”the air curtains can be

supplied from more than one connection”.

Adjusting the unit and the air stream

Direction and speed of the air stream should
be adjusted with regard to the load on the
door. Pressure forces the air stream to bend
towards the interior of the room (when the
room is heated and the outside is cold). To
withstand the load, the air stream should be
directed outwards. An angel up to 15° can be
recommended. The more load caused by
negativ pressure, temperature differences
and wind, the more should the air stream be
directed outwards.

A baffle on each side of the doorway will

improve the efficiency of the air curtains.

When used above freezer or cooler doors,

the units should be mounted on the warm

side with the air stream directed 0-10°
towards the warm side.

Basic air flow settings

The air flow is set with the air flow selector
so that the speed of the air is 3-4 m/s 1 m
above the floor. The direction of the air
stream and the air speed may need to be
adjusted more exactly depending on the
load on the door.

Trouble shooting

If the fans stand still, check the following:
a) Power supply; check fuses, circuit-breaker,

time switch (if any) that starts and stops
the unit.

b) That the air flow selector is correctly set.
c) That the position limit switch is working

(if any).

If the error cannot be fixed, please contact
qualified service technician.

If there is no heat, check the following:
a) Power supply to electric heater; check

fuses and circuit-breaker (if any).

b) Thermostat settings and actual

temperature.

c) That the output selector (if any) is set

correctly.

d) That the overheat protection has not

been released. If so, please check
description on next page.

Overheating
(applies to units with electric heat)

The Thermozone is equipped with an
overheat protector. If it is released due to
overheating, reset as follows:
a) Disconnect the electricity with the fully

isolated switch.

b) Investigate the matter and repair the

fault.

c) Reset is performed as follows:

• Dismount the service hatch on the
  underside of the unit.
• Locate the red buttons.
• Press the buttons until a click is heard
  (you do not need to press them
  simultaneously).

d) Connect the Thermozone again.

If the error cannot be fixed, please contact
qualified service technician.

GB

21

Summary of Contents for Thermozone AC 300

Page 1: ...Thermozone AC 300 SE 12 8 NO FR 28 24 PL 40 44 IT FI 20 16 GB NL 36 32 RU ES 48 DE...

Page 2: ...Thermozone AC 300 Thermozone AC 300 2 1000 1665 335 11 20 490 Fig 1 975 1640 640 400 min 300 580 Fig 3 280 325 24 65 100 3x 29 287 Fig 2 360 Thermozone AC 300...

Page 3: ...Thermozone AC 300 3 AC 300 Fig 4 45 AVMP300 AVMP300 45 AC 300 Thermozone Thermozone...

Page 4: ...7 5 3 1 2 6 8 ACR 304 0 1 3 5 7 1 2 3 4 N L PTC 1 2 3 4 5 6 N L N L 7 8 9 230V AC 301 302 230V N 2221 AG AC 301 302 1 2 3 4 N L 230V AGB 304 N 2221 AG AC 301 302 1 2 3 4 N L 230V M C M C M C AC301 8...

Page 5: ...Thermozone AC 300 AC 301 302 1 2 3 4 5 6 N L 9 230V AC 301 302 4 5 6 9 AC 301 302 4 5 6 9 1 2 3 4 AGB 304 4 5 6 7 8 3 ACR 3042 2 1 KS104 1 5...

Page 6: ...2 1 400V 3 L L L K1 K2 230 V 3 14 400V 3 230V 3 AC 308 312 400V 3 N 230V 3 1 2 3 2 3 1 Hi Lo KRT 2800 Diff Hi Lo 1 4 C C C C 7 5 3 1 2 6 8 ACR 304 0 1 3 5 7 1 2 3 4 N L PTC 1 2 3 4 5 6 N L N L 7 8 9 2...

Page 7: ...308 312 4 5 6 AC 308 312 4 5 6 3 2 1L L L 400V 3 230V 3 5 1 2 6 EV 300 121314 10 3 2 1L L L 400V 3 230V 3 121314 10 3 2 1L L L 400V 3 230V 3 121314 10 1 2 3 2 3 1 Lo KRT 2800 AGB 304 34 35 36 37 38 3...

Page 8: ...1 Aggregaten f sts med M10 skruvar i monteringskonsolens centrumh l och i ett av sp ren s att hela aggregatet kan vridas och luftens utbl s ningsriktning d rmed justeras Observera angivna minimiavst n...

Page 9: ...n fall till fall Grundinst llning varvtal St ll in varvtalet med hj lp av varvtalsregulatorna s att lufthastigheten 1 meter ver golvet blir 3 4 m s Observera att utbl striktning och varvtal kan beh v...

Page 10: ...den kan variera fr n n gon timma till ett par dygn l f rebyg gande syfte r det l mpligt att anl ggningen tas i drift kortare stunder under l ngre anv ndningsuppeh ll Garantin g ller endast om Frico mo...

Page 11: ...64 L ngd mm 1000 1670 1000 1670 Kapslingsklass IP 24 IP 24 IP 24 IP 24 E nummer 87 514 02 87 514 04 87 514 15 87 514 17 Tillbeh r Beteckning E nummer Varvtalsomkopplare 4 steg 1 ACR 304 87 514 91 Varv...

Page 12: ...tes med M10 skruer i monteringskonsollens sentrumshull og i et av sporene slik att hele aggregatet kan vrides og luftens utbl sningsrettning dermed justeres Observer angitte minimumsavstander fig 3 og...

Page 13: ...lfelle Grunninstilling turtall Still inn turtallet ved hjelp av turtallsregulatorene slik at lufthastigheten 1 meter over gulvet blir 3 4 m s Observer at utbl sningsrettning og turtall kan beh ves fin...

Page 14: ...T rketiden kan variere fra noen timmer til ett par d gn For forebygge dette er det fornuftig at anlegget tas i drift i kortere stunder under lengre driftsstans Garantien gjelder bare om Frico montasj...

Page 15: ...ekt kg 39 57 44 64 Lengde mm 1000 1670 1000 1670 Kapslingsklasse IP 24 IP 24 IP 24 IP 24 El nummer 49 320 14 49 320 15 49 320 16 49 320 17 Tillbeh r Beteckning E nummer Turtallsbryter 4 steg 1 ACR 304...

Page 16: ...in n tai sopivaan rakenteeseen Ilmaverho kiinnitet n kannakkeisiin Kuva 1 Laitteen kiinnitys varmistetaan M 10 ruuveilla kannatti men keskirei st ja yhdest ulokkeesta Kannakkeet sallivat laitteen k nt...

Page 17: ...snopeus s det n tarkemmin kun oviaukko on normaalik yt ss Vianhaku Mik li puhaltimet pys htyv t tarkista seuraavat asiat a S hk liit nt tarkista sulakkeet virtakytkin aikakytkin mik li sellainen on k...

Page 18: ...isaika voi vaihdella muutamasta tunnista muutamaan p iv n Takuu on voimassa ainoastaan silloin kun Thermozone laitetta k ytet n toimittajan ohjeiden mukaan ja noudattamalla asennus ja huolto ohjeita V...

Page 19: ...00 1670 Kotelointiluokka IP 24 IP 24 IP 24 IP 24 Py rimisnopeusvalitsin 4 porras 1 Py rimisnopeusvalitsinmax min 1 Lis laitteet Tyyppi Mitat lxkxs mm Py rimisnopeusvalitsin 4 porras 1 ACR 304 80 100 9...

Page 20: ...ets securely to the wall or suitable structure Attach the air curtain to the brackets Fig 1 The units are secured with M10 screws in the centre hole of each bracket and in one of the notches thus allo...

Page 21: ...sed by negativ pressure temperature differences and wind the more should the air stream be directed outwards A baffle on each side of the doorway will improve the efficiency of the air curtains When u...

Page 22: ...rectified by connecting the appliance to the mains supply via a socket without a safety cut out so that the moisture can be driven out of the element The drying time can vary from a few hours to a fe...

Page 23: ...kg 39 57 44 64 Length mm 1000 1670 1000 1670 Protection class IP 24 IP 24 IP 24 IP 24 Accessories Type Measures BxLxD Air flow selector 4 step 1 ACR 304 80x100x90 mm Air flow selector high low 1 ACR 3...

Page 24: ...es deux querres de fixation murale au mur ou sur tout autre structure ad quate Fixer le rideau d air sur les querres fig 1 Les appareils sont ensuite bloqu s par des vis M10 dans le trou central de ch...

Page 25: ...ge le d bit d air vers l int rieur de la pi ce lorsque la pi ce est chauff e et que l ext rieur est froid Afin de r sister cette d pression le d bit d air doit tre orient vers l ext rieur Un angle jus...

Page 26: ...900 1800 1300 2700 Niveau sonore dB A 44 62 45 63 44 62 45 63 Poids kg 39 57 44 64 Longueur mm 1000 1670 1000 1670 Classe d tanch it IP 24 IP 24 IP24 IP 24 IP24 Accessoires Code Dimensions R gulateur...

Page 27: ...Thermozone AC 300 27...

Page 28: ...h um die Schrauben f r dieAufh ngung zu erreichen Markieren und montieren Sie die gelieferten Befestigungskonsolen an der Wand oder in der Decke Danach bitte die Ger te in den Konsolen Fig 1 aufh ngen...

Page 29: ...f die Belastung des Tores justiert Die Druckkraft beeinflusst den Luftstrom so dass dieser nach innen im Lokal abbiegt bei geheiztem Lokal und kalter Aussenluft Deshalb soll der Luftstrom nach aussen...

Page 30: ...enn die Installation mit Erdschlusschalter gesch tzt ist und dieser beim Einschalten ausl st kann dies auf Feuchte in den W rmeelementen beruhen Wann ein Ger t W rmeelemente enth lt und dies w hrend e...

Page 31: ...dB A 44 62 45 63 44 62 45 63 Gewicht kg 39 57 44 64 L nge mm 1000 1670 1000 1670 Schutzklasse IP 24 IP 24 IP 24 IP 24 Zubeh r Typ Bezeichnung BxLxD Drehzahlregler 4 Stufen 1 ACR 304 80x100x90 mm Dreh...

Page 32: ...even voor wandmontage te kunnen bereiken is een opening van 50 mm tussen de toestellen nodig Bevestig de twee 2 wandmontagebeugels stevig op de wand of geschikte constructie Bevestig het luchtgordijn...

Page 33: ...n de luchtstroom dienen aangepast te worden aan de omstandigheden van de deur Druk laat de luchtstroom naar de binnenzijde van het vertrek buigen wanneer de ruimte verwarmd wordt en de buitenzijde kou...

Page 34: ...erwarming kunnen over meerdere aansluitingen beschikken De ventilatormotoren en andere componenten vereisen geen ander onderhoud dan regelmatig schoonmaken wanneer nodig echter minimaal eens per jaar...

Page 35: ...ij vol vermogen C 27 13 27 13 Geluidsniveau dB A 44 62 45 63 44 62 45 63 Gewicht kg 39 57 44 64 Lengte mm 1000 1670 1000 1670 Beschermklasse IP 24 IP 24 IP 24 IP 24 Accessoires Model Afmetingen BxLxD...

Page 36: ...Thermozone AC 300 RU Thermozone AC300 2 3 5 Thermozone AC300 IP44 ACR304 3042 0 1 2 1 1 EV300 2 KRT2800 50 1 10 10 1 3 AVMP300 AVMP300 10 AVMP300 AVMP300 36...

Page 37: ...zone AC 300 RU 3 5 AXP300 ACR304 3042 EV300 ACR304 KRT2800 4 3 4 5 1 4 SO5VV U AO5VV R 2 29 4 23 Min 2 230 1 5 AC 3088 230 3 4 AC 3088 400 3 2 5 AC 31212 230 3 10 AC 31212 400 3 4 15 0 0 100 3 4 1 a b...

Page 38: ...Thermozone AC 300 RU a b c d a b c Thermozone Frico 38...

Page 39: ...1 6 2 4 11 5 17 3 3 900 1800 1300 2700 900 1800 1300 2700 C 27 13 27 13 44 62 45 63 44 62 45 63 39 57 44 64 mm 1000 1670 1000 1670 IP 24 IP 24 IP 24 IP 24 x x 4 1 ACR 304 80x100x90mm 1 ACR 3042 150x2...

Page 40: ...i M10 Uwaga Zwr uwag na spos b monto wania rys 3 oraz e kurtyny nie mog by instalowane bezpo rednio pod i nad gnia zdami wtykowymi elektrycznymi 40 b Posadowienie kurtyn z boku otworu W przypadku gdy...

Page 41: ...gdy strumie powietrza jest skierowany w przeciwnym kierunku kierunek wychylenia powinien by poprzedzony indiwidualnymi pr bami dla ka dej bramy Nastawa pr dko ci obrotowej Nastawa pr dko ci obrotowej...

Page 42: ...pr dowy Nie powinno to by odbierane jako awaria urz dzenia lecz jako ostrze enie e kurtyna jest zawilgocona W takim wypadku trzeba osuszy grza ki elektryczne we w asnym zakresie Je eli to nie pomo e p...

Page 43: ...62 45 63 Masa kg 39 57 44 64 D ugo mm 1000 1670 1000 1670 Klasa szczelno ci IP 24 IP 24 IP 24 IP 24 Wyposa enie Typ Wymiary BxLxD Regulator obrot w 4 stopniowy 1 ACR 304 80x100x90mm Regulator obrot w...

Page 44: ...ili infiltrazioni d aria tra gli apparecchi i moduli devono essere montati affiancati il pi possibile uno all altro E importante lasciare uno spazio minimo di 50 mm fra i moduli per fissarli a muro Ap...

Page 45: ...ativamente alla pressione sulla porta La pressione forza il flusso d aria verso l interno del locale quando il locale riscaldato e fuori freddo Per contrastare la pressione il flusso dell aria va dire...

Page 46: ...do un modulo stato tenuto fuori esercizio o staccato in ambiente umido su di esso si potrebbe essere formata umidit e quindi potrebbe non funzionare Questo potrebbe non essere considerato come un guas...

Page 47: ...4 62 45 63 Peso kg 39 57 44 64 Lunghezza mm 1000 1670 1000 1670 Classe protezione IP 24 IP 24 IP 24 IP 24 Accessori Tipo Dimensioni BxHxP Selettore velocit 4 stadi 1 ACR 304 80x100x90mm Selettore velo...

Page 48: ...ntre las unidades Fijar los dos soportes de montaje de forma segura a la pared o a una estructura adecuada Fijar la cortina de aire a los soportes Fig 1 Las unidades se aseguran con tornillos M10 en e...

Page 49: ...ratura y al viento m s hacia fuera deber ser dirigida la corriente de aire Una pantalla a cada lado de la puerta mejorar la eficiencia de las cortinas de aire Cuando se usan sobre puertas con refriger...

Page 50: ...4 64 Longitud mm 1000 1670 1000 1670 Clase de protecci n IP 24 IP 24 IP 24 IP 24 Accesorios C digo Dimensiones BxHxP Regulador de caudal 4 etapas 1 ACR 304 80x100x90mm Regulador de caudal 4 etapas alt...

Page 51: ...Thermozone AC 300 51...

Page 52: ...information see www frico se United Kingdom Frico Limited Tel 44 0 1213220854 72ChestonRoad Fax 44 0 1213220858 B7 5EJ info uk frico se UK Birmingham www frico co uk United Kingdom Russia Frico repres...

Reviews: