Unit with electrical heating

The electrical installation is made on the 
top of the unit, fig.2. Control supply (230V~) 
and power supply for heating (400V3~) are 
connected to terminal block in the internal 
connection boxes. 2-metre units require dual 
power supplies.

  The largest cable diameter for the terminal 

block is 16 mm². The cable glands used must 
meet the protection class requirements. In 
the distribution board it is to be indicated that 
”the air curtains can be supplied from more 
than one connection”.

 

See wiring diagrams.
 

Start-up (E)

When the unit is used for the first time or 
after a long period of disuse, smoke or odour 
may result from dust or dirt that has collected 
on the element. This is completely normal 
and disappears after a short time.
 

Connecting the water coil (W)

The installation must be carried out by an 
authorised installer.

The water coil has copper tubes with 

aluminium louvres and is suitable for 
connection to a closed water heating system. 
The heating coil must not be connected to 
a mains pressure water system or an open 
water system.

 Note that the unit shall be preceded by a 

regulating valve, see valve kits.  

The water coil is connected on the upper 

side of the unit with ø15 mm smooth copper 
pipe with a suitable coupling or soldering. 
The connections to the heating coil must be 
equipped with shut off valves (not included) 
to allow problem free removal. Water coil is 
equipped with a drain valve.

A vent valve should be connected at a high 

point in the pipe system. Air valves are not 
included. 
 NOTE: Care must be taken when connecting 
the pipes. Use a wrench or similar to hold the 
air curtain connections to prevent straining 
of the pipes and subsequent water leakage 
during connection to water supply pipe-work. 
 

Adjustment of the air curtain and air flow 

The direction and speed of the air flow should 
be adjusted considering the load on the 
opening. Pressure forces affect the air stream 
and make it bend inwards into the premises 
(when the premises are heated and the 
outdoor air is cold).

The air stream should therefore be directed 

outwards to withstand the load. Generally 
speaking, the higher the load, the greater the 
angle that is needed.

 

Basic setting fan speed 

The fan speed when the door is open is set 
using the control. Note that the air flow 
direction and fan speed may need fine 
adjustment depending on the loading of the 
door.
 

Filter (W)

The water coil is protected against dirt and 
blockage by an internal air filter which covers 
the coil face. 

Service, repairs and maintenance 

For all service, repair and maintenance first 
carry out the following 
1.  Disconnect the power supply.
2.  The front hatch is removed by removing 
the screws on the top of the unit and then 
detach the bent edge at the bottom. (Fig.3)
3.  After the service, repair and maintenance 
reattach the front hatch. Place the hatch at 
the lower edge with the bent edge and fasten 
on top with screws. 

Type

Output 

 

[kW]

Voltage 

 

[V]

Minimum
area

*1

 

[mm

2

]

Control

0

230V~

1,5

PL2510E08

8

400V3~  2,5

PL2515E12

12

400V3~  4

PL2520E16

16

400V3~  6

Summary of Contents for PL2500

Page 1: ...PL2500 Suitable for small entrances 16 GB 20 FR...

Page 2: ...7 5 32 5 25 5 20 5 17 5 Gland Knock out Knock out Knock out Gland Fig 1 Fig 2 Gland 145 345 40 183 78 165 40 1025 1535 2025 20 210 10 145 min 500 min 500 min 500 145 62 40 22 Cu 15 min 500 min 500 145...

Page 3: ...3 PL2500 Fig 3 Open the unit A B C TX20...

Page 4: ...4 PL2500 Fig 4 Minimum distance min 60 Minimum distance...

Page 5: ...5 PL2500 Fig 6 Mounting with wall brackets PL2510 2 pcs PL2515 2 pcs PL2520 3 pcs min 500 mm Mounting with wall brackets A B C D 20 35 75 210 33 8 3x 5 10 162 Fig 6 Mounting with wall brackets...

Page 6: ...PL2500 PA34TR15 PL2510 PL2515 1 m PA34TR20 PL2520 1 m PA2P15 PL2510 PL2515 1 m PA2P20 PL2520 1 m PA2PF15 PL2510 PL2515 PA2PF20 PL2520 PAMLK PL2500 PAWAK PL2500 W FHDN15 PL2500 W PA34TR PA2P PA2PF PAML...

Page 7: ...3 09 25 10 m CC615 673 09 26 15 m CC403 673 09 27 30 m CC405 673 09 28 50 m CC410 673 09 29 10 m CC415 673 09 30 15 Accessories PLS C PLSB PLSAC PLSRTX PLSUR CC CJ4 CJ6 VKF15LF DN15 VKF15NF DN15 VKF20...

Page 8: ...power L2 PE L1 L N L3 400V 3N ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection PLSB2 Over heat C cut out PL2510E08 PL2515E12 PL2520E16 C4 C3 L2 PE L1 L3 400V 3 C1 low power C2 high power M...

Page 9: ...Heating Motor trafo ID pot ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection PLSB2 PL2510WA PL2515WA PL2520WA M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left...

Page 10: ...o Mid Run Right motor L N PE N N F1 F2 F3 H1H2 Heating Motor trafo ID pot ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection SIReB2 N F1 F2 F3 OUT PAMLK C NC NO M Blue Black Brown C Lo Mid R...

Page 11: ...0V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1...

Page 12: ...OOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC SIReCC6XX max 50...

Page 13: ...0 07 1 9 19 8 45 8 0 24 19 6 Min 1250 7 2 36 0 0 03 0 6 14 3 51 5 0 18 10 8 PL2520W Max 2600 15 1 41 0 0 08 3 1 24 4 45 6 0 30 34 6 Min 1800 10 6 36 0 0 05 1 5 19 3 49 6 0 24 22 8 Supply water tempera...

Page 14: ...0 0 11 6 5 9 1 32 9 0 11 6 5 1 Recommended outlet air temperature for good comfort and optimized output 2 Nominal output at given supply and return water temperature Supply water temperature 55 C Roo...

Page 15: ...erage motor A Length mm Weight kg PL2510W 4 7 900 1300 12 11 0 71 42 53 230V 0 45 1026 17 5 PL2515W 9 2 1250 2100 16 13 1 09 41 54 230V 0 6 1536 26 PL2520W 11 5 1800 2600 15 13 1 42 43 55 230V 0 9 202...

Page 16: ...quick fit connections Modular cables are connected to the control board See manual for PLS Unit without heating or with water heating Connected via the built in control board PLS with 1 5 m cord and...

Page 17: ...a drain valve A vent valve should be connected at a high point in the pipe system Air valves are not included NOTE Care must be taken when connecting the pipes Use a wrench or similar to hold the air...

Page 18: ...nit at the inner gable of the connection box 5 Reattach the front hatch and connect the unit again All motors are equipped with an integral thermal safety cut out This will operate stopping the air cu...

Page 19: ...environment moisture can enter the element This should not be seen as a fault but is simply rectified by connecting the appliance to the mains supply via a socket without a safety cut out so that the...

Page 20: ...Art no 208876 2015 02 18 CH Technical Support tel 46 313368600...

Reviews: