background image

Installation Instructions

NOTE: 

Read the entire instruction manual before starting the installation.

SAFETY CONSIDERATIONS

Improper  installation,  adjustment,  alteration,  service,  maintenance,  or

use can cause explosion, fire, electrical shock, or other conditions which

may  cause  death,  personal  injury,  or  property  damage.  Consult  a

qualified  installer,  service  agency,  or  your  distributor  or  branch  for

information  or  assistance.  The  qualified  installer  or  agency  must  use

factory-authorized  kits  or  accessories  when  modifying  this  product.

Refer to the individual instructions packaged with the kits or accessories

when installing. 
Follow  all  safety  codes. Wear  safety  glasses,  protective  clothing,  and

work  gloves.  Use  quenching  cloth  for  brazing  operations.  Have  fire

extinguisher available. Read these instructions thoroughly and follow all

warnings  or  cautions  included  in  literature  and    attached  to  the  unit.

Consult  local  building  codes  and  current  editions  of  the  National

Electrical Code (NEC) NFPA 70.  In Canada, refer to current editions of

the Canadian Electrical Code CSA 22.1.

Recognize safety information. This is the safety-alert symbol 

 When

you see this symbol on the unit and in instructions or manuals, be alert to

the  potential  for  personal  injury.    Understand  these  signal  words;

DANGER, WARNING, and CAUTION. These words are used with the

safety-alert  symbol. 

DANGER

  identifies  the  most  serious  hazards

which  will  result  in  severe  personal  injury  or  death. 

WARNING

signifies  hazards  which  could  result  in  personal  injury  or  death.

CAUTION

 is used to  identify unsafe practices which  would  result in

minor personal injury or product and property damage. 

NOTE

 is used to

highlight  suggestions  which  will  result  in  enhanced  installation,

reliability, or operation.

Installation Recommendations

NOTE: 

In  some cases noise in  the  living area has been traced  to gas

pulsations from improper installation of equipment.

1. Locate  unit  away  from  windows,  patios,  decks,  etc.  where  unit

operation sound may disturb customer. 

2. Ensure that vapor and liquid tube diameters are appropriate for unit

capacity. 

3. Run  refrigerant  tubes  as  directly  as  possible  by  avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb vibration.

5. When passing refrigerant tubes through the wall, seal opening with

RTV or other pliable silicon-based caulk. (See 

Fig. 1

.)

6. Avoid  direct  tubing  contact  with  water  pipes,  duct  work,  floor

joists, wall studs, floors, and walls. 

7. Do not suspend refrigerant tubing from joists and studs with a rigid

wire or strap which comes in direct contact with tubing.(See 

Fig. 1

.)

8. Ensure  that tubing insulation is pliable and completely surrounds

vapor tube.

9. When necessary, use hanger straps which are 1 in. (25.4 mm) wide

and conform to shape of tubing insulation. (See 

Fig. 1

.)

10. Isolate hanger straps from insulation by using metal sleeves bent to

conform to shape of insulation.

A07588

Fig. 1 – Piping Installation

When outdoor unit is connected to factory-approved indoor unit, outdoor

unit contains system refrigerant charge for operation with AHRI rated

indoor  unit  when  connected  by  15  ft.  (4.57  m)  of  field-supplied  or

factory  accessory  tubing.  For  proper  unit  operation,  check  refrigerant

charge using charging information located on control box cover and/or

in the Check Charge section of this instruction.

IMPORTANT: 

Maximum liquid-line size is 3/8-in. OD for all

residential applications including line line.

IMPORTANT: 

Always  install  the  factory-supplied  liquid-line  filter

drier. Obtain replacement filter driers from your distributor or branch.

GH7T

SPLIT-SYSTEM 2-STAGE HEAT PUMP

WITH R-410A REFRIGERANT

2-5 TONS

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before  installing,  modifying,  or  servicing  system,  main  electrical

disconnect switch must be in the OFF position. There may be more than

1 disconnect switch. Lock out and tag switch with a suitable warning

label. 

WARNING

!

EXPLOSION HAZARD

Failure  to  follow  this  warning  could  result  in

death,  serious  personal  injury,  death,  and/or

property damage.

Never use air or any gas containing oxygen for

leak  testing  or  operating  refrigerant

compressors.  Never allow compressor suction

pressure  to  operate  in  a  vacuum  with  service

valves  closed.    See  Service  Manual  for

pump-down instructions. 

Summary of Contents for GH7T

Page 1: ...propriate for unit capacity 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tubes through the wall seal opening with RTV or other pliable silicon based caulk See Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7...

Page 2: ...space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units Position so water snow or ice from roof or eaves cannot fall directly on ...

Page 3: ...iston body of the liquid service valve temporarily held in place with a plastic cap Do not remove the plastic cap until line set tubing is ready to be installed Refer to Fig 4 and follow these steps for piston installation 1 Remove plastic cap holding piston in piston body of liquid service valve 2 Check that piston size stamped on side of piston matches with number listed on unit rating plate Ret...

Page 4: ...th a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Install Liquid Line Filter Drier Indoor Refer to Fig 6 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to 5 in 127 mm long liquid tube from step 1 4 Connect and braze liquid refrigerant tube to the filter dr...

Page 5: ...d readily accessible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 8 A94025 Fig 8 Line Connec...

Page 6: ...at the Y2 signal is communicated via the cool tap to the desired speed tap 2 The Y1 call for low stage cooling energizes the Fan tap on the control board The red wire from the fan tap is connected to tap 1 on the motor Refer to the furnace Product Data to find the corresponding airflow If the airflow setting for low cooling needs to be switched from tap 1 to a different tap jumper a connection fro...

Page 7: ... 5 minute time guard begins counting Compressor will not come on until this delay expires In the event of a power interruption the time guard will not allow another cycle for 5 minutes Compressor Operation The basic scroll design has been modified with the addition of an internal unloading mechanism that opens a by pass port in the first compression pocket effectively reducing the displacement of ...

Page 8: ...oor temperature is between 70 F and 80 F 21 11 C and 26 67 C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjust charge by adding or removing 0 6 oz ft 018 kg m of 3 8 liquid line above or below 15ft 4 57 m respectively For standard refrigerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable...

Page 9: ...unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file Troubleshooting If the compressor fails to operate with a cooling call the t...

Page 10: ...erved A Carrier Company Edition Date 03 22 Catalog No GH7T 01SI Replaces New GH7T Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 10 ...

Reviews: