Frico Arden 3500 Original Instructions Manual Download Page 15

Arden 3500

15

EN

Replacing the electrical coil (E)

1.  Mark and disconnect the cables to the 

electric coil. 

2. Remove the mounting screws securing the 

electric coil in the unit and lift out.

3. Replace faulty electrical coil. 

4. Install the new electric coil in reverse order to 

the above. 

Replacing the water coil (W) 

1. Shut off the water supply to the unit. 

2. Open the vent valve. 

3. Open the drain valve.  

4. When the water coil is empty, disconnect its 

connections. 

5. Remove the mounting screws securing the 

coil in the unit and lift out.

6. Install the new coil in reverse order to the 

above. 

Draining the water coil (W) 

The drain valve is on the underside of the coil 

on the connector side. It can be accessed via 

the service hatch.

Replacing the PC board 

1. The PC board is located in the terminal box. 

Fig. 4  

2. Mark and disconnect the cables to the PC 

board. 

3. Remove the screws securing the board and 

lift out.  

4. Install the new PC board as above in reverse 

order. 

Temperature control 

Temperature control of FC maintains the 

exhaust temperature. Should the temperature 

exceed the preset value, the overheating alarm 

will activate. For more information see the FC 

manual.  

 

Overheating  

The air curtain unit with electrical heating is 

equipped with an overheat protection. If it is 

deployed due to overheating, reset as follows: 

1. Disconnect the power supply with the isolator 

switch. 

2. Determine the cause of overheating and 

rectify the fault. 

3. Open the service hatch. Locate the red button 

next to the terminal box inside the air curtain. 

The 2 metre unit is equipped with two red 

buttons placed in the centre of the unit. 

4. Press the red button until a click is heard. 

5. Reconnect the unit.

Safety cut-out 

All motors are equipped with an integrated 

safety cut-out. This will operate, stopping the 

air curtain should the motor temperature rise 

excessively or the electronics fail or overheat. 

The cut-out will automatically reset when the 

motor temperature has returned to within the 

Troubleshooting  

If the fans are not running or do not perform 

properly, check the following: 

•  The power supply. 

• 

That the intake grille/filter is not dirty. 

•  That the motor's safety cut-out has not been 

deployed.

•  Functions and settings of the FC control 

system, see the FC manual.  

If there is no heat, check the following: 

•  Functions and settings of the FC control 

system, see the FC manual. 

For units with electrical heating, also check the 

following:

•  Power supply to electric heater coil; check 

fuses and circuit-breaker (if any).

•  That the overheat protection has not been 

deployed.

  

For units with a water coil, also check the 

following:

•  That the water coil is air free.

• 

That there is sufficient water flow and 

pressure.

• 

That incoming water is heated adequately.

 

If the fault cannot be rectified, please contact a 

qualified service technician. 

motor’s operating limits. Failure or damage to 

electronics components may require repair or 

replacement of such components or the entire 

product.  

 

Fan replacement 

1. Determine which of the fans is not 

functioning.

2. Disconnect the cables from the relevant fan.

3. Remove the screws securing the fan and lift 

the fan out.

4. Install the new fan as above in reverse order.

Summary of Contents for Arden 3500

Page 1: ...Original instructions Arden 3500 13 EN 17 SE 22 NO 27 FR 33 DE 39 NL 45 ES 51 IT 57 PL 63 RU 69 FI DK 74...

Page 2: ...ten DE Le pagine introduttive contengono prevalentemente immagini Per le traduzioni dei testi scritti in inglese vedere le pagine nelle diverse lingue IT Pocz tkowe strony zawieraj g wnie rysunki T um...

Page 3: ...Type A mm B mm C mm D mm ARFEC3510 1057 1016 1067 956 ARFEC3515 1567 1526 1577 1466 ARFEC3520 2073 2031 2083 1971 646 595 523 302 A B C D 325 532 646 595 523 302 A B C D 325 532 Arden 3500 3...

Page 4: ...eaded bars outside the unit Fig 2 Mounting on threaded bars inside the unit Note that the brackets are placed at different heights and therefore threaded rods should be of different lengths Mounting F...

Page 5: ...tegrated within the air curtain at delivery PC board FC Gland 90 AR Service hatch Service hatch Arden 3500 5 Water connections Fig 5 The water coil is connected inside the unit through holes which are...

Page 6: ...68 FH1020 ARFEC3500W 2 pcs L 1 m 17597 DTV200S ARFEC3500W 19070 AR35XTT10 ARFEC3510 H 130 210 mm 19071 AR35XTT15 ARFEC3515 H 130 210 mm 19072 AR35XTT20 ARFEC3520 H 130 210 mm PA34CB PA34TR PA34VD FH10...

Page 7: ...4695 FCOTX 39x39x23 mm 74699 FCLAP 89x89x26 mm 74702 FCWTA for water heated units 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703 FCTXRF for F...

Page 8: ...GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND 3510 2 Motors 3515 3 Motors 3520 4 Motors 3525 5 Motors 4210 5010 3...

Page 9: ...Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination PAFEC ARF N L3 L2 L1 M M M Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo N Motor 230V L PE 12V HI LO GND 12...

Page 10: ...S1 400V 3 FCBASEPCB REA Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M K4 K3 ARFEC3520E M Outlet sensor Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo...

Page 11: ...r I1 I2 O1O2 Inlet sensor A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE Actuator 24V WTA 12V HI LO GND 12V HI LO BUS 1 BUS 2 E1 E2 GND Outlet sensor 3510 2 Motors 3515 3 Motors 3520 4 Motors 3...

Page 12: ...E IP20 Item number Type Output steps kW Airflow 1 m3 h t 4 C Sound power 2 dB A Sound pressure 3 dB A Motor W Amperage motor A Voltage V Amperage A heat Weight kg 190545 ARFEC3510E09 4 5 9 0 1000 190...

Page 13: ...rways several units can be mounted in series alongside each other Minimum distance from outlet to floor for electrically heated units is 1800 mm Mounting on threaded bars outside the unit 1 The mounti...

Page 14: ...le protects against dirt and blockage and makes a separate filter unnecessary Service repairs and maintenance For all service repair and maintenance first carry out the following 1 Disconnect the powe...

Page 15: ...to the terminal box inside the air curtain The 2 metre unit is equipped with two red buttons placed in the centre of the unit 4 Press the red button until a click is heard 5 Reconnect the unit Safety...

Page 16: ...ection point Safety For all installations of electrically heated products a residual current circuit breaker 300 mA for fire protection should be used Keep the areas around the air intake and exhaust...

Page 17: ......

Page 18: ...AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 189631 2...

Reviews: