one side of the unit. Pierce the gland with 

a screwdriver before entering the cable. 

Control supply 230V~ is routed via the motor 

compartment, secured with preinstalled cable 

ties, and connected to the PC board. Power 

supply for heating (400V3~) is routed via the 

motor compartment, secured with preinstalled 

cable ties, and connected to the terminal block 

in the terminal box. 

The largest cable diameter for the terminal 

block is 16 mm². The cable glands used must 

meet the protection class requirements. In the 

distribution board, it is to be indicated that ”the 

air curtains can be supplied from more than 

one connection”. 

Type 

Output  Voltage 

Minimum 

area*

Control 

*) Dimensioning of external wiring shall comply with 

applicable regulations and local deviations may occur. 

Start-up (E) 

When the unit is used for the first time or after 

a long period of non-use, smoke or an odour 

may result from dust or dirt which has collected 

on the element. This is completely normal and 

disappears after a short time. 

 

Adjustment of the air curtain and airflow 

The direction and speed of the airflow should 

be adjusted considering the load on the 

opening. Pressure forces affect the airstream 

and force it inwards towards the premises 

(when the premises are heated and the 

outdoor air is cold).

The airstream should, therefore, be directed 

outwards to withstand the load. Generally 

speaking, the higher the load, the greater the 

angle required.

  

Basic setting fan speed 

The fan speed when the door is open is 

set using the control. Note that the airflow 

direction and the fan speed may need fine 

adjustment depending on the loading of the 

door.

  

Filter (W) 

The heat coil fin distance, in combination with 

the hole diameter of the intake grille, protects 

against dirt and blockage and makes a separate 

filter unnecessary. 

Service, repairs and maintenance  

For all service, repair and maintenance first 

carry out the following:  

1. Disconnect the power supply. 

2. The service hatch is opened by loosening the 

snap fixings located on the bottom of the unit 

(turn 90°). See Fig. 3.

3. After service, repairs and maintenance close 

the service hatch and make sure that the 

snap fixings lock securely.  

Maintenance 

 Since fan motors and other components are 

maintenance-free, no maintenance other than 

cleaning is necessary. The level of cleaning can 

vary depending on local conditions. Undertake 

cleaning at least twice a year. Inlet and exhaust 

grilles, impeller and elements can be vacuum 

cleaned or wiped using a damp cloth. Use a 

brush when vacuuming to prevent damaging 

sensitive parts. Avoid the use of strong alkaline 

or acidic cleaning agents. 

Connecting the water coil (W) 

The installation must be carried out by an 

authorised installer. 

The water coil has copper tubes with 

aluminium fins and is suitable for connection 

to a closed water heating system. The heating 

coil must not be connected to a mains pressure 

water system or an open water system. 

Note that the unit shall be preceded by a 

regulating valve, see Frico valve kit.  

To access the connections the service hatch 

and intake grille must be opened. The 

water coil is connected via connections with 

dimensions DN20 (3/4’’), inside thread, inside 

the unit. Holes are made during installation on 

the top or the side of the unit, possible places 

are marked with punch marks. See Fig. 5. 

Flexible hoses are available as accessories.  

NOTE: Care must be taken when 

connecting the pipes. Use a pipe wrench 

or a similar tool to grip the air curtain 

connections to prevent straining of the 

pipes and subsequent water leakage during 

connection to the water supply pipe-work. 

The connections to the heating coil must be 

equipped with shut off valves to allow trouble-

free removal.  

Water coil is equipped with a drain and a vent 

valve. 

Summary of Contents for Arden 3500

Page 1: ...Original instructions Arden 3500 13 EN 17 SE 22 NO 27 FR 33 DE 39 NL 45 ES 51 IT 57 PL 63 RU 69 FI DK 74...

Page 2: ...ten DE Le pagine introduttive contengono prevalentemente immagini Per le traduzioni dei testi scritti in inglese vedere le pagine nelle diverse lingue IT Pocz tkowe strony zawieraj g wnie rysunki T um...

Page 3: ...Type A mm B mm C mm D mm ARFEC3510 1057 1016 1067 956 ARFEC3515 1567 1526 1577 1466 ARFEC3520 2073 2031 2083 1971 646 595 523 302 A B C D 325 532 646 595 523 302 A B C D 325 532 Arden 3500 3...

Page 4: ...eaded bars outside the unit Fig 2 Mounting on threaded bars inside the unit Note that the brackets are placed at different heights and therefore threaded rods should be of different lengths Mounting F...

Page 5: ...tegrated within the air curtain at delivery PC board FC Gland 90 AR Service hatch Service hatch Arden 3500 5 Water connections Fig 5 The water coil is connected inside the unit through holes which are...

Page 6: ...68 FH1020 ARFEC3500W 2 pcs L 1 m 17597 DTV200S ARFEC3500W 19070 AR35XTT10 ARFEC3510 H 130 210 mm 19071 AR35XTT15 ARFEC3515 H 130 210 mm 19072 AR35XTT20 ARFEC3520 H 130 210 mm PA34CB PA34TR PA34VD FH10...

Page 7: ...4695 FCOTX 39x39x23 mm 74699 FCLAP 89x89x26 mm 74702 FCWTA for water heated units 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703 FCTXRF for F...

Page 8: ...GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND 3510 2 Motors 3515 3 Motors 3520 4 Motors 3525 5 Motors 4210 5010 3...

Page 9: ...Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination PAFEC ARF N L3 L2 L1 M M M Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo N Motor 230V L PE 12V HI LO GND 12...

Page 10: ...S1 400V 3 FCBASEPCB REA Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M K4 K3 ARFEC3520E M Outlet sensor Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo...

Page 11: ...r I1 I2 O1O2 Inlet sensor A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE Actuator 24V WTA 12V HI LO GND 12V HI LO BUS 1 BUS 2 E1 E2 GND Outlet sensor 3510 2 Motors 3515 3 Motors 3520 4 Motors 3...

Page 12: ...E IP20 Item number Type Output steps kW Airflow 1 m3 h t 4 C Sound power 2 dB A Sound pressure 3 dB A Motor W Amperage motor A Voltage V Amperage A heat Weight kg 190545 ARFEC3510E09 4 5 9 0 1000 190...

Page 13: ...rways several units can be mounted in series alongside each other Minimum distance from outlet to floor for electrically heated units is 1800 mm Mounting on threaded bars outside the unit 1 The mounti...

Page 14: ...le protects against dirt and blockage and makes a separate filter unnecessary Service repairs and maintenance For all service repair and maintenance first carry out the following 1 Disconnect the powe...

Page 15: ...to the terminal box inside the air curtain The 2 metre unit is equipped with two red buttons placed in the centre of the unit 4 Press the red button until a click is heard 5 Reconnect the unit Safety...

Page 16: ...ection point Safety For all installations of electrically heated products a residual current circuit breaker 300 mA for fire protection should be used Keep the areas around the air intake and exhaust...

Page 17: ......

Page 18: ...AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 189631 2...

Reviews: