LDR 8s ac Installation
Page 14
Service Manual LDR 8s AC
PKII
form 9120934 rev. 02/2022
GAS CONNECTION
1. All gas supply connections and any pipe joint compound used must be resistant to the action
of propane gases. Codes require a gas shutoff valve be installed in the gas line ahead of the
rotisserie.
2. With a gas conduit (not included) you can lead the gas connection to the main gas supply.
Connect the rotisserie to the gas line after leveling. Gas supply line must be at least the equi-
valent of 1/2“ (12.7 mm) iron pipe and capable of maintaining the required gas pressure during
full power. Make sure the pipes are clean and free of obstructions, dirt, and piping compound.
Note: After the piping has been checked for leaks, fully purge gas pipes to remove air. Disconnect
the rotisserie from the gas supply piping system during any pressure testing on the gas supply
piping system.
Note: Check all joints in the gas supply line for leaks prior to start up the rotisserie. You can use a
soap and water solution. Do not use an open flame.
3. The gas connection has an outside diameter of ½ inch. See position
2
on the above chapter
“Power connection. The gas connection must be mounted by a registered installer.
4. The r
otisserie must be installed so that the flow of combustion and ventilation air will not be
obstructed. Make sure there is an adequate supply of air in the room to allow for that required
combustion of gas of the rotisserie chamber.
5. Keep the space around the bottom and the ventilation opening in the top of the rotisserie free
from obstacles to guarantee a good air flow in the electrical compartment and combustion
chamber.
6. Appli
ance is for use only with the specific legs or casters specified by the manufacturer.
7. North American rotisseries must be installed conform local codes, or in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Pro-
pane Installation Code, CSA B149.1, as applicable, including:
8. i) Th
e appliance and its individual shutoff valve must be disconnected from the gas supply
piping system during any pressure testing of that system at test pressures in excess of ½ psi
(3.5 kPa).
9. ii) The appliance must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test pres
-
sures equal to or less than ½ psi (3.5 kPa).
10. North American rotisseries must when installed be electrically grounded in accordance with
local codes, or in the absence of local codes, with the National Electric Code, NFPA 70, or the
Canadian Electrical Code, CSA C22.2, as applicable.
11. North American rotisseries equipped with casters must be installed with connectors that com-
ply with the Standard for Connectors for Movable Gas Appliances, ANSI Z21.69 • CSA 6.16.
This connection must include a quick disconnect device that complies with the Standard for
Quick Disconnect Devices for Use With Gas Fuel, ANSI Z21.41 • CSA 6.9.
12. Adequate means must be provided to limit the movement of the appliance without depending
on the connector and quick-disconnect device or its associated piping to limit the appliance
movement. See chapter “Thethering of the unit.