Freedom LiTE Installation Manual Revision 14
P a g e
6 | 30
Table 2.1 Freedom LiTE Range Overview
Freedom LiTE
Home
5/4
Home
10/8
Home
15/12
Home
20/16
Home
30/24
Business
40/32
Business
60/48
Business
80/64
Total Energy Capacity [kWh]
5
10
15
20
30
40
60
80
Energy, 80% DoD [kWh] (1)
4
8
12
16
24
32
48
64
Energy, 90% DoD [kWh]
4,5
9
13,5
18
27
36
54
72
Current Capacity [Ah]
100
200
300
400
600
800
1200
1600
Max & Continuous Charge
Current Limit[A] (2)
100
200
300
400
600
600
800
800
Max & Continuous Charge
Power Limit [kW] (2)
5
10
15
20
30
30
40
40
Max/Continuous Discharge
Current Limit [A] (2)
200/100
300/200
480/300
480/400
750/600
750/600
1000/800
1000/800
Max/Continuous. Discharge
Power Limit [kW] (2)
10/6
15/10
24/15
24/20
38/30
38/30
50/40
50/40
Max Recommended Inverter
Total Rated Continuous
Power [kVA]
8
10
15
15
25
25
35
35
Nominal Voltage [V]
52V, to suit 48V Inverters, min 47V, max 56V
Weight [kg]
49
89
130
173
260
326
508
637
Dimensions on or against wall -
Height x Width x Depth [mm]
500x
340x290
745x
340x290
745x
490x290
745x
640x290
1300x
490x290
1300x
522x370
1300x
743x370
1300x
1009x370
Enclosure and Environmental
Conditions
Aluminium enclosure painted white, for indoor or fully protected under-cover environments, rated to IP20.
DC Connection - Integrated
Cables, [no. and size per
electrode] (3)
1x 50mm
2
1 x 50mm
2
2 x 50mm
2
2 x 50mm
2
2 x 95mm
2
2 x 95mm
2
2 x 95mm
2
2 x 95mm
2
Note: for Australian market external DC isolator required on + and -
Control Interface
RJ45 Socket x 2
–
CAN Bus for Interfacing with Compatible Inverters and System Controllers, and communication
for the connection of parallel batteries
–
note that parallel batteries must all be of the same model.
Protection
Shunt Trip Circuit Breaker sized to suit max current, can be tripped by BMS if critical fault, manual reset. Includes
overcurrent, cell under and over voltage, temperature, weak cell detection, minimum SOC control
Human Interface
State of Charge Display (0 to 100%), Error light, Error Reset Button, USB Plug for Programming
Warranty [4]
10 years or 4 000 cycles for average 80% DoD, and max 90% DoD (refer to product warranty for more details)
Service Life [4]
>16 years (>5 500 cycles) expected life at 70% DoD (1), >20 years (>7 500 cycles) at 50% DoD
Essential Accessories
Note that for connecting the battery to a PC a
USB “printer” cable is required (one is supplied with each battery)
CAN Bus Termination Resistor
–
one required per battery (one included with battery)
CAN Bus Cable (RJ45 LAN Cable)
–
one required per battery (not supplied with battery). Note some inverters will
require a special (non-standard pin configuration) cable
–
see installation manual
Notes to Table 2.1
1)
DoD = Depth of Discharge, recommended 80% DoD for average daily discharge, 70% DoD on average for optimal life
–
max for normal operation 90% DoD, max for system in standby 100% DoD.
2)
Max load duration – 30 seconds per 60 second cycle. 1.5 x Max overload can be handled for 5 seconds.
3)
Fly Leads 1,8m long, power cable Red = Positive, Black = Negative, conductors in table refer to one electrode i.e. per
positive and negative connections