FR200 Series Vector control inverter
- 95 -
Figure 6-11 setting of three-line mode 2
As shown in the preceding figure, if SB1 is ON, the AC drive starts running when SB2 is pressed
to be ON; the AC drive instructs forward rotation when K is OFF and instructs reverse rotation when K
is ON. The AC drives stops immediately after SB1 becomes OFF. During normal startup and running,
SB1 must remain ON. The AC drive's running state is determined by the final actions of SB1, SB2 and
K.
F04.16
Terminal UP/DOWN frequency
adjustment treatment
Range:00
~
11
Default:00
Unit's place: action when stop
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared when the drive stops.
1: Holding
Terminal UP/DOWN frequency adjustment value is maintained when the drive stops.
Ten's digit: action on power loss
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared in case of power loss.
1: Holding
Terminal UP/DOWN frequency adjustment value is saved in case of power loss.
Hundred's digit: integral function
0: No integral function
Adjustment step size is kept constant during terminal UP/DOWN adjustment, in compliance with
F04.17.
1: Integral function enabled
When frequency is adjusted through terminal UP/DOWN, initial step size is set by F04.17.
With the effective lasting time of the terminals, adjustment step size will increase gradually.
F04.17
Terminal UP/DOWN
frequency change step size
Range:0.00
~
50.00Hz
Default:1.00Hz/200ms
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of
terminal UP/DOWN.
F04.18
Power on running terminal
action selection
Range
:
0
~
1
Default
:
0
It is only valid to running command terminal which is set in number 1,2,4,5(Running forward,
running reverse, JOG forward, JOG reverse), and only valid for the first running after power on
0
:
Electrial level effective
When terminal is given running command, running terminal is detected to be ON, inverter start to
run. Please ensure the terminal statue before power on.
1
:
Edge t Electrical level effective
When terminal is given running command, the terminal is detected to jump from OFF to ON and
maintain ON, inverter start to run.
Group F05 Digital Output
F05.00
Y1 output function
Range:0
~
99
Default:1
F05.01
Y2/HO output function
(when used as Y2)
Range:0
~
99
Default:3
F05.02
Relay 1 output function
Range:0
~
99
Default:2
F05.03
Relay 2 output function
Range:0
~
99
Default:11
Define the functions of digital output terminals Y1 & Y2, relay 1 and relay 2.Output terminal
function selections are as follows:
Settin
g
Corresponding
function
Description
0
No output
Output terminal is disabled, and there is no output.
1
Drive is running
The output is ON when the drive is running, and output is
OFF when drive stopped.
2
Fault output
When the drive is in fault, outputs ON.
3
Frequency-level
detection FDT1 output
Refer to the descriptions of F05.10 and F05.11.
4
Frequency-level
Refer to the descriptions of F05.12 and F05.13.