AMA200 Rev150720
15
Options:
00
-
99
This code sets the time interval (1 to 99 minutes) after the silence button is pressed
until the audible alarm sounds again. If set to 0, the alarm will not repeat after the
silence button is pressed.
Code 340 CAN Terminator
Factory programmed value:
On
Options:
On,
Off
This code sets the datalink terminating resistors for this module.
Error Code E201 Datalink
The remote does not detect a valid packet on the datalink from the primary.
Error Code E202 Invalid Code
An invalid program code has been entered. Re-enter program code when the digital
display resets.
Error Code E208 Memory
There is a failure with the internal memory of the module. The bottle pressure shows
in the display alternating with the error code. The Low Air Warning, LED bar graph,
and programming does not function. Contact factory if this error code is displayed.
Error Code E212 Sensor
The primary does not detect the pressure sensor, or the output voltage from the
sensor is out of range (0.3 to 4.9).
Exit Program Access Mode
Press both the
MENU
and
SILENCE
buttons and hold them until the display
shows five dashes. Release the buttons and enter a new code, or after five seconds the
program times out and returns to normal operation.