T
it
le
Franklin Home Power User Manual
Date
August 10, 2021
Doc. No.
FD21081001
Revision
V01
© 2021. FranklinWH Technologies Co., Ltd.
Page 20 Total 31
4
,
Datasheet
4.1 aPower datasheet
Table aPower datasheet
PERFORMANCE SPECIFICATION
COMPLIANCE INFORMATION
Battery Type
Lithium Iron Phosphate
(LFP)
Certificate
UL1973, UL9540, UL9540A, UN38.3, UL1741,
IEEE 1547, IEEE 1547.1, EMI
:
Part 15, Class B
Usable Capacity
13.6kWh
1
Seismic
ACI56, IEE693-2005 (High)
Aggregate Throughput
43MWh
2
Environmental
RoHS Directive 2011/EU
California Proposition 65
Coupling Type
AC Coupling
Emissions
FCC Part 15 Class B
Rated Input/Output Voltage
120/240VAC split
MECHANICAL SPECIFICATION
Feed-in Type
Split phase
Dimensions (H x W x D)
45.3in x 29.5in x 11.4in
1150mm x 750mm x 290mm
Connection Support
L1/L2/N/PE
Net Weight
386lbs. (175kg)
5
Grid Frequency
60Hz
Volume
234L
Real Power, Maximum Continuous
5kW
Mounting
Wall mount or floor mount
Real Power, Peak(10s, off-grid/backup)
10kW (Discharge)
ENVIRONMENTAL SPECIFICATION
Apparent Power, Max Continuous
5.8kVA
Operating Temperature
-
4℉ to 122℉ (
-
20℃ to 50℃)
6
Apparent Power, Peak
(10s, off-grid/backup)
10kVA (Discharge)
Recommended
Temperature
32℉ to 86℉ (0℃ to 30℃)
Load Start Capacity
110A LRA
Operating Humidity (RH) Up to 100% condensing
Maximum Supply Fault Current
10kA
Recommended Storage
Temperature
-
4℉ to 86℉ (
-
20℃ to 30℃)
Up to 95%RH, non-condensing
Maximum Output Fault Current
42A
Maximum Elevation
9843 feet (3000m)
Imbalance for Split-phase Loads
100%
Environment
Indoor or Outdoor
Power Factor Range (Full-rated Power)
-0.85 to +0.85
Enclosure Type
Type 3R
Round Trip Efficiency
86%
3, 4
Ingress Rating
IP67 (Battery and Power Converted
System)
IP56 (Wiring Compartment)
Inverter Topology
Isolated
Warranty
12 y
ears
Noise Level
<30dB(A) optimal,
<45dB(A) maximum
1.
Measured at battery DC output at beginning of life
2.
70% EOL at warranty 12 years and measured at battery AC output.
3.
At 25℃ (77℉) 2.5kW charge/discharge power
4.
AC to battery to AC at beginning of life
5.
The net weight doesn’t include the installation bracket.
6
,
Performance will be derated when the operation temperature >45℃