PUMPTEC-PLUS Pump Protection System
C. Red Light
The red light (C) indicates a line voltage fault occurred and Pumptec-Plus has turned off the pump motor.
A SOLID RED LIGHT indicates an under voltage condition (line< 207 VAC) existed for more than 2.5
seconds. Pumptec-Plus will automatically try to reset the motor within two minutes. The RESET BUTTON
(D) may also be pressed to clear this condition.
A FLASHING RED LIGHT indicates an over voltage condition (line> 253 VAC) has existed more than 2.5
seconds. Pumptec-Plus will automatically try to reset the motor within two minutes. The RESET BUTTON
(D) may also be pressed to clear this condition.
B & C. Red and Yellow Flashing Lights
The red light (C) indicates a line voltage fault occurred and Pumptec-Plus has turned off the pump motor.
A SOLID RED LIGHT indicates an under voltage condition (line< 207 VAC) existed for more than 2.5
seconds. Pumptec-Plus will automatically try to reset the motor within two minutes. The RESET BUTTON
(D) may also be pressed to clear this condition.
A FLASHING RED LIGHT indicates an over voltage condition (line> 253 VAC) has existed more than 2.5
seconds. Pumptec-Plus will automatically try to reset the motor within two minutes. The RESET BUTTON
(D) may also be pressed to clear this condition.
D. Reset Button
The reset button is used to restart the Pumptec-Plus from a tripped condition. Pressing the reset button
for less than ten seconds has no effect on the calibration. Simply press and release the button. The unit
will reset.
Pressing the reset button for more than 10 seconds will cause the unit to go into the calibration mode. A
rotating light sequence from green to yellow to red will begin. At this point, the contactor closes and the
motor will start to run. The unit will stay in the calibration mode for 3 minutes or until the reset button is
pressed again.
If after three minutes the reset button is not pressed, the unit will revert back to its normal running mode,
making no changes to the calibration.
Pressing the reset button before the three minute period expires will cause the unit to recalibrate to the
motor load present at the time the reset button is pressed the second time.
RESET BUTTON
Summary of Contents for PUMPTEC-PLUS
Page 1: ...PUMPTEC PLUS Pump Protection System Installation and Operating Guide ...
Page 14: ...NOTES ...
Page 15: ...NOTES ...
Page 17: ...PUMPTEC PLUS Sistema de protección de bombas Guía de instalación y funcionamiento ...
Page 30: ...NOTAS ...
Page 31: ...NOTAS ...
Page 33: ...PUMPTEC PLUS Système de protection de pompe Instructions d installation et de fonctionnement ...
Page 46: ...REMARQUES ...
Page 47: ...REMARQUES ...