background image

6

STP-SCIIIC:

 For 240 Volt hook signal; 380-415 Volt, 3 phase, 50Hz ¾ , 1 ½ , 3 and 5 Horsepower pumps.

Installation Instructions

1. 

Install STP per applicable Installation and Owner’s Manual.

2.  Remove cover of STP-SCIIIC and mount base to wall or other surface.

3. 

Connect input power of 380-415V for STP-SCIIIC to L1, L2, L3 and Ground wire to terminals. 

 

(See Figure 2.) On High Capacity Pumps (3HP & 5HP) there is no need to connect the Thermal Overload 
wires (blue) coming from the pump as long as an STP-SCIIIC is being used and is calibrated properly. 

4. 

Connect dispenser hook signal or other equipment to terminals, 240V supply and return for STP-SCIIIC.

5. 

Using an ohmmeter, confirm M1, M2 & M3 have continuity to pump. Also, make sure M1 to Ground, M2 to 
Ground, and M3 to Ground are not shorted.

6. 

Connect motor leads to M1, M2 and M3, and Ground wire to terminals.

7. 

Set SW1 Poles 4 and 5 for the motor Horsepower rating (see Table 3).

8.  For Stand Alone installation, set (SW1) poles 1-3 per Table 2 (Factory Set). If installed as Master-Slave and/

or Alternating Circuit go to “Master-Slave/Alternating Circuit” section.

9. 

Attach cover of controller to base. Then go to “Calibration” section to complete installation.

 

WARNING

 

Always replace the cover of the STP-SCIIIC before applying power. Failure to do so could 
result in severe injury or death.

Calibration

Note: 

It is recommended to calibrate all manifolded Master and Slave controllers at the same time.

1. 

Turn on power supply to the STP-SCIIIC. The green light indicator will come on steady, the red light 
indicator will flash 8 times and an audible alarm will sound, thus indicating the controller is Uncalibrated.

Note:

 The audible alarm will sound each time the red light indicator flashes. During the calibration process, 

do not silence the alarm. Once the calibration process has been completed, an alarm can be silenced when an 
abnormal condition is present by briefly depressing the push button. See “Troubleshooting Guide” for details.

2.  Press and hold the push button on the bottom of the box until all three light indicators blink alternately. 

This will take approximately 10 seconds. At this point the push-button should be released.

3. 

The handle on the dispenser should then be lifted to turn the pump on (for more than 16 seconds). After 
16 seconds the controller will take a “snapshot” of the voltage, current and power. The three lights will 
quit alternating and only the green light should remain flashing. This will indicate the calibration has been 
completed and the dispenser handle can then be turned off. If the controller(s) will not calibrate, see the 
“Troubleshooting Guide” section.

Calibration Tips

The “snapshot” values will be used as the nominal values. The calibration process will be aborted if not 
completed within 10 minutes or if the push button is depressed during calibration. The calibration must be 
done at zero flow. If an electronic line leak detector is being used, it is important that the STP-SCIIIC be in the 
calibration mode (all three lights flashing alternately) before the dispenser handle is turned on. Otherwise, the 
STP-SCIIIC will not turn on and the line leak detector will likely detect a fault. If the line leak detector shows a 
fault, it will not provide a dispenser hook signal to the STP-SCIIIC and it will not be possible to calibrate the STP-
SCIIIC until the line leak detector is reset. 

Note:

 

All STP-SCIIICs must be calibrated prior to operation.

Note:

 All three indicator lights will flash alternately in calibration mode.

Note: 

When calibrating system and dispensers that are blenders, both STP-SCIIICs must be calibrated 

simultaneously by selecting the mid-grade at the dispenser.

Note:

 The calibration data is retained in non-volatile memory (i.e. it is saved in the event of power loss to the 

controller).

Summary of Contents for STP-SCIIIC

Page 1: ...3 PHASE SMART CONTROLLER STP SCIIIC INSTALLATION GUIDE...

Page 2: ...ringement of patents or other rights of third parties that may result from use of this manual or the products We make no warranty of any kind with regard to this material including but not limited to...

Page 3: ...ant Safety Messages 5 Installation Instructions 6 Calibration 6 Calibration Tips 6 Master Slave Alternating Circuit 7 Wiring Diagram 1 10 Troubleshooting Guide 11 Resetting The Controller 11 Disabling...

Page 4: ...4 Intentionally Blank...

Page 5: ...ions that follow it are not adhered to could result in serious property damage including possible environmental contamination as a result of the leakage of fuel from the equipment WARNING Follow all f...

Page 6: ...ibration process has been completed an alarm can be silenced when an abnormal condition is present by briefly depressing the push button See Troubleshooting Guide for details 2 Press and hold the push...

Page 7: ...ain wire of shielded cable to Ground G at one end only Wire per NFPA 30A and NFPA 70 For the signal wires use 18 AWG 3 conductor cable 300V min with conductors twisted and within a common jacket Cut w...

Page 8: ...POWER SUPPLY L1 L2 L3 M2 M1 M3 L1 L2 L3 M1 M2 M3 M1 L2 L1 L3 L2 L1 L3 M2 M1 M3 M2 M3 To STP To STP RS 485 G CONNECTION USE THREE CONDUCTOR SHIELDED CABLE WITH DRAIN WIRE 22 AWG MINIMUM RS 485 TO ADDIT...

Page 9: ...tion Table Motor Horsepower Rating Pole 4 Pole 5 Off Off 1 5 Off On 3 On Off 5 On On Table 3 Fault Readout Selection Table Pole 6 Setting Description Off Normal Operation On With this mode selected th...

Page 10: ...THE CONTROL BOX WILL BE ENERGIZED PROVIDING POWER TO THE STP NOTE SEE PRODUCT INSTALLATION INSTRUCTIONS FOR FURTHER DETAILS WIRING MUST CONFORM TO ALL FEDERAL STATE AND LOCAL ELECTRICAL CODES MOTOR CO...

Page 11: ...the dispensers are turned off there may be some power still applied to the STP SCIIIC Hook Connector If this condition exists call Franklin Fueling Systems Technical Service for assistance No lights...

Page 12: ...ew installation reinstall extractable Note PMA can have a locked rotor during startups if it has been exposed to a corrosive environment such as a ballasted tank Turn on power to the STP SCIII unit an...

Page 13: ...M2 M1 to M3 and M2 to M3 and compare the values with the values found in the STP IST Installation Manual High Capacity Installation Manual or TB004 6 Troubleshoot the wiring to determine the cause of...

Page 14: ...ep If condition is still present continue to next step 3 Disconnect power at load centers lock and tag circuit breakers 4 Replace Relay see Replacement Parts section 5 Turn on power to the STP SCIII u...

Page 15: ...or present proceed to the next step 4 With the power still off measure the resistance of the windings See TB004 for the proper values If the measurements are not within the acceptable limits replace P...

Page 16: ...223879102 r2 A Franklin Fueling Systems Brand...

Reviews: