12
Tank Alarms Register
Bit #
Status Bit
0
High High Product
1
High Product
2
High Water
3
Low Product
4
Low Low Product
5
Precision Leak Detected
6
Gross Leak Detected
7
SCALD Leak Detected
8
Product Density High Limit Exceeded
9
Product Density Low Limit Exceeded
10
Float Missing
11
Probe Synchronization Error
12
No Probe Detected
13
Float Height Error
14-31
Reserved
Manifold Data
Manifold Data Register Set
Manifold Register Start Address = (ManifoldNumber-1)*26+3200
Register Description
Address Offset
Data Format
Resolution
Manifold Status Register
0, 1
See Manifold Status Register
Manifold Alarms Register*
2,3
See Manifold Alarms Register
Temperature
4,5
Signed 32-bit Integer
See Volume Units
Gross Product Volume
6,7
Signed 32-bit Integer
See Volume Units
Net Product Volume
8,9
Signed 32-bit Integer
See Volume Units
Water Volume
10,11
Signed 32-bit Integer
See Volume Units
Ullage Volume
12,13
Signed 32-bit Integer
See Volume Units
Reserved
14-20
N/A
*Note that this register does not contain all possible alarms for a tank.
Manifold Status Register
Bit #
Status Bit
0
Manifold in Alarm
1
Delivery in Progress
2-31
Reserved
Manifold Alarms Register
Bit #
Status Bit
0
Low Product
1
Low Low Product
2
SCALD Leak Detected
3-31
Reserved