50
Codes
Fault
Possible Causes
Corrective Action
FF66
Short Circuit
•
When fault is indicated immediately
after power-up, short circuit caused by a
shorted connection, defective cable,
splice, or motor
•
Amperage exceeded 25 amps on DC test
at start or SF amps during running
•
Incorrect output wiring, phase to phase
short, phase to ground short in wiring or
motor
•
Check wiring and fix as necessary
•
If fault is present after resetting and removing mo-
tor leads, replace drive
FF77
Overheated
Drive
•
High ambient temperature
•
Direct sunlight
•
Obstruction of airflow channel
•
Fan blocked or inoperable, ambient
above 122 °F (50 °C)
•
Wait until drive temperature drops below 194 °F (90
°C) to restart
•
Replace fans or fan module; or relocate drive as
necessary
•
Remove debris from fan intake/exhaust
•
Remove and clean optional air screen kit (if
installed)
FF99
Internal PCB
Fault
•
A fault was found internal to drive
•
Contact your Franklin Electric Service Personnel
•
Unit may require replacement. Contact your
supplier.
FF1122
Overvoltage
•
High line voltage
•
Internal voltage too high
•
Check incoming power connections and correct or
tighten terminals if necessary
•
If line voltage is stable and measured below 260
VAC and problem persists, contact your Franklin
Electric Service Personnel.
FF1144
Broken Pipe
•
Broken pipe or large leak is detected in
the system
•
Drive runs at full power for 10 minutes
without reaching pressure setpoint
•
Large water draw, such as a sprinkler
system, does not allow system to reach
pressure setpoint
•
Check system for large leak or broken pipe
•
If the system contains a sprinkler system or is being
used to fill a pool or cistern, disable the Broken Pipe
Detection.
FF1155
Phase
Imbalance
•
Motor phase currents differ by 20% or
more.
•
Motor is worn internally
•
Motor cable resistance is not equal
•
Incorrect motor type setting (single- or
three-phase)
•
Check resistance of motor cable and motor
windings.
•
Verify motor type matched drive settings (single- or
three-phase)
FF1166
Ground Fault
•
Motor output cable is damaged or ex-
posed to water
•
Phase to ground short
•
Check motor cable insulation resistance with megger
(while not connected to drive). Replace motor cable
if needed.
FF1177
Inverter
Temperature
Sensor Fault
•
Internal temperature sensor is
malfunctioning
•
Contact your Franklin Electric Service Personnel
•
If problem persists, unit may require replacement.
Contact your supplier.
FF1188
PFC
Temperature
Sensor Fault
FF1199
Communication
Fault
•
Cable connection between Control Board
and Power Board is loose or
disconnected
•
Internal circuit failure
•
Check cable connection between Display/Wi-Fi
Board and Main Control Board.
•
If problem persists, unit may require replacement.
Contact your supplier.
Summary of Contents for SubDrive 15
Page 1: ...S SU UB BD DR RIIV VE E C CO ON NN NE EC CT T Owner s Manual ...
Page 14: ...14 ...
Page 22: ...22 ...
Page 30: ...30 ...
Page 36: ...36 ...
Page 40: ...40 ...
Page 56: ...56 ...
Page 62: ......
Page 63: ...ESPAÑOL ES franklinagua com SUBDRIVECONNECT Manual para propietarios ...
Page 70: ...8 ...
Page 78: ...16 ...
Page 84: ...22 ...
Page 88: ...26 ...
Page 96: ...34 ...
Page 102: ...40 ...
Page 106: ...44 ...
Page 128: ......
Page 129: ...franklinwater com FRANÇAIS FR SUBDRIVECONNECT Manuel du propriétaire ...
Page 136: ...8 ...
Page 144: ...16 ...
Page 150: ...22 ...
Page 154: ...26 ...
Page 162: ...34 ...
Page 168: ...40 ...
Page 172: ...44 ...
Page 194: ...REMARQUES ...
Page 195: ...REMARQUES ...
Page 196: ......