Fuse/Circuit Breaker and Wire Sizing
The Listed fuse/Listed circuit breaker size and maximum allowable wire lengths for connection to the
SubDrive/MonoDrive are given in the following tables:
A 10-foot (3.05 m) section of cable is provided with the SubDrive/MonoDrive to connect the pressure sensor.
NOTE:
• Maximum allowable wire lengths are measured between the controller and motor.
• Aluminum wires should not be used with the SubDrive/MonoDrive.
• All wiring to comply with the National Electrical Code and/or local codes.
• MonoDrive minimum breaker amps may be lower than AIM Manual specifications for the motors listed
due to the soft-starting characteristic of the MonoDrive controller.
• SubDrive minimum breaker amps may appear to exceed AIM Manual specifications for the motors listed
because SubDrive controllers are supplied from a single-phase service rather than three-phase.
• Motor Overload Protection Note:
The drive electronics provide motor overload protection by preventing motor
current from exceeding the maximum Service Factor Amps (SFA). Motor overtemperature sensing is not
provided by the drive.
Model Family
Listed fuse /
Listed Circuit
Breaker Amps
Nominal
Input
Voltage
AWG Copper Wire Sizes, 167° F (75° C) Insulation Unless Otherwise Noted
14
12
10
8
6
4
3
2
1
1/0
2/0
MonoDrive
15
208
80
125
205
315
500
790
980
1290
1635
-
-
15
230
95
150
250
385
615
970
1200
1580
2000
-
-
SubDrive75
15
208
70
110
185
280
450
710
880
1160
1465
-
-
15
230
85
135
225
345
550
865
1075
1415
1795
-
-
SubDrive2W
20
230
-
125
205
315
505
795
985
1295
1645
-
-
MonoDriveXT
20
208
-
85
140
220
345
550
680
895
1135
-
-
20
230
-
105
175
265
425
670
835
1095
1390
-
-
SubDrive100
25
208
-
-
115
180
285
450
555
730
925
-
-
20
230
-
85
140
220
345
550
680
895
1130
-
-
SubDrive150
30
208
-
-
95
145
235
370
460
605
765
-
-
25
230
-
-
115
180
285
455
560
740
935
-
-
SubDrive300
40
208
-
-
-
-
150
235
295
385
490
610
735
40
230
-
-
-
115
185
290
360
470
600
745
895
Table 3: Maximum Motor Cable Length (in feet)
Controller Model
Franklin Electric
Motor Model
HP
AWG Copper Wire Sizes, 140
o
F (60
o
C) Insulation
14
12
10
8
6
4
SubDrive75
234 514 xxxx
1.5 (1.1 kW)
420
670
1060
-
-
-
SubDrive100
234 315 xxxx
2.0 (1.5 kW)
320
510
810
1000
-
SubDrive150
234 316 xxxx
3.0 (2.2 kW)
240
390
620
990
-
-
SubDrive300
234 317 xxxx
5.0 (3.7 kW)
-
230
370
590
920
-
SubDrive2W
244 505 xxxx
244 507 xxxx
244 508 xxxx
1/2 (.37 kW)
3/4 (.55 kW)
1.0 (.75 kW)
400
300
250
650
480
400
1000
760
630
-
1000
990
-
-
-
-
-
-
MonoDrive
214 505 xxxx
214 507 xxxx
214 508 xxxx
1/2 (.37 kW)
3/4 (.55 kW)
1.0 (.75 kW)
400
300
250
650
480
400
1020
760
630
-
1000
990
-
-
-
-
-
-
MonoDriveXT
224 300 xxxx
224 301 xxxx
1.5 (1.1 kW)
2.0 (1.5kW)
190
150
310
250
480
390
770
620
1000
970
-
-
Table 2: Circuit Breaker Sizing and Maximum Input Cable Lengths (in Feet)
Based on a 3% voltage drop
Highlighted Numbers denote wire with 194° F (90° C) insulation only
XXXX
NOTE: 1 ft = 0.305 m