INSTALLATION AND SETUP
Installation Process
13
Minimum Pressure Tank and Supply Pipe Sizing
A VFD system needs only a small pressure tank to maintain constant pressure, although a larger
tank may be used. If adding a MonoDrive Utility to a conventional system with an existing large
tank, refer to
“Tank Size and Bump Mode Adjustments” on page
26
.
The pressure tank pre-charge setting should be 70% of the targeted system pressure. To check the
tank’s pre-charge, de-pressurize the water system by opening a tap with the drive off. Measure
with a pressure gauge at the inflation valve and make any necessary adjustments.
Refer to the following recommendations for best performance.
Submersible Pump Applications
Minimum Supply Pipe Sizes
The minimum supply pipe inside diameter past the pressure sensor (transducer) should be
selected to not exceed a maximum velocity of 8 feet per second (2.4 m/s) based on the flow rate of
the system.
Pump Flow Rating
Minimum Tank Size up to 1 HP
Minimum Tank Size over 1 HP
Less than 12 gpm (45.4 lpm)
2 gallons (7.6 liters)
4 gallons (15.1 liters)
12 gpm (45.4 lpm) and higher
4 gallons (15.1 liters)
8 gallons (30.3 liters)
Maximum GPM (lpm)
Minimum Pipe Diameter
11.0 (41.6)
3/4”
19.6 (74.2)
1”
30.6 (115.8)
1-1/4”
44.1 (166.9)
1-1/2”
78.3 (296.4)
2”
176.3 (667.4)
2-1/2”
Summary of Contents for MONODRIVE UTILITY UT3W
Page 1: ...MONODRIVEUTILITY Owner s Manual ...
Page 41: ...MONODRIVEUTILITY Manuel d utilisation ...
Page 81: ...REMARQUES Normes en vigueur 41 REMARQUES ...
Page 82: ...REMARQUES Normes en vigueur 42 REMARQUES ...
Page 85: ...MONODRIVEUTILITY Manual del propietario ...
Page 125: ...NOTAS Estándares aplicables 41 NOTAS ...