This instruction sheet provides you with the information required 

to safely own and operate your Little Giant product. Retain these 

instructions for future reference.
The Little Giant product you have purchased is of the highest quality 

workmanship and material, and has been engineered to give you 

long and reliable service. Little Giant products are carefully tested, 

inspected, and packaged to ensure safe delivery and operation. Please 

examine your item(s) carefully to ensure that no damage occurred 

during shipment. If damage has occurred, please contact the place of 

purchase. They will assist you in replacement or repair, if required.
READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE, OR SERVICE 

YOUR LITTLE GIANT PRODUCT. KNOW THE PRODUCT’S 

APPLICATION, LIMITATIONS, AND POTENTIAL HAZARDS. 

PROTECT YOURSELF AND OTHERS BY OBSERVING ALL 

SAFETY INFORMATION. FAILURE TO COMPLY WITH THESE 

INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/

OR PROPERTY DAMAGE!

DESCRIPTION

The OS3 oil-sensing sump system is designed and approved for 

the safe pumping, alarming, and monitoring of elevator sump pits, 

transformer vaults, and leachate wells. The OS3 will activate a pump 

to remove water from elevator pits in accordance with aSme a17.1. 

The OS3 stops the pump before oil or other harmful substances 

enter the water supply. Indicator lights will illuminate on the control 

panel for the following: power, pump running, high alarm, high 

oil, and pump overload (optional). The panel has a set of auxiliary 

contacts that activate on power loss or high oil/water conditions. 

These contacts can be connected to the OS3 remote alarm panel, 

which contains audio/visual alarming along with auxiliary contacts 

for connection to building automation system or Scada system.
When the water level rises to the STaRT probe, the pump turns on. 

The pump remains on until the water level drops below the OFF 

probe. The OFF probe senses air or oil and turns the pump off so 

the oil layer will not be pumped out of the sump. If the liquid level 

reaches the aLaRm probe and HIGH-LeVeL float, the system will 

differentiate between water and oil and activate the remote alarm.

SAFETY GUIDELINES

WARNING: RISK OF eLecTRIcaL SHOcK. PLeaSe OBSeRVe 

THe FOLLOWING SaFeTY GUIdeLINeS.
WARNING: Installation of the system must comply with all federal, 

state and local codes, regulations and practices.
The system must be installed by qualified personnel familiar with 

all applicable local electrical and mechanical codes. Refer to the 

national electrical code (NFPa 70). Failure to properly install and test 

this product can result in personal injury or equipment malfunction.
do not use with flammable or explosive fluids such as gasoline, fuel 

oil, kerosene, etc. do not use in explosive atmospheres. 
Use probe/float switch with water only.
do not handle the system with wet hands or when standing on a wet 

or damp surface or in water.
disconnect all electrical service before working on or handling the system.
ensure that the incoming voltage matches the system voltage.
To prevent electrical shock and equipment malfunction, use only 

with a pump supplied with a grounding conductor and grounding-

type attachment plug. Be certain to plug the OS3 panel into a 

properly grounded, grounding-type outlet.
mount the control panel and alarm indoors. consult the manufacturer 

for outdoor applications.
Use caution with models that use an overload relay. The pump 

motor may start immediately when the overload is reset.
Secure the level sensor on a discharge pipe at a level that guarantees 

partial pump submergence when water level is just below the OFF 

probe. Failure to properly mount the level sensor may cause the 

pump to activate even when oil is present in the sump.
CAUTION: Remove any float switch that is currently used or 

supplied with the pump. If the float switch cannot be removed, 

secure it so that it is always on.

OIL-SENSING 

SUMP SYSTEM 

MODEL OS3

Page 1 of 8

Franklin Electric Co., Inc.

P. O. Box 12010

Oklahoma city, OK 73157-2010

888.956.0000 • Fax: 405.947.8720

www.LittleGiantPump.com

[email protected]

FIGURE 1

Oil Film

Detection Level

Pump START

Level 

Pump OFF

Level

120 V Outlet

120 V outlet 

in elevator 

equipment room

Elevator Sump

Control Panel

Remote alarm has additional 

auxiliary contacts for building 

alarm system.

Oil Alert

Remote alarm

8.82"

6.50"
4.02"

9.75"

5.25"

Mounting flange (1 of 2)

FIGURE 2

Form  #998668        

Summary of Contents for Little Giant OS3

Page 1: ... will differentiate between water and oil and activate the remote alarm SAFETY GUIDELINES WARNING RISK OF ELECTRICAL SHOCK PLEASE OBSERVE THE FOLLOWING SAFETY GUIDELINES WARNING Installation of the system must comply with all federal state and local codes regulations and practices The system must be installed by qualified personnel familiar with all applicable local electrical and mechanical codes...

Page 2: ...ins on Let go of the TEST switch and observe that the alarm light turns off and the green NORMAL light turns on This indicates that the system is now in a normal condition TESTING Upon the complete installation of controls pump and piping test the system for proper operation 1 Test the high oil circuit by lifting the float switch with the sump empty of water Oil is non conductive and when the floa...

Page 3: ...e Le cordon d alimentation ne peut être réparé ou remplacé S il est endommagé la pompe doit être remplacée Ne pas installer ou entreposer la pompe dans un endroit où elle sera exposée à des températures inférieures à 0 C 32 F Ne pas faire fonctionner la pompe dans de l eau ayant une tempéra ture supérieure à 35 C 95 F Garder hors de portée des enfants Ne pas soulever ou abaisser la pompe par son c...

Page 4: ...avant d apparaître 7 Pour réduire le débit des bulles brancher un bout de tube et une vanne non inclus au raccord d entrée REMARQUE Ceci n entrave pas le fonctionnement de la pompe ENTRETIEN AVERTISSEMENT Ne jamais effectuer de manœuvre dans l eau pendant que la pompe ou tout autre composant électrique submergé est branché à une source d alimentation MISE EN GARDE Ne pas utiliser de solvant ou de ...

Page 5: ...Coloque la bomba en el agua PRECAUCIÓN Asegúrese de que todos los componentes están seguros antes de encender la bomba Para una mayor estabilidad y para evitar que la bomba flote sujete el cable de energía al tubo de aire usando amarres y llene las dos aletas laterales con guijarros piedras o grava 5 Cree un bucle para goteo en el cable de energía Figura 3 luego conecte el cable a un tomacorriente...

Page 6: ...The Company shall not be liable for any costs or charges attributable to any product testing maintenance installation repair or removal or for any tools supplies or equipment needed to install repair or remove any product III Limitations Applicable to this Limited Warranty THIS WARRANTY DOES NOT APPLY TO ANY OF THE FOLLOWING 1 Any product that is not installed applied maintained and used in accord...

Page 7: ...ération d accident d abus de modification d actes de Dieu y compris la foudre d actes de terrorisme d actes de guerre d incendie d un mauvais entreposage ou installation d une mauvaise utilisation d un mauvais entretien ou d une mauvaise réparation de dommages ou pertes ou d une utilisation au delà des maximums recommandés comme énoncés dans les instructions du produit 4 Tout produit qui est utili...

Page 8: ...ompañía y la alteración no autorizada de productos de la Compañía 6 Los productos dañados por el desgaste normal mantenimiento normal y las piezas utilizadas en conexión con dicho servicio o cualquier otras condiciones más allá del control de la Compañía 7 Cualquier producto que haya sido utilizado para otros propósitos más allá de aquellos para los cuales fue diseñado y fabricado 8 Cualquier uso ...

Reviews: