36
Trouble
Possible cause
What to do about it
Burner fails to switch
on or switches off
during operation
Lack of water
Provide sufficient water supply
Lack of fuel oil
Refill fuel oil
Burner fails to light or
only with difficulty, bur-
ner is sooting, burner
causes inadmissible
emissions
Wrong burner nozzle
Have an expert replace or clean
burner nozzle resp., (see also
6.4.2 and special dimensioned
drawing incl. technical specifi-
cations).
Burner nozzle dirty
No spark
Have an expert check ignition
transformer and cable; replace
if necessary
Electrodes not in correct posi-
tion; sparks may reach burner
nozzle or baffle
Have an expert adjust elec-
trodes (see special dimensi-
oned drawing)
Faulty fuel oil preheater
Have an expert replace fuel oil
preheater
Solenoid valve fails to open
Have an expert check solenoid
valve, and replace if necessary
Regulating thermostat does not
work
Have an expert check regula-
ting thermostat, and replace if
necessary
Air values not correct
Have an expert adjust air
throttle (see also special dimen-
sioned drawing)
Combustion chamber or hea-
ting oil contaminated
Have an expert clean heating
coil (see also 6.3)
Burner settings incorrect
Have an expert adjust the
correct values on burner (see
special dimensioned drawing)
Heating performance
of the water heater
too low
Combustion chamber or hea-
ting coil contaminated
Have an expert clean heating
coil (see also 6.3)
Heating coil coated with lime
Have an expert delime heating
coil (see also 6.2)