Test for adequacy of air supply is to-: 
Set  the  oil  fired  appliance  going,  close  all  doors  and  windows  in  the  room,  turn  on  the 
extractor fan to its maximum capacity, light the open fire and let it get well established. 
Test for adequate maintenance of chimney vacuum on the appliance, both before and after the 
extractor fan is turned on, with the open fire going.  
During the tests the flue vacuum of the oil fired appliance should be measured to see if there 
is any noticeable reduction beyond that called for in these instructions. 
WARNING 
Instructions on ventilation must be adhered to. 
 
4-4a WATER HEATING 
 
Colibri  Boilers  are  all  high  water  content  boilers  and  as  such  can  easily  replace  solid  fuel 
installations with the minimum of complication. 
Before  you  start  to  install  a  water  heating  Colibri  Boiler  remember  that  the  central  heating 
system must comply with BS:5449 part 1. 
If a combined heating and domestic hot water system is to be used, then a double feed indirect 
hot water storage cylinder to BS:1556 part 1 should be used. 
In order to prevent the build up of scale and corrosion a suitable inhibitor should be used.  
The system must be correctly vented. 
The  height  differential  between  the  header  tank  and  the  appliance  must  not  exceed  15.2 
metres (50 feet) Where a common return is used an injector tee must be incorporated into the 
system  to  ensure  adequate  primary  circulation  when  the  circulating  pump  is  operating.  (see 
detail in FIG16) 
The system must incorporate a gravity circuit which will normally heat the domestic hot water 
and an un-valved radiator or radiators with an output of at least equal to the minimum water 
heating output of the appliance. (see technical spec for details) 
When  the  appliance  is  not  connected  to  a  domestic  hot  water  system  a  gravity  system  must 
still  be  used  with  the  unvalved  radiator(s)  on  the  gravity  circuit  having  a  total  output  of  at 
least the minimum output of the appliance, this is to prevent boiling in case of pump failure. 
Min. pipework in the primary circuit must be 28mm diameter and the gravity flow pipe must 
rise continuously from the boiler to the open vent. 
Typical systems are shown in illustrations FIGS 15,16,18,19 and 20 
Connect  the  heating  system  to  the  boiler  ensuring  that  the  primary  flow  pipe  rises 
continuously from the appliance to the vent. 
Fill the system with water and check for leaks and air locks. 
 
APPLIANCE CONTROLS 
The appliance can be controlled via -: 
The oil control valve which is fitted with-: 
1. A manually operated oil flow control knob 
2. A manually set, automatic thermostat, built into the oil control valve. 
3. A manually and automatically operated oil cut off lever, built into the oil control valve. 
4. An automatically operated safety shut off thermostat, built into the oil control valve which 
trips the oil flow cut off lever mentioned in 3 above. 
The  valve  operates  as  follows,  it  has  flow  control  potential  from  mini  to  maxi  via  six 
graduations and so the appliance can be manually controlled from MINI to MAXI by simply 
turning the flow control knob (1 above), in addition it also has a water sensing thermostat and 
an  automatic  safety  oil  cut  off  device  should  the  appliance  water  temperature  exceed  90 
degree C. 
The water sensing thermostat will automatically control the boiler water temperature at what 
ever setting is required  up to a maximum of 70 degree C.  (2. above) and it is operated by a 
control knob situated alongside the oil flow control knob. 

Summary of Contents for COLIBRI 971.14.11.Z

Page 1: ...raft vaporising pot burner CONTENTS These instructions have been laid out as follows 1 0 HEALTH AND SAFETY 2 0 APPLICABLE REGULATIONS 3 0 INTRODUCTION 3 0 1 MATERIALS REQUIRED 4 0 GENERAL INFORMATION...

Page 2: ...0 90 Max operating pressure bars 3 3 Flexi oil hose diameter mm 6 x 8 6 x 8 Weight kg 105 116 1 0 HEALTH AND SAFETY Control of Substances Take great care when handling materials such as insulation boa...

Page 3: ...could lead to prosecution under the law If you have any difficulties please phone our sales department on Telephone 01302 742520 3 lines INTRODUCTION 1 The Colibri is an oil fired free standing centra...

Page 4: ...nsation and improve the chimney vacuum The chimney should terminate 2 feet above the ridge of the main or highest roof in compliance with relevant legislation For a guide to terminal positions see FIG...

Page 5: ...in the same room as the appliance in a conveniently accessible place see FIGS 7 and 8 Environment protection is of paramount importance Where properties are prone to be at risk from flooding take gre...

Page 6: ...t least equal to the minimum water heating output of the appliance see technical spec for details When the appliance is not connected to a domestic hot water system a gravity system must still be used...

Page 7: ...der the aluminium thermostat casting When the cover is removed it will reveal the operating bellows of the safety stat on the left hand end of the bellows is a straight knurled nut which if screwed in...

Page 8: ...12 CONNECT THE CHIMNEY 13 CONNECT THE ELECTRICAL SUPPLY optional 14 CONNECT THE OIL SUPPLY The appliance leaves the factory with the oil control valve correctly adjusted on the O C V bracket clamping...

Page 9: ...NER IS COMPLETELY COOLED DOWN BEFORE RE LIGHTING EXTINGUISHING Shutting the burner off is a very simple manoeuvre Turn the oil flow control knob fully in a clockwise direction until you feel it stop i...

Page 10: ...is extremely sensitive to flue vacuum variations 2 Good combustion will not be possible unless our instructions on chimneys and flue vacuum are followed 3 If the burner does not burn with a blue flame...

Page 11: ...mance at these flow rates you will need to have matching flue vacuums as stated If the chimney does not generate enough vacuum the flow rates will have to be adjusted so that the burner maintains equi...

Page 12: ...COLIBRI REF 971 14 11 Z 971 21 11 Z Fig 3 Schematic of flue gas flow Fig 4 14kW Burner Fig 5 21kW Burner...

Page 13: ...COLIBRI REF 971 14 11 Z 971 21 11 Z Fig 6 Diagram for Parts List...

Page 14: ...COLIBRI REF 971 14 11 Z 971 21 11 Z Fig 8 Fig 9 Fig 10 C C R S S V3V V E...

Page 15: ...COLIBRI REF 971 14 11 Z 971 21 11 Z Fig 11 Fig 12 Fig 13 Fig 14...

Page 16: ...COLIBRI REF 971 14 11 Z 971 21 11 Z Fig 15 Fig 16 Fig 17 Fig 19...

Page 17: ...COLIBRI REF 971 14 11 Z 971 21 11 Z...

Reviews: