background image

Oil flow rate to low 

If  the  oil  flow  rate  is  too  low  insufficient  heat  will  be 
produced  to  vaporise  the  oil  entering  the  burner,  this  will 
result in the fuel being burnt as liquid which will wick from 
the  bottom  of  the  burner  creating  smoke.  The  same 
symptom can occur with excessive chimney draught at low 
fire as the amount of air passing through the burner will cool 
the burner preventing vaporisation of the fuel. 
 

 
Maximum flame size (no 6 setting) 

The  maximum  flame  size,  depending  on  the  chimney  draught 
requirements, should not touch the top of the stove. The size of the 
flame depends on the chimney draught produced.  
 
If  insufficient  draught  is  created  a  tall  long  lazy  yellow  and 
sometimes sooty flame will occur.  
If excessive the flame size will be small and noisy within the burner. 
 
A good guide is that the flame should not pass higher than the top 
of the glass in the door. If a poor flue draught occurs the flame at 
maximum flow rate should be adjusted to reduce the flow rate to 
gain a correct maximum flame. 
 
 

Solving Negative Pressure Problems 

What to do if the chimney draught is too high at low fire. 
There are two reasons chimney draught can be high at low fire. 
 
1. The chimney is susceptible to increases of draught from external conditions such as wind. 
 If this is the case the flue termination position must be examined to confirm it is correct and a draught stabilising cowl 
fitted.  
 
2. Excessive negative pressure can occur with chimneys over 20ft (6 meters). 
 
Utilize the draught stabiliser at low setting to reduce the chimney draught. This solution can only be used if the higher 
heat settings of the stove are unlikely to be required. 

In this case adjust the draught stabilizer to reduce the flue draught at setting 1 to 0.045” water gauge. Turn the control 

knob to setting 6 maximum and reduce the high fire oil flow setting to decrease the flame size until a clean soot free 
flame is produced. 
A 90mm choke plate, FB237405, can be fitted under the flue collar which will reduce flue draught where there is a 
high flue draught due to the chimney being tall. It cannot be used where the high flue draught is due to wind induced 
conditions. 
 

What to do if the chimney draught is too low at high fire setting. 

This  problem  will  only  normally  occur  with  poor  flue  construction  or  an  unlined  flue  or  short  chimneys.  The  only 
solution to this is to improve the chimney system or calibrate the high fire oil flow to reduce the flame size so it burns 
cleanly. 
 
As many stoves will never be run at high fire the reduction in the flame size on high is generally not a problem in 
comparison to soot formation within the stove. 

Summary of Contents for Burgundy

Page 1: ...TECHNICAL ABGO 1 SIDINGS CLOSE WEDNESFIELD ROAD WOLVERHAMPTON WV11 3DR Oil Stove Installation INSTRUCTIONS FOR FRANCO BELGE OIL STOVES...

Page 2: ...e publications may be superseded during the life of this manual BS 799 Part Five Specification for Oil Tanks BS 5410 Part One Oil Firing Installations Up To 44kW BS 4543 Parts One Three Factory Made I...

Page 3: ...d Installation Commissioning and Servicing Technicians and Tank Installation Technicians from the need to give notice and pay a fee when carrying out new installation work replacement work or making a...

Page 4: ...ote acting fire valves and major changes to flueing systems Part L1 of the Regulations which came into force at the same time covers the energy efficiency aspects of heating system installation partic...

Page 5: ...plate 5 and the clamp 4 from the back and refit them on the top with the 2 screws and washers supplied 7 ensuring there is a good seal 2 Set the ceramic rope in the groove and fix the flue collar at r...

Page 6: ...the requirements of Building Regulations and providing suitable access to facilitate servicing the stove providing a setting which will complement the stove is not a luxury it is the practicality of m...

Page 7: ...ss required for installation This is the minimum distance in front at floor level from the base of the stove All combustible materials above floor level in front of the appliance must be a minimum dis...

Page 8: ...f this heat by being constructed with an internal surface as smooth as possible and by being thermally insulated Both these requirements can be met in an existing chimney by lining it with a stainless...

Page 9: ...ue shall have no more than four bends each providing a maximum change of direction of 45 there should be not more than two of these bends before an access point for sweeping and two between a sweeping...

Page 10: ...e anti down draught cowls work by inducing up draught which can seriously affect the combustion within the burner and may even cause damage to the catalyser It is as important to fit the cowl correctl...

Page 11: ...A metal bowl oil filter mounted to allow adequate room for the removal of the sediment bowl and filter element without difficulty should be fitted in the pipeline to the property We recommend a repla...

Page 12: ...in its main body it regulates with a float valve the depth of oil held it meters with an adjustable outlet the fuel supplied to the burner and its safety float valve will isolate the fuel should the l...

Page 13: ...Toby valve CI valve...

Page 14: ...ill give the actual pressure within the stove but it is not possible to verify the pressures to enable the correct adjustment of the draught stabilizer without a suitable manometer The pressure must b...

Page 15: ...Draught Requirements Burgundy 0 075inches WG 17 Pa 0 035 inches WG 8 Pa Note This is not a water gauge used to measure gas pressure Minimum Maximum Inches water gauge...

Page 16: ...ions The customers who will operate the stove are an essential component of any installation Ensuring they understand the operation of the stove its controls and what to expect from the installation w...

Page 17: ...e stove and flue warm the supply of air being induced into the burner will increase and it will be possible to raise the stove s firing rate progressively until the stove is running at its maximum out...

Page 18: ...inutes should be allowed for the flue draft to stabilise after adjusting the flue stabilizer Low Fire Minimum flame size Flue draught set at the requirement for low fire No 1 setting e g 0 04 wg The c...

Page 19: ...ases of draught from external conditions such as wind If this is the case the flue termination position must be examined to confirm it is correct and a draught stabilising cowl fitted 2 Excessive nega...

Page 20: ...Advise the customer that if the stove is to be out of operation for more than a few weeks that the isolation tap which should be located by the stove should be turned off demonstrate this to the custo...

Page 21: ...Fault Finding Flow Charts...

Page 22: ...Check continuity of igniter Replace igniter if defective Is igniter 2mm from burner floor Adjust igniter to 2mm above burner floor Has oil reached area below igniter...

Page 23: ...Dwyer 460 flue draught gauge recommended Flame burning only from inlet port...

Page 24: ...Fit a stabilizing cowl and or Secondary draught stabilizer Fit a secondary draught stabilizer Adjust draught stabilizer Direct heat from heater or hair drier into stove Balance draught stabilizer agai...

Page 25: ......

Page 26: ...n good condition replace if damaged or hard 13 Using a vacuum cleaner remove dust dog and cat hairs and any cobwebs from behind the stove that could be a fire hazard 14 Reassemble the stove and light...

Page 27: ...Service Record Year Date Company Engineer Tel No Parts replaced 1 2 3 4 5 6 7 8 9 10...

Page 28: ...ppliances without prior notice We make every effort to ensure that the information provided in this document is correct and accurate at the time of printing We would request that you inform ABGO of in...

Reviews: