TECHNICAL DATA
Mod.
FDHE403
Nominal power consumption at
80°F-60% R.H.
W
620W
Voltage Supply
V
115 V, 1 P,
60 Hz
Refrigerant charge
Type
R410A
Quantity of refrigerant
g
720
CONTROL AND SAFETY DEVICES
CONTROL DEVICES
All the control devices are tested on factory before the unit is delivered.
Their operating mode is described in the following paragraphs.
HUMIDITY CONTROL SWITCH
Humidity control switch enables or disables unit operation depending on the humidity value desired.
To verify its correct operation, set the humidity desired value close to lower limit. At this point verify
that fan and compressor (after a time delay) will be started in sequence. Verify as well that the unit is
stopped when humidity set is reached.
INSPECTION, TRANSPORT AND SITE HANDLING
The machine must not be set running in narrow areas, which do not allow a
proper diffusion in the room of the air coming out from the grille. It is, instead,
allowed to set the machine on the sides near the walls.
The front panel should not be used to lay over it cloths or other things: it could
cause damages or dangers.