Description of the menu | 61
FRAKO | Operating Manual | Power Quality Controller – PQC
6.3.5.2 Modbus TCP (IoT)
DHCP ON
To operate the PQC in DHCP mode, DHCP ON must be selected. The data displayed
in this menu (IP, Mask, Gateway) indicate the network settings assigned by the server,
meaning that the available services (Modbus TCP, web server) are accessible in the
network.
DHCP OFF
To use the Ethernet interface with manual network configuration, the following settings
must be made in the PQC:
– IP address
– Subnet mask
– Gateway (optional)
When these settings have been made, the available services (Modbus TCP, web
server) can be accessed in the network.
The PQC is accessible via the Modbus TCP/IP protocol and port 502 at the set IP
address. The data that can be retrieved are listed in the FRAKO Modbus Specification.
Note
The web server is only fully functional with the following browsers:
– Mozilla Firefox version 60.0.1 or later
– Google Chrome version 66.0.3359.181 or later.
The PQC allows a maximum of 2 simultaneous connections.
Note
For additional information on the optional Ethernet interface please refer to
the “PQC Application Note”.