8.1 PQC initial start-up
Key
Action
Back to
main menu
Select
language
de, en, fr
Select
language
de, en, fr
Confirm language
and return to
parameter selection
–
8.1.1 Language selection on start-up
Figure 17 Changing the working language
When the PQC is commissioned, the following parameters can be changed:
Language
·
German, English (factory default setting), French
Voltage transformer
·
Range 1 to 300
Current transformer
·
Range 1 to 7000
Detection
·
Stage + Connection, Stage, Connection or Manual
Stage + Connection
The PQC carries out the automatic stage and connection identification procedure
[see Figure 18
on page 38]
.
Stage
The PQC carries out the automatic stage identification procedure.
The connection must be set manually
[see Figures 21 and 22 on page 38]
.
Connection
The PQC carries out the automatic connection identification procedure.
The parameters for stage detection must be set manually
[see Figures 19 and 20 on page 38]
.
Manual
All parameters for connection and stage identification must be set manually
[see Figures 23 and
24 on page 38]
.
Key
Action
Back to
main menu
Select
par
Select
parameter -
Confirm
–