5

FPI U31-2 Gas Fireplace Insert

REQUIREMENTS 

5.08: 

Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements: 

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for 
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than 
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall 
be satisfied:  

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is 
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery 
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure 
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of 
qualified licensed professionals for the installation of hard wired carbon monoxide detectors 

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon 
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed. 

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions 
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The 
sign shall read, in print size no less than one-half (1/2) inch in size, 

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL 

OBSTRUCTIONS". 

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation 
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 
5.08(2)(a)1 through 4.  

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by 
the Board; and  

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or 
structure used in whole or in part for residential purposes.  

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product 
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the 
instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 

1. Detailed instructions for the installation of the venting system design or the venting system components; and 

2. A complete parts list for the venting system design or venting system.  

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a 
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 
"special venting systems", the following requirements shall be satisfied by the manufacturer: 

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 
detailed installation instructions.  

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, 
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of 
the installation.  

MA Code - CO Detector

(for the State of Massachusetts only)

Summary of Contents for U31-LP2

Page 1: ...appliance Do not touch any electrical switch do not use any phone in your build ing Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot rea...

Page 2: ...VER WILL CAUSE BURNS GLASS UNTIL COOLED ALLOW CHILDREN TO TOUCH GLASS CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES ESPECIALLY THE FIREPLACE GLASS AND SHOULD STAYAW...

Page 3: ...been designed to provide you with all the warmth and charm of a fireplace at the flick of a switch The models U31 NG2 and U31 LP2 of this series have been approved by Warnock Hersey for both safety an...

Page 4: ...ON For Your Safety 6 Specifications 6 Installation into a Solid Fuel Fireplace 6 General Safety Information 6 Installation Checklist 7 Materials Required 7 Minimum Fireplace Clearances 7 Clearances to...

Page 5: ...the fireplace re approved by the authority having jurisdiction Installer l appareil selon les codes ou r glements locaux ou en l absence de tels r glements selon les codes d installation ANSI Z223 1 N...

Page 6: ...in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY...

Page 7: ...is to be installed 3 Ifthefactory builtfireplacehasnogasaccess hole s provided an access hole of 1 1 2 37 5mm or less may be drilled though the lower sides or bottom of the firebox in a proper workman...

Page 8: ...s See page 9 8 Install the log set See page 9 9 Assemble and install the faceplate and trim See page 11 10 InstalltheglassfrontandoptionalBayFront See pages 11 12 11 Install both louvers See page 12 1...

Page 9: ...ance Move the appliance into the exact location where it is to be installed Ensure that the Insert is level 4 The installer must provide a valve with a plugged tapping accessible for test gauge conne...

Page 10: ...ENTING Diagram 1 Diagram 2 THE APPLIANCE MUST NOT BE CONNECTEDTOACHIMNEYFLUE SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE Thisapplianceisdesignedtoattachtoa4 diam eter type B Vent or listed gas fue...

Page 11: ...preventabuild upofcarbonmonoxide Ifthe flue is blocked or has no draw the switch will automatically shut off the supply of gas within 5 10 minutes Tampering with the switch can result in carbon monoxi...

Page 12: ...P Vermiculite k 946 669 Platinum Embers supplied with packaged manual Note Install Optional Brick Panels prior to installing logs 1 Carefully remove the logs from the box and unwrap them The logs are...

Page 13: ...ss the cutout on Log A 02 43 Cutout Pin Cutout Notch 8 Position notch in Front Right Log F 02 48 on Log E 02 47 and push the bottom right edge against the bracket on the burner tray and the front edge...

Page 14: ...nd the front edge of the rear burner Side View 11 Separate platinum embers and place on and around the embers and rockwool on the burner tray Avoid stacking platinum embers 12 Test fire to ensure prop...

Page 15: ...n the assembled faceplate panels aligning the wire connections from the switches with the notch on the left side panel 5 Connect the fan switch wires by taking the black and red wires with the male en...

Page 16: ...ass clips at the top corners of the glass Secure glass clips with the screws provided Do not over tighten as this could break the glass 5 Slide in the top glass trim under the spring clips 2 Position...

Page 17: ...onal remote control thermostat will continue to operate However a 120V A C power supply is needed for the fan blower operation Caution Ensure that the wires do not touch any hot surfaces and are away...

Page 18: ...side trim 2 Lift unit up slightly and push down on the corners of the Bottom Trim Bracket and slide under unit Unit should touch tabs on Bottom Trim Bracket Bottom Trim Bracket Push in Corners 3 Compl...

Page 19: ...Top Frame is held in place by friction fit if the frame needs to be adjusted bend the bracket accordingly Top Frame Hinge Screen Door 7 Install the Left and Right Side Screen Doors in the fully open...

Page 20: ...switch box as sembly 8 Place the switch box assembly over the boss on the rear left side piece and secure with one screw Ensure that the top and sides are aligned 4 Use a measuring tape to ensure that...

Page 21: ...ON Note The top louver should be placed with the curved cut out facing up 13 To put on the Hampton logo peel the sticker from the back of the logo and place it centered on the bottom left hand corner...

Page 22: ...nnectors from the fan speed control Place clips over wires and tuck into side trim for gas connection Self adhesive wire clip ON OFF switch wires to ON OFF switch wires to Fan switch connectors Fan Sp...

Page 23: ...ush down to secure Tug on the Sur round to ensure it is securely locked in place Backside of Sur round Shown Hooks Faceplate Slots Surround Faceplate 4 Secure the Faceplate by sliding the slots in the...

Page 24: ...me control to adjust the flame height higher or lower 10 Close the bottom louver assembly DO NOT BURN THE APPLIANCE WITH THE GLASS ASSEMBLY REMOVED OPTIONAL WALL THERMOSTAT A wall thermostat may be in...

Page 25: ...y or property damage Refer to the owner s information manual provided with this appliance For assistance or additional information consult a qualified installer service agency or gas supplier Release...

Page 26: ...nce and need only be cleanedwithadampcloth DONOTuseabrasive materials or chemical cleaners as they may harm the finish and void the warranty Cleananyfingerprintsoff beforeturningthe unit on If the top...

Page 27: ...oom temperature 2 Unplug or disconnect power source to stove 3 Remove glass front see page 11 4 Remove logs 5 Remove brick panels 6 Remove the Grate by removing the screws on each side of the grate 7...

Page 28: ...Power Cord 20 400 024 Air Channel 21 402 922 Flush Louvers Set Gold Black 402 920 Flush Louvers Set Black 402 924 Flush Louvers Set Steel Black 25 400 992 Bay Louvers Set Gold Black 400 990 Bay Louver...

Page 29: ...Orifice Nat Gas 37 904 593 Burner Orifice Nat Gas 40 High Altitude 904 390 Burner Orifice LP 52 904 345 Burner Orifice Nat Gas 53 High Altitude 60 402 526 Grate Assembly 62 402 512 Burner Assembly NG...

Page 30: ...n Knob Pilot ON OFF 910 426 Extension Knob Flame HI LOW 402 956 Gold Trim Bay Front Bay Flush Front Assembly Part Description Part Description Flush Door 402 515 P Complete Flush Front 150 936 243 Doo...

Page 31: ...d 92 Faceplate Top Standard 93 Faceplate Side Left Assy Standard 402 532 Trims Pkg Standard 94 Faceplate Trim Right Standard 95 Faceplate Trim Top Standard 96 Faceplate Trim Left Assy Standard 402 933...

Page 32: ...31 FPI U31 2 Gas Fireplace Insert PARTS LIST...

Page 33: ...201 Cast Faceplate Right 202 Cast Faceplate Top 203 Cast Faceplate Left 205 Flush Glass Frame 194 Mounting Flange 207 402 981 Cast Grill Set Top Bottom Not available as a replacement part Last digit o...

Page 34: ..._______________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ____________________________...

Page 35: ..._______________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ____________________________...

Page 36: ...portation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of...

Page 37: ...Excalibur and energy are trademarks of FPI Fireplace Products International Ltd FPI fireplaces are designed with reliability and simplic ity in mind In addition our internal Quality Assurance Team ca...

Reviews: