FPI P36-3 Zero Clearance Direct Vent Gas Fireplace
26
Vertical Venting with Two (2) 90
o
Elbows
Option V
H
V + V1
A)
0' Min.
2' Max.
1' Min.
B)
1' Min.
4' Max.
2' Min.
C)
2' Min.
5' Max.
3' Min.
D)
3' Min.
6' Max.
4' Min.
E)
4' Min.
7' Max.
5' Min.
F)
5' Min.
8' Max.
6' Min.
With these options, max.
total pipe length is 30 feet
with min. of 6 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.
Vertical Venting with Three (3) 90
o
Elbows
Option V
H + H1
V + V1
A)
0' Min.
2' Max.
2' Min.
B)
1' Min.
2' Max.
3' Min.
C)
2' Min.
3' Max.
4' Min.
D)
3' Min.
4' Max.
6' Min.
E)
4' Min.
5' Max.
7' Min.
F)
5' Min.
6' Max.
8' Min.
G)
6' Min.
7' Max.
9' Min.
H)
7' Min.
8' Max.
10' Min.
With these options, max.
total pipe length is 30 feet
with min. of 10 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.
INSTALLATION
One 90
o
elbow = Two 45
o
elbows.
One 90
o
elbow = Two 45
o
elbows.
For additional vertical venting with 2 x 90
o
elbows, refer to next page.
Lengths do not include elbow indicated
Lengths do not include
elbow indicated
V1
V
H
V
H1
H
V1