Part No. 26984  Rev. C   May 2018 

- 26 - 

Refrigerated Milk Drawer

 

 
Refrigeration 

cont.

 

REFRIGERATED CABINETS   -  SERVICING 

 

Dixell Default 
Settings

 cont.

 

Label 

Name 

Range 

Default 

AFH 

Differential for temperat. alarm recovery 

(0,1 °C÷25,5°C) (1 °F÷45°F) 

ALd 

Temperature alarm delay 

0 ÷ 255 min 

15 

dAO 

Delay of temperature alarm at start up 

0 ÷ 23h e 50’

 

1.3 

AP2 

Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

P4 

AL2 

Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 

AU2 

Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 

AH2 

Differ. for condenser temp. alar. recovery 

[0,1 °C ÷ 25,5°C] [1 °F ÷ 45°F] 

Ad2 

Condenser temperature alarm delay 

0 ÷ 254 (min.) , 255=nU 

15 

dA2 

Delay of cond. temper. alarm at start up 

0.0 ÷ 23h 50’

 

1,3 

bLL 

Compressor OFF for  condenser low temperature alarm 

n(0) - Y(1) 

AC2 

Compressor OFF for  condenser high temperature alarm 

n(0) - Y(1) 

i1P 

Digital input polarity 

oP=opening; CL=closing 

cL 

i1F 

Digital input configuration 

EAL, bAL, PAL, dor; dEF; Htr, AUS 

EAL 

did 

Digital input alarm delay 

0÷255min 

Nps 

Number of activation of pressure switch 

0 ÷15 

15 

odc 

Compress status when open door 

no; Fan; CPr; F_C 

no 

rrd 

Regulation restart with door open alarm 

 Y 

HES 

Differential for Energy Saving 

(-30°C÷ 30°C) (-54°F÷ 54°F) 

Adr 

Serial address 

0÷247 

PbC 

Kind of probe 

Ptc; ntc 

ntc 

onF 

on/off key enabling 

nu, oFF; ES 

nu 

dP1 

Room probe display 

-- 

-- 

dP2 

Evaporator probe display 

-- 

-- 

dP3 

Third probe display 

-- 

-- 

dP4 

Fourth probe display 

-- 

-- 

rSE 

Set operating value 

actual set 

-- 

rEL 

Software release 

-- 

-- 

Ptb 

Map code 

-- 

-- 

 

XR40CX  
Hot Key 

To program the controller from a Hot Key: 

  Turn OFF the instrument. 

  Insert a programmed Hot Key into the 5 PIN socket and then turn the 

Controller ON. 

  The parameter list of the Hot Key is automatically downloaded into the 

Controller memory, the 

doL

 will blink, followed a by a flashing 

End

  After 10 seconds the instrument will restart working with the new parameters. 

  Remove the Hot Key. 

NOTE the message 

Err

 is displayed if programming fails. In this case turn the 

unit off and then on again, if you want to restart the download again, or remove 
the Hot Key to abort the operation. 

Continued on next page 

Summary of Contents for IL-C-DRW-A001

Page 1: ...Refrigerated Milk Drawer...

Page 2: ...roducts Group Limited All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recor...

Page 3: ...binet Features 8 Large Capacity 8 Adjustable Guides 8 Access Flap 8 Control Panels 9 Temperature Controller 9 Preparation 9 Load the Drawer 9 Power Supply 10 Close the Drawer 10 Turn on Main Switch 10...

Page 4: ...irements 16 Setting Up 16 Unpacking 16 Positioning the Cabinet 16 Support Bolt 16 Condensate Drain 17 Cabinet Preparation 17 Power Supply and Earthing 17 Connection Terminals 17 Isolation 17 Mains Lea...

Page 5: ...27 XR40CX Alarm Recovery 27 XR40CX Connections 27 SPECIFICATIONS 28 Mechanical 28 Electrical 28 Controller Settings 29 Changes from Dixell Defaults 29 1 XR40CX Settings 29 NOTE 29 Compliance 30 Safety...

Page 6: ...structions both general and technical tell you how to operate and look after your inline food service cabinet so that you can receive the full benefits that this cabinet has to offer These instruction...

Page 7: ...rds in the event of compressor failure Any damage or malfunction resulting from the use of non FPG supplied spare parts Specific Exclusions The following are specifically excluded from warranty Breaka...

Page 8: ...packaging Adjustable Guides The inclined gravity feed base has adjustable guides so that products can be consistently organised The products must be lifted into the access flap section so that spaces...

Page 9: ...to the internal temperature of the cabinet The refrigeration gas pressure is also monitored to protect the compressor from damage resulting from a blocked radiator or loss of gas Preparation REFRIGER...

Page 10: ...ION After Hours Ideally cabinets should not be turned off after hours If the cabinet is turned off move the products to cool storage and allow the cabinet to run for about half an hour before replacin...

Page 11: ...ion grills are blocked Vacuum or remove blockage Evaporator coil fins blocked Clean coil fins of food etc Thermostat needs adjustment Adjust controller Ambient temperature 25 C Adjust store air condit...

Page 12: ...rm appears on the Dixell controller screen take the following action 1 Turn off the power supply to the cabinet 2 Clean the condenser pre filter or the condenser coil if the cabinet is not equipped wi...

Page 13: ...h hot soapy water or a good quality glass cleaner DO NOT clean surfaces with abrasive pads or cleaners as surfaces will be damaged Drawer Runners With the drawer fully open vacuum or brush away any de...

Page 14: ...sections may be unclipped from the acrylic strip if required The acrylic strip must be toward the front of the drawer when re assembled Lift Out Sloping Base Tray Note the position of the tray tabs a...

Page 15: ...ont panel Use a vacuum cleaner to remove dust and fluff and wash if necessary Condenser Radiator For efficient refrigeration performance the condenser radiator must be kept clean see Servicing Condens...

Page 16: ...location and any bench cut outs are made to the precise measurements shown in the Mechanical Drawings Position the cabinet in its allocated working position Adjust each foot to set the height ensuring...

Page 17: ...abinet is to be hard wired this must only be done by a suitably qualified person Before connecting to the power supply check that the local supply is correct to that shown on the rating plate located...

Page 18: ...or the low power items and a 24V dc power supply for the anti condensation heating element See the circuit diagram for details The mains switch and refrigeration controller are mounted on the front pa...

Page 19: ...the condenser radiator must be kept clean Failure to do this will lead to a build up of dust and restricted airflow will prevent the unit from working properly The compressor may overheat and the cabi...

Page 20: ...d and lift upwards to disengage the runners The fan panel is secured with four screws and can be lowered after pulling the bottom edge forward Evaporator Fans The fans are hard wired but the panel can...

Page 21: ...yboard XR40CX Compressor Control The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases...

Page 22: ...alue DOWN To see the min stored temperature in programming mode it browses the parameter codes or decreases the displayed value To switch the instrument off if onF oFF Not enabled To lock unlock the k...

Page 23: ...ress and immediately release the SET key or wait for 5 seconds to display the probe temperature again XR40CX Change the Set point To change the set point value press the SET key for more than 2 second...

Page 24: ...key NOTE 1 If no parameter is present in Pr1 after 3s the noP message is displayed Keep the keys pushed till the Pr2 message is displayed NOTE 2 The set value is stored even when the procedure is exit...

Page 25: ...cycle duration 0 0 24 0h 0 0 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 COn Compressor ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty probe 0 255 min 30 CF...

Page 26: ...AL did Digital input alarm delay 0 255min 5 Nps Number of activation of pressure switch 0 15 15 odc Compress status when open door no Fan CPr F_C no rrd Regulation restart with door open alarm n Y y H...

Page 27: ...ous external alarm i1 F bAL All outputs OFF CA Pressure switch alarm i1 F PAL All outputs OFF XR40CX Alarm Recovery Probe alarms P1 P2 P3 and P4 start some seconds after the fault in the related probe...

Page 28: ...s 1 1 Drawer Capacity 24 x 2 litre bottles 24 x 2 litre bottles Refrigerant R134A R134A Refrigerant Charge See cabinet rating label See cabinet rating label Climatic Class IP Cabinets are suitable for...

Page 29: ...ion Unit range Set Set Point 2 degC Hy Differential 2 degC AC Anti Short Cycle Delay 0 Min C0n Comp On Time Faulty Probe 4 Min C0F Comp Off Time Faulty Probe 6 Min dtE Defrost Terminate Temp 4 degC Id...

Page 30: ...tandard EN 61000 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions equipment input current up to and including 16A per phase Part 3 Limits Section 3 Limitations o...

Page 31: ...IL C DRW A001 A003 31 Future Products Group ELECTRICAL CIRCUIT DIAGRAMS Model IL C DRW A001 A003 Refrigerated Milk Drawer...

Page 32: ...o satisfy warranty conditions and ensure optimum performance use only FPG supplied spare parts Part Description FPG Part No Switch DPST 16A 250V 17287 Fuse 5A 13330 Power supply 24V 60W 21613 Dixell X...

Page 33: ...IL C DRW A001 A003 33 Future Products Group MECHANICAL DRAWINGS Model IL C DRW A001...

Page 34: ...Part No 26984 Rev C May 2018 34 Refrigerated Milk Drawer Model IL C DRW A003...

Page 35: ...IL C DRW A001 A003 35 Future Products Group...

Page 36: ...change specifications and design without notice AUSTRALIA E ausales fpgworld com T 1800 813 745 CHINA ASIA E asales fpgworld com T 86 21 3351 3390 EUROPE E eusales fpgworld com T 31 6 5253 4769 INDIA...

Reviews: