Refrigerated Milk Drawer
Refrigeration
cont.
REFRIGERATED CABINETS - SERVICING
Support Bolt
The support bolt must be unscrewed if
the cabinet is to be removed from the
joinery, or access to the evaporator
fans, coil or probes is required.
Evaporator
Access
The drawer must be removed to access
the evaporator fans, coil and
temperature probes.
Pull the drawer fully forward and lift
upwards to disengage the runners.
The fan panel is secured with four
screws, and can be lowered after pulling
the bottom edge forward.
Evaporator
Fans
The fans are hard-wired, but the panel
can be rested on the runners whilst
servicing.
Take care not to trap the cables when
replacing the panel.
Temperature
Probes
There are two temperature probes on the cooling
coil.
The defrost termination probe is located between
the fins, at the top of the coil.
The temperature control probe is supported in
free air, below the coil. It responds to the return
air, (air-on) temperature.
Continued on next page