DANGER
RISK OF ELECTRIC

SHOCK

   

DANGER

     

WARNING

 

 

The “Mains power on” LED comes on to indicate that the board is functioning properly. 

The motor can be governed directly by the operator with man present (Manual) or by remote 

signals (Automatic) by means of the “Automatic – Off – Manual” buttons; (when the 
automatic button is pushed the related LED above the button lights and the control panel is 
ready to receive remote signals from the sensors and floats).  

 
- G.MIN input  can have double function: 

  
With “AUTORITENUTA” jumper ON: G.MIN is used as STOP LEVEL (The 2 pumps continue 

to run, after G1 and G2 command, until the G.MIN float switch is no longer tilted); 
Without “AUTORITENUTA” jumper : G.MIN is used as MINIMUM LEVEL FLOAT SWITCH and 

all the pumps can only work when the minimal level is exceeded.

 

With “EXC ALLAR.” Jumper it is possible to exclude the “LEVEL ALARM” red light  
and the OUTPUT ALARM RELAY when G. MIN float switch is switches off. 

This function is used when “AUTORITENUTA” Jumper is ON. 
 

- G1 input  is used as EXCHANGER function (it can be any free voltage contact – float switch) 
 

- G2 input is used as EMERGENCY  function (the second pump starts after 4-5 second) 
 

- G.A. input is used as LEVEL ALARM function (when switches-on the 12Vcc SIREN output is 
ON with a MAXIMUM absorption 30 mA) 
  

The green pilot lights “Motor ON” indicate the functioning of the motors.  

If the Overload protections are tripped

, the motors stop and the red “MOTOR PROTECTION 

ENABLED” and the red “LEVEL ALARM” LED lights on. Push RESET to reset the alarm; 

Check for the cause of the malfunction before restoring the motor to operation.  
 
If the motor has 2 wires for the thermal protection of the motor winding, connect them to the 

“THERMAL T1” input terminal. If the protection cuts in, the motor is cut out when the contacts 
open. If the motor does not have a built-in protection, then it is necessary to make a jumper 

on THERMAL T1 input in order to enable the motor.  
 

- The ammetric protection tripping current can be adjusted by means of the 
“CORRENTE MOTORE” (MOTOR CURRENT) Trimmer, based on the rated absorption of 

the motor; the adjustment can be made from a minimum of 2A to a maximum of 22A.  
The cut-in delay time is fixed at 5 seconds and can be overridden during setting by 
bridging the “ESCL.TIM.TA” Jumpers; 

 
GENERAL NOTES :

 

During the calibration for Over-Load Protection, start the motor 2-3 times to check the 
correct operating. 

 

 
 
 

 
 

 
 

 
 

5. STANDARD OPERATIONS 

Summary of Contents for DUPLEX-UP

Page 1: ...TION HANDBOOK DUPLEX UP CONTROL PANEL FOR 2 ELECTRIC PUMPS WITH CURRENT CONTROL PR T FG006172 Date 10 02 14 Rev 01 Via Enrico Fermi 8 35020 Polverara PD Tel 049 9772407 Fax 049 9772289 www fourgroup i...

Page 2: ...6 6 Installation page 7 8 7 Electrical connection page 9 10 8 Regulation and calibration page 11 9 Stop of the pumps page 12 10 Lights and push buttons page 12 11 Maintenance page 13 12 Waste disposal...

Page 3: ...rt them CAUTION The control panel must be connected by a qualified electrician in compliance with the electrical regulations in force CAUTION The electric pump or the motor and the panel must be conne...

Page 4: ...our customer service Our units must be installed in sheltered well ventilated non hazardous environments and must be used at a maximum temperature of 40 C and minimum of 5 C DANGER WARNING The panel m...

Page 5: ...2 pumps Possibility to exclude a damaged pump Internal selector for exclusion of pumps exchanger Push buttons for AUTO OFF MANUAL motor operation MANUAL temporary Green led for power on N 2 green led...

Page 6: ...function the second pump starts after 4 5 second G A input is used as LEVEL ALARM function when switches on the 12Vcc SIREN output is ON with a MAXIMUM absorption 30 mA The green pilot lights Motor O...

Page 7: ...switch measured in accordance with the regulations locally in force Line of motor power supply Connect the unit at ground before carrying out any other operation The voltage input corresponds to the...

Page 8: ...ANEL TO A WALL AS IN PICTURE N 1 WITH SCREWS AND SCREW ANCHOR USING THE HOLES ARRANGED IN THE BOX OR THE FIXING BRACKET IF PRESENT AFTER THE FIXING REMOVE EVERY PLASTIC OR METALLIC SURPLUS ex Pieces o...

Page 9: ...WITH JUMPER IN ON POSITION PUMPS EXCHANGE IS ACTIVES WITH JUMPER IN OFF POSITION PUMPS EXCHANGE IS NOT ACTIVES G1 IS ONLY THE FLOAT SWITCH FOR PUMP 1 G2 IS ONLY THE FLOAT SWICTH FOR PUMP 2 JP1 JUMPER...

Page 10: ...PUMP 1 G2 IS ONLY THE FLOAT SWICTH FOR PUMP 2 JP1 JUMPER AUTORIT WITH JUMPER CONNECTED AUTORITENUTA IS ACTIVE G MIN IS USED AS STOP LEVEL FLOAT WITH JUMPER DISCONNECTED AUTORITENUTA IS NOT ACTIVE G MI...

Page 11: ...e current protection cut in delay time by CONNECTING the E T TA JUMPER Set the maximum value with the internal regulator on the Protection tripping current panel turn clockwise Turn the motor on and w...

Page 12: ...S ON RED LIGHT INDICATES THAT THE MOTOR IS RUNNING GREEN LIGHT CONTEMPORARY LIGHTING INDICATES THAT THE OVERLOAD PROTECTION IS ON RED LIGHTS INDICATES THAT THE CLICSON THERMAL PROTECTIONS IS ON RED LI...

Page 13: ...trol panel has been installed and started the customer must provide for the appropriate elimination disposal of the waste materials according to the legislation locally in force If the control panel o...

Page 14: ...f any type or nature malfunction due to improper installation repair disassembly or tampering by unauthorized persons failure by the customer to pay due amounts The defective product must be returned...

Page 15: ...wing European directives and with the national directives of actuation Machine 2006 42 CEE European Directive 2006 95 CE Electromagnetic compatibility 2004 108 CEE and the following technical rules EN...

Page 16: ...16 16 CONNECTION DIAGRAMS CONNECTIONS DUPLEX UP M CONNECTIONS DUPLEX UP T...

Reviews: