Foster FKS 10-4 Technical Manual Download Page 7

Controller Parameter Settings

Display

When the unit is switched on the display shows “- - -” for a period of 

five seconds, during which the controller performs a self check.  The 

display then shows the air temperature measured by probe 1.

The coil temperature, measured by probe 2 may be viewed by pressing  

 ].

Access to the control parameters is achieved by pressing in sequence 

  ]

  + 

  ]

  + 

  ]

  and  holding  in  keys  for  a  period  of  4 

seconds.

It is possible to scroll through the parameters by pressing  —  

 

  or  

 ]

.

The value of a selected parameter is checked by pressing  - 

 ]

 and 

may be altered by pressing at the same time 

 ]

 + 

 ]

 or

 ]

.

Exit from setup occurs after 10 seconds if no key is pressed.

If  an  alarm  condition  is  entered  the  alarm  buzzer  will  sound  and 

ALM

will  flash  on  the  display.    The  alarm  may  be  acknowledge  by 

pressing

any key causing the buzzer to cease and the display will alternate 

between  ‘

ALM

’  and  air  temperature  while  the  alarm  condition 

persists. 

Display 

Parameter 

LDU151E-B 

Duet High Temp

 

 

Default Values 

Used in Panels F,H,L.

  SCL 

Readout Scale 

2°C 

2°C

  SPL 

Minimum Temperature Set Point 

05 

0

  SPH 

Maximum Temperature Set Point 

01 

8

  SP 

Effective Temperature Set Point 

03 

2

  HYS 

Hysteresis 

+3

  CRT 

Compressor Rest Time (minutes) 

10 

2

  CDC 

Compressor Regulation with T1 Fail 

20 

7

  DFR 

Defrosting Frequency (/24 hours)  

4

  DTO 

Defrosting Duration (minutes) 

20 

15

  DDY 

Defrost Display Control 

1

  ATL 

Low Alarm Differential 

-5 

-5

  ATH 

High Alarm Differential 

10

  ATD 

Temperature Alarm Delay (minutes) 

60 

90

  ACC 

Condenser Clean Interval 

05 

0

  OAU 

Auxiliary Output Mode of Operation 

30 

ALR

  BAU 

Auxiliary Button Mode of Operation  

05 

NON

  OS1 

T1 Offset 

00 

00

  SIM 

Display Slowdown 

00 

00

  ADR 

Address 

01 

01

 

ALARMS AND WARNINGS

 

HI 

High Temperature Alarm 

LO 

Low Temperature Alarm 

E1  

T1 Probe Failure

DF 

Defrosting in Progress

CLN  

Condenser

LDU 151E-BG Electrical Connections

DUET ‘HV’ AND ‘GP’ SERIES

DA
TA

PWR

AUX

T1

1

2

3

4

5

6

7

8

9

10

11

FTG Cooler Dimensions

LIQUID AND SUCTION LINE PIPE SIZE

Model 

32°C Ambient

 

Liquid Line Pipe Size 

Suction Line Pipe Size

 

 

Horizontal (Vertical)

Duet 

20m 

50m 

20m       (V) 

50m       (V)

1-1 H/M 

3/8” 

3/8” 

1/2”       1/2” 

5/8”       1/2”

2-1 H/M 

3/8” 

3/8” 

5/8”       1/2” 

5/8”       1/2”

3-1 H/M 

3/8” 

3/8” 

5/8”       1/2” 

5/8”       1/2”

4-3 H/M 

3/8” 

3/8” 

7/8”       3/4” 

7/8”       3/4”

5-3 H/M 

3/8” 

3/8” 

7/8”       3/4” 

11/8”       7/8”

6-3 H/M 

3/8” 

3/8” 

11/8”       7/8”  11/8”       7/8”

1-1 L 

3/8” 

3/8” 

5/8”       1/2” 

3/4”       5/8”

2-1 L 

3/8” 

3/8” 

3/4”       5/8” 

7/8”       3/4”

3-3 L 

3/8” 

3/8” 

7/8”       3/4” 

7/8”       3/4”

4-3 L 

3/8” 

3/8” 

7/8”       3/4” 

11/8”       7/8”

5-3 L 

3/8” 

3/8” 

11/8”       7/8”  13/8”       11/8”

6-3 L 

1/2” 

1/2” 

13/8”       11/8”  13/8”       11/8”

Note: 

These are guidelines only.  Exact pipe sizing to be carried out for each application.

 

“H” models include HV and GP range

 

“M” models include C, F and M range

 

“L” models

 

The exact pipe size should be determined by application.

 

Recommended maximum vertical change 5 metres.  The suction lines have been selected to achieve a pressure drop of 2psi or less whilst maintaining refrigerant velocity in the horizontal 

plane of 3.5m/s (700ft/min) and in the vertical plane of 7.0m/s (1500ft/min) to achieve oil return.

Model 

43°C Ambient

 

Liquid Line Pipe Size 

Suction Line Pipe Size

 

 

Horizontal (Vertical)

Duet 

20m 

50m 

20m       (V) 

50m       (V)

1-1 H/M 

3/8” 

3/8” 

1/2”       1/2” 

5/8”       1/2”

2-1 H/M 

3/8” 

3/8” 

5/8”       1/2” 

5/8”       1/2”

3-1 H/M 

3/8” 

3/8” 

5/8”       1/2” 

5/8”       1/2”

4-3 H/M 

3/8” 

3/8” 

7/8”       3/4” 

7/8”       3/4”

5-3 H/M 

3/8” 

3/8” 

7/8”       3/4” 

11/8”       7/8”

6-3 H/M 

3/8” 

3/8” 

11/8”       7/8”  11/8”       7/8”

1-1 L 

3/8” 

3/8” 

5/8”       1/2” 

3/4”       5/8”

2-1 L 

3/8” 

3/8” 

3/4”       5/8” 

7/8”       3/4”

3-3 L 

3/8” 

3/8” 

7/8”       3/4” 

7/8”       3/4”

4-3 L 

3/8” 

3/8” 

7/8”       3/4” 

11/8”       7/8”

5-3 L 

3/8” 

3/8” 

11/8”       7/8”  13/8”       11/8”

6-3 L 

1/2” 

1/2” 

13/8”       11/8”  13/8”       11/8”

10

7

LIQUID AND SUCTION VALVE HEXAGONAL WRENCH SIZE

3/8” valve = 5mm

1/2” valve = 5mm

5/8” valve = 5mm

7/8” valve = 10mm

Summary of Contents for FKS 10-4

Page 1: ...T e c h n i c a l M a n u a l Duet Condensing Unit Cooler ...

Page 2: ...al management Product Support and Installation contractors are required to 1 Ensure that wherever possible waste is removed from the client s site where arrangements are in place all waste should be retumed to Foster Refrigerator s premises In certain circumstances waste may be disposed of on the clients site if permission is given if the client has arrangements in place for the type of waste 2 If...

Page 3: ...defrost heaters FKS Range with and without defrost heaters Control Panel Microprocessor Controller c w function indicators Ten metre sensing probes Component contactors Component circuit breakers Not included Interconnecting pipework Pipe installation Mechanical fasteners screws pipe clamps etc Refrigerant Mains supply wiring Lockable isolator switch White enclosure Remote alarm contacts Ancillari...

Page 4: ...4 Cooler Specification ...

Page 5: ... 50 3 2 6 2 9 7 27 20 1 x 400 3100 1 x 160 64 102 595 x 1075 x 532 10 22 DCU1 1L 0 75 R 404a 1 50 1 6 28 0 2 230 1 50 0 8 3 8 7 28 16 1 x 250 750 1 x 90 60 46 368 x 660 x 330 10 16 DCU2 1L 1 8 R 404a 1 60 2 5 28 0 2 230 1 50 1 4 8 6 16 40 20 1 x 300 1400 1 x 90 60 60 458 x 880 x 400 10 22 DCU3 3L 2 3 R 404a 1 60 2 5 28 0 2 400 3 50 1 8 4 5 6 2 25 16 1 x 300 1400 1 x 90 61 65 458 x 880 x 400 10 22 ...

Page 6: ...FKS Cooler Dimensions 6 ...

Page 7: ... pipe size should be determined by application Recommended maximum vertical change 5 metres The suction lines have been selected to achieve a pressure drop of 2psi or less whilst maintaining refrigerant velocity in the horizontal plane of 3 5m s 700ft min and in the vertical plane of 7 0m s 1500ft min to achieve oil return Model 43 C Ambient Liquid Line Pipe Size Suction Line Pipe Size Horizontal ...

Page 8: ... a single line appears on the display for 3 seconds to indicate the autotest period After this period the air temperature measured by the T1 probe is displayed It is strongly advised that before adjusting any Service Parameters a thorough understanding of the following instructions should be obtained LDU 15 CONTROLLER lae aux Check temperature set point Check set point by pressing the set button T...

Page 9: ...is 1 30 mins dEF is displayed during defrost and until the set time has elapsed after defrosting or until air temperature falls below the value setpoint hysteresis dtY Defrost type FAn Off cycle defrost ELE Electric heater defrost GAS Hot gas defrost doP Defrost optimisation con At regular intervals of drE hrs Acc Defrost timer only runs while evaporator temperature is below 0 C defrosting occurs ...

Page 10: ...lternate between ALM and air temperature while the alarm condition persists Display Parameter LDU151E B Duet High Temp Default Values Used in Panels F H L SCL Readout Scale 2 C 2 C SPL Minimum Temperature Set Point 05 0 SPH Maximum Temperature Set Point 01 8 SP Effective Temperature Set Point 03 2 HYS Hysteresis 3 3 CRT Compressor Rest Time minutes 10 2 CDC Compressor Regulation with T1 Fail 20 7 ...

Page 11: ... 23 24 25 26 DUET C F M L AND IC SERIES 00 OFF 01 Te FrS 02 Always ON Units Deg Deg Deg Min Min Sec Hrs Deg Min Min Min Flag Flag Min Deg Flag Deg Deg Min Flag Deg Deg Deg Flag 01 Mnemonic SPL SPh hYS coF con cdc crS drE dLi dto drP diS dtY doP Fct FrS Fid ALo Ahi AdL Ain oS1 oS2 oS3 SiM Adr Min Limit 50 SPL 01 00 00 00 00 01 01 00 00 01 FAn con 01 50 00 50 SPh 01 01 20 20 20 00 1 ELE 00 01 00 02 ...

Page 12: ...Cables for three phase supply Condensing Unit Unit Cooler Liq Line Solenoid 1mm2 3 core Evaporator Fan 1mm2 3 core Defrost Heater if fitted 1mm2 5 core Drain Line Heater 1mm2 3 core Wiring Diagram 00 838359 00 00 838362 00 See page 11 for model reference Compressor Fan 2 5mm2 5 core Supply In 230v 50 1 N Control Panel HP LP Switch 1mm2 3 core Optional Condenser Fan Pressure Switch Crankcase Heater ...

Page 13: ... of an oil separator should be considered especially on low temperature applications plus the position of the oil P trap and the size of the suction line to maximise oil return to the compressor 4 EVAPORATORS COOLERS FTG Range Ceiling Mounted These are used for small coldroom applications and are available for both high and low temperature conditions The low temperature models have defrost heaters...

Page 14: ...r Oldmedow Road King s Lynn Norfolk PE30 4JU England Tel 01553 691122 Fax 01553 691447 Website www fosterrefrigerator co uk E mail sales foster uk com a Division of ITW UK Ltd DUET TM 05 05 T e c h n i c a l M a n u a l ...