background image

 

6  

continue pressing both buttons until the display shows the temperature required then release both buttons.  
Use the same procedure to adjust all of the parameters displaying „-or‟. 

 
Fuzzy Logic is not incorporated in this model as no door switches are fitted. 

 

Controller parameters for models manufactured prior to March 1

st

 2006 

The parameter settings for the cabinets produced prior to March 1

st

 2006 can be altered to the following parameter 

lists and will function as described above. 
 

Note

 

Parameter FPC is not included. 

LCD 28CS4E-B (00-555735) Controller Parameter lists 

 

Note: as of 16-05-

2008 temperature set point „SP‟ set to +1°C for unit to operate b1°C and +3°C. 

 

Note: On early versions of the controller parameter „FPc‟ is not included in the set up, this will have no 
bearing on the operational function of the controller. 

 

Mnem. 

Definition 

Min. 

Max 

Default 

Dim. 

VALUES (A) 

ScL 

Readout scale 

1°C; 2°C; °F 

1°C 

flag 

SPL 

Minimum set point  [ I ] 

-30 

SPH 

-25 

°C 

SPh 

Maximum set point  [ I ] 

SPL 

30 

10 

°C 

SP 

Set point [ I ] 

SPL 

SPH 

-20 

°C 

hYS 

Thermostat hysteresis [ I ] 

0.1 

10 

2.5 

°K 

crt 

Minimum compressor rest time 

30 

min. 

cdc 

10 min. run cycle with PF1 

10 

min. 

cSd 

Compressor Stop delay after door open 

30 

min. 

dFr 

Defrost frequency  [ I ] 

24 

1/24h 

dLi 

Defrost end temperature 

-30 

30 

15 

°C 

20 

dto 

Maximum defrost duration 

120 

20 

min. 

20 

dty 

Defrost type 

FAN; ELE; GAS 

ELE 

flag 

OFF 

drn 

Drain down time 

30 

min. 

ddY 

Display control during defrost 

60 

10 

min. 

10 

Fid 

Fan operation in defrost 

NO 

YES 

NO 

flag 

YES 

Fdd 

Evaporator. Fan re-start 

-30 

30 

-50 

°C 

10 

Ftc 

Fan timed control [ I ] 

NO 

YES 

YES 

flag 

NO 

FPc 

Evaporator fan On / Off Ratio 

flag 

Atl 

Low temperature alarm 

-12 

°K 

-5 

Ath 

High temperature alarm 

12 

°K 

Atd 

Temperature alarm delay 

120 

30 

min. 

90 

Ado 

Door alarm delay 

30 

min. 

Aht 

Condenser HP Alarm 

70 

60 

°C 

60 

Ahm 

AHT alarm management 

NON; ALR; STP 

NON 

flag 

NON 

Acc 

Condenser cleaning 

52 

wks 

hdS 

Eco->Heavy Duty sensitivity 

flag 

11SM 

2nd parameter set management 

NON; MAN; HDD 

NON 

flag 

NON 

11SL 

Minimum set point  [ II ] 

-30 

IISH 

-25 

°C 

-25 

11SH 

Maximum set point  [ II ] 

IISL 

30 

10 

°C 

10 

11SP 

Set point [ II ] 

IISL 

IISH 

-20 

°C 

-20 

11HY 

Thermostat hysteresis [ II ] 

0.1 

10 

°K 

11dF 

Defrost frequency  [ II ] 

24 

1/24h 

11Ft 

Fan timed control [ II ] 

NO 

YES 

NO 

flag 

NO 

Sb 

Stand By button function 

NO 

YES 

YES 

flag 

YES 

dS 

Door switch enabling 

NO 

YES 

NO 

flag 

NO 

oAu 

AUX Output Control 

NON; 0-1; ALR 

ALR 

flag 

NON 

oS1 

Air probe offset 

-12.5 

12.5 

°K 

Summary of Contents for LL1/2H

Page 1: ...Foster Low Level Counters with LCD28 Controller Service Manual Re Issued Version July 2010 ISO 14001 ISO 9001...

Page 2: ...formation Make sure the power supply is turned off before making any electrical repairs To minimise shock and fire hazards please do not plug or unplug the unit with wet hands During maintenance and c...

Page 3: ...w Guidance is available from the Environment Agency on how to comply with the waste management duty of care 3 The following waste must be stored of separately from other wastes as they are hazardous t...

Page 4: ...70x368 566x670x139 357x570x487 566x670x139 566x670x368 566x670x139 Nett Capacity litres 140 140 222 140 279 279 Number of Drawers 1 2 2 2 4 2 Maximum Weight Load per drawer 40kg 40kg 40kg 40kg 40kg 40...

Page 5: ...al operating temperature will automatically cancel the alarm Possible Causes Evaporator fan not working Restricted airflow through airduct Evaporator iced up Compressor not working Low temperature ala...

Page 6: ...ay the value Exit from the info menu by pressing or is automatic after 6 seconds if no buttons are pressed To reset the temperature settings recorded in THI and TLO and the hours counted in CND access...

Page 7: ...n cycle with PF1 0 10 6 min 6 cSd Compressor Stop delay after door open 0 30 1 min 1 dFr Defrost frequency I 0 24 3 1 24h 4 dLi Defrost end temperature 30 30 15 C 20 dto Maximum defrost duration 1 120...

Page 8: ...g NO oS3 Condenser Probe offset 12 5 12 5 0 K 0 tLd Logging Temp Delay 1 30 5 min 5 Sim Display slowdown 0 100 3 exp 3 Adr Unit address 1 255 1 exp 1 Unit Diagrams Standard Low Level Counter Condensin...

Page 9: ...t the condensing unit Check the insulation of the thermostat If problem persists change the thermostat Control contacts are stuck closed Change the control Check amperage load Defective or incorrect t...

Page 10: ...er are tightened The evaporator and or condenser fans are loose Check if the fans are securely fastened Also check if the fan blades are loose broken or crooked If so change the faulty blade Compresso...

Page 11: ...y Ensure gaskets are snapped in completely Remove gasket and wash with soap and water Check condition of gasket replace if necessary Dirty condenser coil Clean condenser coil Evaporator coil iced over...

Page 12: ...osterfrance com Germany Foster Refrigerator Gmbh Tel 49 781 990 7840 Fax 49 781 990 7844 Email info foster gmbh de Foster Refrigerator Oldmedow Road Kings Lynn Norfolk PE30 4JU Tel 0843 216 8833 Fax 0...

Reviews: