4  

 

Check temperature set point.  

Important to note that the ability to increase and decrease the set point is not a function available to the user as the 
set point is fixed. To make adjustments to the set point it is necessary to access the parameter and alter SPL and 
SPH accordingly. 

 

Check set point by pressing the button 
 
To increase set point press 

until required temperature is displayed. 

 

To decrease set point press 

until required temperature is displayed. 

 

Factory Temperature Set Point 

Refrig1°C to +4°C 
Meat 0°C to 2°C. 
Freezer -18°C to -21°C. 
Exit from set up occurs after 10 seconds if no button is pressed.   

 

Manual Defrost. 

To initiate a manual defrost press and hold 

will be displayed release. 

 
On completion of the defrost 

will be displayed until the cabinet temperature is achieved and then it will 

revert to displaying the normal cabinet temperature. 

 

Set Unit to Standby. 
 
Press 

display shows  

 

Standby Indication 

This indication is displayed while the unit is not operating but with mains power applied to the unit. This mode may 
be used for internal cleaning regimes and short periods when the unit is not required. 
For extended periods of inactivity the mains supply should be isolated. 

 

Alarm and Warnings 

 

High temperature alarm  

 

Will be displayed. 
The alarm will sound but can be silenced by pressing any of the buttons, however it will return after the 

pre-set designated period. The unit returning to normal operating temperature will automatically cancel the alarm. 

Possible Causes: 

Evaporator fan not working. Restricted airflow through airduct. Evaporator iced up. Compressor 

not working. 

 

Low temperature alarm. 

 

Will be displayed. 

The  alarm  will  sound  but  can  be  silenced  by  pressing  any  of  the  buttons  and  the  unit  will  continue  to  operate, 
however  it  will  return  after  the  pre-set  designated  period.  The  unit  returning  to  normal  operating  temperature  will 
automatically cancel the alarm. 

Possible  Causes: 

Controller  faulty  (not  switching  compressor  off).  Compressor  secondary  relay  will  not  de-

energise (low temperature models). 

 

Door Open Alarm. 

(

Only applies to cabinets fitted with door switches

.)

  

 

Will be displayed. 

The alarm will sound but can be silenced by pressing.  
The display will continue to display the alarm message until cancelled by shutting the door. 
If the alarm cannot be cancelled by doing this call your Foster Authorised Service Company

Possible Causes: Faulty door switch. Door left open for more than 5minutes. 

 

High Pressure Alarm (Only applies to machines fitted with a condenser probe). 

 
Will be displayed 

This  alarm  relate  to  the  condenser  which  must  be  checked  and  cleaned  at  regular  intervals  the  frequency  being 
determined by site conditions.  
The  alarm  will  sound  but  can  be  silenced  by  pressing  any  of  the  buttons  and  the  unit  will  continue  to  operate, 
however  it  will  return  after  the  pre-set  designated  period.  The  unit  returning  to  normal  operating  temperature  will 
automatically cancel the alarm. 

Possible Causes: 

Condenser fan not working. Condenser blocked/ dirty. Condenser obstructed.

 

dEF 

HI 

LO 

REC 

OFF 

DO 

HP 

Summary of Contents for LL1/2H

Page 1: ...Foster Low Level Counters with LCD28 Controller Service Manual Re Issued Version July 2010 ISO 14001 ISO 9001...

Page 2: ...formation Make sure the power supply is turned off before making any electrical repairs To minimise shock and fire hazards please do not plug or unplug the unit with wet hands During maintenance and c...

Page 3: ...w Guidance is available from the Environment Agency on how to comply with the waste management duty of care 3 The following waste must be stored of separately from other wastes as they are hazardous t...

Page 4: ...70x368 566x670x139 357x570x487 566x670x139 566x670x368 566x670x139 Nett Capacity litres 140 140 222 140 279 279 Number of Drawers 1 2 2 2 4 2 Maximum Weight Load per drawer 40kg 40kg 40kg 40kg 40kg 40...

Page 5: ...al operating temperature will automatically cancel the alarm Possible Causes Evaporator fan not working Restricted airflow through airduct Evaporator iced up Compressor not working Low temperature ala...

Page 6: ...ay the value Exit from the info menu by pressing or is automatic after 6 seconds if no buttons are pressed To reset the temperature settings recorded in THI and TLO and the hours counted in CND access...

Page 7: ...n cycle with PF1 0 10 6 min 6 cSd Compressor Stop delay after door open 0 30 1 min 1 dFr Defrost frequency I 0 24 3 1 24h 4 dLi Defrost end temperature 30 30 15 C 20 dto Maximum defrost duration 1 120...

Page 8: ...g NO oS3 Condenser Probe offset 12 5 12 5 0 K 0 tLd Logging Temp Delay 1 30 5 min 5 Sim Display slowdown 0 100 3 exp 3 Adr Unit address 1 255 1 exp 1 Unit Diagrams Standard Low Level Counter Condensin...

Page 9: ...t the condensing unit Check the insulation of the thermostat If problem persists change the thermostat Control contacts are stuck closed Change the control Check amperage load Defective or incorrect t...

Page 10: ...er are tightened The evaporator and or condenser fans are loose Check if the fans are securely fastened Also check if the fan blades are loose broken or crooked If so change the faulty blade Compresso...

Page 11: ...y Ensure gaskets are snapped in completely Remove gasket and wash with soap and water Check condition of gasket replace if necessary Dirty condenser coil Clean condenser coil Evaporator coil iced over...

Page 12: ...osterfrance com Germany Foster Refrigerator Gmbh Tel 49 781 990 7840 Fax 49 781 990 7844 Email info foster gmbh de Foster Refrigerator Oldmedow Road Kings Lynn Norfolk PE30 4JU Tel 0843 216 8833 Fax 0...

Reviews: